Optigo OP10 user manual
Chapter 4
Installation and wiring
11
Wiring
This section only describes general rules and technical limitations concerning the wiring.
In chapter 5 there are specific wiring diagrams for the different control modes. Choose the
one suitable for the application on hand.
It is important to make sure that the wiring is correctly done, in accordance with the
instructions given in this manual and in accordance with local legislation for this type of
installation.
Supply voltage
OP10-230: 230 V AC +10%, -15%, 50/60 Hz. 6 VA
OP10: 24 V AC ±15%, 50/60 Hz. 6 VA
If the Optigo OP10 (24V supply model only) and actuators connected to it share transformer,
it is essential that the same transformer-pole is used as reference for all the equipment.
Failure to do so will prevent the equipment from functioning as intended and may also lead to
damages.
Inputs and outputs
A
GND
All A
GND
terminals are interconnected and also connected to G0.