Connect a Battery
WARNING
When you connect or disconnect the battery an electrical
arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
For Safety information on the handling of lithium
batteries, including handling and disposal of leaking
batteries, see Guidelines for Handling Lithium Batteries,
publication AG 5-4.
ATTENTION
To prevent possible battery leakage, even if the BAT LED
is off, replace a 1756-BA1 or 1756-BA2 battery according
to the following schedule:
ATTENTION
Store batteries in a cool, dry environment. We
recommend 25
°
C with 40%…60% relative humidity. You
may store batteries for up to 30 days between
-45
°
…85
°
C, such as during transportation. To avoid
leakage or other hazards,
do not
store batteries above
60
°
C for more than 30 days.
If the temperature 1 in.
below the chassis is:
Replace the battery within:
0
°
… 35
°
C
No required replacement
36
°
… 40
°
C
3 years
41
°
… 45
°
C
2 years
46
°
… 50
°
C
16 months
51
°
… 55
°
C
11 months
56
°
… 60
°
C
8 months
Содержание 1756-ENBT ControlLogix
Страница 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Страница 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Страница 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Страница 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...