ControlLogix™ DC (10-31.2V) Input Module
11
Publication
1756-IN031D-EN-P - February 2003
Assemble the Removable Terminal Block and the Housing
Install the Removable Terminal Block onto the Module
Before installing the RTB, make certain:
·
field-side wiring of the RTB has been completed.
·
the RTB housing is snapped in place on the RTB.
·
the RTB housing is closed.
·
the locking tab at the top of the module is unlocked.
!
WARNING
When you connect or disconnect the Removable Terminal Block
(RTB) with field side power applied, an electrical arc can occur.
This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
20852-M
Groove
Groove
Side edge of the RTB
Side edge of the RTB
Strain relief area
1.
Align the grooves at the bottom of the housing with the side edges of the RTB.
2.
Slide the RTB into the housing until it snaps into place.
20853–M
20854–M
Module
guide
RTB guides
Locking tab
1.
Align the side and top, bottom guides.
2.
Press quickly and evenly to seat the RTB
until the latches snap into place.
3.
To lock the RTB on the module,
slide the locking tab down.
Содержание 1756-ENBT ControlLogix
Страница 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Страница 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Страница 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Страница 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...