20
ControlLogix™ Voltage/Current Input Module
Publication
1756-IN039D-EN-P - February 2003
Module Scan Time for All
Channels (Sample Rate Module
Filter Dependent)
16 pt single ended - 16-488ms
8 pt differential - 8-244ms
4 pt differential - 5-122ms
RTB Screw Torque (Cage clamp)
4.4 inch-pounds (0.4Nm)
Module Keying (Backplane)
Electronic
RTB Keying
User defined
Field Wiring Arm and Housing
36 Position RTB (1756-TBCH or TBS6H)
(2)
Environmental Conditions
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
–40 to 85°C (–40 to 185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5 to 95% non-condensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz
Shock
IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g
Emissions
CISPR 11:
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
EFT/B Immunity
IEC 61000-4-4:
±2kV at 5kHz on signal ports
Содержание 1756-ENBT ControlLogix
Страница 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Страница 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Страница 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Страница 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...