59
Table 17 - Gas Heat Ignition Times
Time
Pre-Purge
5 sec
Inter-Purge
45 sec
Post Purge
5 sec
Ignition Trial
10 sec
Blower On Delay
30 sec
Blower Off Delay
120 sec
Lockout Recovery
60 min
Gas
Heater
Operating
and
Safety
Instructions
1. This furnace does not have a pilot. It is
equipped with a direct spark ignition device
that automatically lights the gas burner. DO
NOT try to light burners by hand.
2. BEFORE OPERATING, leak test all gas
piping up to heater gas valve. Smell around
the unit area for gas. DO NOT attempt to
place heater in operation until source of gas
leak is identified and corrected.
3. Use only hand force to push and turn the
gas control switch to the “ON” position.
NEVER use tools. If switch does not operate
by hand, replace gas valve prior to staring the
unit. Forcing or attempting to repair the gas
valve may result in fire or explosion.
4. Do not attempt to operate unit if there is
indication that any part or control has been
under water. Any control or component that
has been under water must be replaced prior
to trying to start the unit.
Shutdown
1. Set thermostat or controller to lowest
setting.
2. Turn off electrical supply to unit at
disconnect switch.
3. Turn off manual gas supply (supplied by
others).
4. Disconnect manifold and inlet pressure
taps and re-install pipe plugs.
5. Close module door.
Normal Operation
1. Turn on electrical supply to unit at
disconnect switch.
2. Turn on manual gas supply (supplied by
others).
3. Set Thermostat or Temperature controller
to desired temperature.
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
WARNING