25
A color-coded wiring diagram is laminated
and affixed to the inside of the control
compartment access door.
V3 Series units are equipped with a single
point power connection. Wire from the unit
to external controls and power sources must
be provided in the field.
3.
Connect Sections
Remove the access side panels by removing
the screws and pulling the panels off. Using
the V3 Schematic as an example, section 1
will have a duct flange, and it will connect to
section 2 on the side that does not have a
flange.
Apply ½” thick, 5/8” wide adhesive gasket
around the edges of the box without the
flanges.
Push section 1 and 2 together so that the
flange from section 1 is inside of section 2.
Figure 8 - Connect Sections
Use bar clamps or other non-destructive
winching device to pull the tops of the
modules together tightly.
Figure 9 - Bar Clamp
At each of the pre-drilled holes in the flange,
drill 5/16 hex head self-tapping screws to
secure the two sections together.
Figure 10 - Flange Overlap
Figure 11 - Self-Tapping Screw
4.
Re-attach Access Side Panels
5.
Final Sealing
It is very important to keep air from
infiltrating the unit cabinet. Seal all piping
penetrations with Armaflex, Permagum or
other suitable sealant. Also seal around drain
connections, electrical connections and all
other inlets where air may enter the cabinet.
This is especially important when the unit is
installed in an unconditioned area.
5/16” Hex Head
Self-Tapping Screws
Provided with Unit
1”
Installing Contractor is responsible for
proper sealing of the electrical and
piping entries into the unit. Failure to
seal the entries may result in damage
to the unit and property.
CAUTION
Section 2
Flange