37
clockwise direction to determine that wheel
rotates freely with slight drag on seals.
9. Reinstall bearing locking collar. Rotate
collar by hand in the direction the wheel
rotates (see label provided on each cassette
for wheel rotation).
10. Lock in position by tapping drift pin hole
with hammer and drift. Secure in position by
tightening set screw.
11. Reinstall Bearing Access Cover.
12. Apply power to wheel and ensure that the
wheel rotates freely without interference.
Figure 26 - Belt Replacement
Electrical
Verify the unit name plate agrees with power
supply. V3 Series units are provided with
single point power wiring connections.
Connection terminations are made to the
main terminal block. A complete set of unit
specific wiring diagrams, showing factory
and field wiring are laminated in plastic and
located inside the control compartment door.
Route power and control wiring, separately,
through the utility entry in the unit. Do not
run power and control signal wires in the
same conduit.
All units require field supplied electrical
overcurrent and short circuit protection.
Device must not be sized larger than the
Maximum Overcurrent Protection (MOP)
shown on the unit nameplate.
Codes may require a disconnect switch be
within sight of the unit.
It is recommended that the field installed
overcurrent protection or disconnect switch
not be installed on the unit.
The
foam
insulation
releases
dangerous fumes when it is burnt. Do
not cut a foam part with a cutting torch
or plasma cutter. Do not weld to a
foam filled part.
WARNING