50
Startup
(See back of the manual for startup form)
During startup, it is necessary to perform
routine checks on the performance of the unit.
This includes checking of the air flow, the air
filters and refrigerant charge.
Filters
Do not operate the unit without filters in
place. Operation of the equipment without
filters in place can result in clogged coils.
Units are shipped with the selected filters
installed. If filters have been removed during
installation, open the filter access door and
re-install the correct filters with the airflow
indicator arrows pointing in the direction of
airflow.
Filters should be checked after a few days of
operation after the unit has been started up as
dust and debris from construction may cause
premature filter loading. Replace the filters
if necessary.
Supply Fans
V3 Series units are equipped with direct drive
backward curved plenum supply fan
assemblies that deliver the air volume
specified according to unit size and job
requirements.
Fan Air Flow Adjustment
A specific air volume is delivered by the fans
with Electronically Commutated Motors
(ECM). Field air flow adjustment may be
required at startup.
Electrically Commutated Motor Airflow
Adjustment
Figure 34 - Typical wiring diagram with EC
motor
If the application is for the motor to run at a
constant speed, the potentiometer can be
utilized without any change. If the
application is to vary the motor speed for
changing conditions, remove the jumper
indicated on the terminal strip (red wire).
Improper
installation,
adjustment,
alteration, service or maintenance can
cause property damage, personal
injury or loss of life. Startup and
service must be performed by a
Factory Trained Service Technician. A
copy of this IOM should be kept with
the unit.
WARNING
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING