31
Table 8 - Drain Trap Dimensions (Metric)
Draw-Through
Drain Pan Pressure
Trap Dimensions
Negative Static
X
X/2
(centimeters of water)
(cm)
(cm)
-1.27
3.81
1.91
-2.54
5.08
2.54
-3.81
6.35
3.18
-5.08
7.62
3.81
-6.35
8.89
4.45
-7.62
10.16
5.08
-8.89
11.43
5.72
-10.16
12.70
6.35
Table 9 – Drain Trap Dimensions (Imperial)
Startup
(See back of the manual for startup form)
During startup, it is necessary to perform
routine checks on the performance of the unit.
This includes checking of the air flow, the air
filters and refrigerant charge.
Filters
Do not operate the unit without filters in
place. Operation of the equipment without
filters in place can result in clogged coils.
Units are shipped with the selected filters
installed. If filters have been removed during
installation, open the filter access door and
re-install the correct filters with the airflow
indicator arrows pointing in the direction of
airflow.
Check filters after a few days of operation
after the unit has been started up as dust and
debris
from
construction
may
cause
premature filter loading. Replace the filters
if necessary.
Supply Fans
H3 Series units are equipped with direct drive
backward curved plenum supply fan
assemblies that deliver the air volume
specified according to unit size and job
requirements.
Fan Air Flow Adjustment
On some H3 Series units, a specific air
volume is delivered by the fans with
Electronically Commutated Motors (ECM).
Field air flow adjustment may be required at
startup.
Draw-Through
Drain Pan Pressure
Trap Dimensions
Negative Static
X
X/2
(inches of water)
(in.)
(in.)
-0.50
1.50
0.75
-1.00
2.00
1.00
-1.50
2.50
1.25
-2.00
3.00
1.50
-2.50
3.50
1.75
-3.00
4.00
2.00
-3.50
4.50
2.25
-4.00
5.00
2.50
Improper
installation,
adjustment,
alteration, service or maintenance can
cause property damage, personal
injury or loss of life. Startup and
service must be performed by a
Factory Trained Service Technician. A
copy of this IOM must be kept with the
unit.
WARNING
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING