Set this function is used to test the current output frequency and
frequency deviation, the output terminal function set to 1 ( the signal
frequency reaches FAR ), when the output frequency of frequency
converter and the difference between the set frequency in P6.13
( frequency ) to check out the width range, the terminal output frequency
to signal ( FAR ) .
Table 7-11
P6.14 FDT1 level
Range: 0.00
~
650.00Hz
【
50.00Hz
】
P6.15 FDT1 lag
Range: 0.00
~
650.00Hz
【
1.00Hz
】
P6.16~P6.17 Reserved
Reserved
P6.14~P6.15 is a complement to the No.2 function in Table 7-8.
For example: when the inverter output frequency reaches FDT1 level, it
outputs an indicating signal until its output frequencydrops below FDT1
level ( FDT1 level-FDT1 lag ) .As shown in Figure 7-13.
Figure 7-13 Frequency Detection
7.8 Closed-loop PID control ( P7 )
0: Non Closeloop PID control
1: Closeloop PID control
0: Digital setting
P7.00 Close-loop PID control
Range: 0, 1
【
0
】
P7.01 Reference input method
Range: 0
~
4
【
0
】
FDT1
lag
Time
Time
Y
FDT1
level
Output frequency