FD Group: Professional function parameters 2 ( total 31 )   

Code 

Name 

Setting Scope 

Min 

Unit 

Defaulted 

Value 

Address 

Change 

PD.05 

Stage 3 

setting 

LEDUnits: 
0: Select mulit 
frequency 3 
( P8.02 )   
1: Frequnecy 
depends on 
thefunction code of 
P0.02 
LEDTens: 
0: Forward 
1: Reverse 
2: Subject to run 
command 

00 

D05H 

○ 

PD.06 

Stage 3 

run time 

0.0~6500 s ( min )   

0.1 

20.0s 

D06H 

○ 

PD.07 

Stage 4 

setting 

LEDUnits: 
0: Select mulit 
frequency 4 
( P8.03 )   
1: Frequnecy 
depends on 
thefunction code of 
P0.02 
LEDTens: 
0: Forward 
1: Reverse 
2: Subject to run 
command 

00 

D07H 

○ 

PD.08 

Stage 4 

run time 

0.0~6500 s ( min )   

0.1 

20.0s 

D08H 

○ 

PD.09~ 

PD.30 

Reserved 

D09H~ 

D1EH 

 

FE GROUP Reserves 21 parameters

 

Содержание DT100-2S0004G

Страница 1: ...A TS 1 https a ts cn en DT100 Series Inverter VFD AC Drive User Manual A TS TECHNOLOGY CORPORATION LIMITED mktg a ts cn...

Страница 2: ...tps a ts cn en DECLARATION Without written permission reprint or copy is strictly forbidden A TS Technology Corporation Limited All rights reserved Version Product Realse Date Note V 18 02 DT100 27 11...

Страница 3: ...nformation of DT100 series 18 4 2 3 Demision 19 4 2 4 LED Keypad Display Unit Size 19 4 2 5 Optional Parts 20 5 Installation and Wiring 21 5 1 Installation 21 5 2 Wiring 22 5 2 1 Overview 22 5 2 2 Pow...

Страница 4: ...parameters P8 59 7 10 Enhanced function P9 59 7 11 Display Control Parameters PA 63 7 12 Communication PB 64 7 13 Professional parameters PC 66 7 14 PLC parameters PD 66 7 15 Constant pressure water s...

Страница 5: ...toring Inverters 86 9 2 4 Warranty 86 10 Parameter profiles 87 11 Communication Protocal 121 11 1 Communication Mode 121 11 2 Protocol Format 121 11 3 Protocol Function 122 11 4 Instruction 128 11 5 T...

Страница 6: ...ction and capabilities of adapting severe power network temperature humidity and dusty environment which improves the products reliability markedly This manual provides guidance on installation wiring...

Страница 7: ...tains the inverter and user manual 2 Inspect the whole exterior of inverter to ensure there are no scratches or other damage caused by transportation If the inverter is damaged during transportation o...

Страница 8: ...s may cause fire severe injury or even death Operation without following instructions may cause medium or minor injury or property damage 3 2 Safety items Before installation DANGER Please do not inst...

Страница 9: ...r At wiring DANGER Wiring must be performed only by qualified personnel under instructions in this manual Improper operation may cause unexpected accidents A circuit breaker must be used between the p...

Страница 10: ...event the danger of electric shock Do not perform the voltage resistance pressure test on any part of the inverter because such test has been done in the factory Otherwise it will cause accidents All...

Страница 11: ...perature otherwise it may get burned Only qualified personnel shall detect the signal otherwise it may cause personal injury or equipment damage When the inverter is running please don t let any sundr...

Страница 12: ...m the inverter during the insulation test Please use 500V insulation tester to measure the insulation resistance It should not be less than 5M Thermal protection of the motor In model selection if the...

Страница 13: ...side rated voltage The inverter could not be used at an operating voltage out of the specified range If needed please use suitable voltage regulation device Try to change the three phase input into tw...

Страница 14: ...urpose RCD with relatively large residual current High leakage current warning The inverter generates high leakage current during running which flows through the PE conductor Earth connection must be...

Страница 15: ...aptive parameters for motors in the inverter According to the actual situation or requirements motor parameter recognition auto tuning needs to be performed or unique default value should be set in or...

Страница 16: ...d range 1 100 Starting torque 180 rated torque at 0 5Hz Accuracy of speed at steady state 0 5 rated synchronous speed Torque boost Auto torque boost Manual torque boost Acc Dec curve Linear Jog Jog fr...

Страница 17: ...otection Overheat and overload protection Environment Operating environment In door no direct sunlight no dust no corrosive gas or combustible gas no oil mist vapor drip or salinity Altitude Less than...

Страница 18: ...0 Input Code Three Phase T Single Phase Voltage Code 220V 2 380V 4 Code Type Constant torque G XX XX Special machine code GM Series changed to default Design version 0 99 0007 0 75 S Built in brake un...

Страница 19: ...including user manual after package 1 22KG 4 2 4 LED Keypad Display Unit Size Through it operation and configuration of the inverter can be done Please refer to its size and configuration in Figure 4...

Страница 20: ...each application However please remember that the braking resistance shouldn t be lower than the above suggested value but the power is allowed to be higher than the recommend numbers Users need to se...

Страница 21: ...ion free of direct sunlight dust metal powder corrosive gas or combustible gas 5 Mount in the location where vibration is less than 5 9m s 2 0 6g 6 Dust free floating fiber and metal particles 7 Insta...

Страница 22: ...Open collector signal P24 I V CN6 0 2 10V 0 4 20mA CN4 Power circuit Control ciruit P24 ON OFF CN 5 Multi function input 2 Multi function input 3 Multi function input 4 Multi function input 5 AI DT10...

Страница 23: ...is CN4 CN5 CN6 Control terminals functions are listed in Table 5 3 Jumper functions in 5 4 Be sure to set the jumper and wire the terminals properly It is recommended to use cable of section area bigg...

Страница 24: ...rmina ls Name Function Specification Communicati on 485 RS485communica tion port RS485 differential sign al Standard RS 485 communication port Please use twisted pair cable or shielded cable 485 RS485...

Страница 25: ...5 Can be defined as multi functional digital inputs see Section 7 6 Reference ground COM Optical isolator 2 way input input resistance 2k maximum input frequency 200Hz Input voltage range 9 30V PLC Co...

Страница 26: ...igital output signals please refer to Section 7 7 TA TB normally closed TA TC normally open Contact capacity 250Vac 2A COS 1 250Vac 1A COS 0 4 30 Vdc 1A The PLC terminal can sink or source current Wir...

Страница 27: ...X5 5V External controller Figure 5 4 Internal 24V wiring diagram drain Inverter internal 24V power supply is used and the external controller uses PNP transistors whose common emitters are connected...

Страница 28: ...power supply wiring drain External power supply wiring source Remember to disconnect PLC and P24 9 30V Shield grounded near the inverter PE 1 PLC Xi P24 COM 24V DC D2 5V 10 X5 5V External controller...

Страница 29: ...8 Multi function output terminal wiring1 Terminal Y1 can also use external power 9 30V supply DC9 30V DT100 COM Y1 P24 5V 24V Relay Figure 5 9 Multi function output terminal wiring2 Note Don t short t...

Страница 30: ...d diagram 6 1 1 Keypad Function Explanation Keys on the LED keypad display unit refer to the function of each key in Table 6 1 Table 6 1 Key function Key Name Function PRG Program Esc key To shift bet...

Страница 31: ...eaning Color Mark Status indicator ON the inverter is running OFF the inverter is no output Green RUN Frequency indicator ON current LED display is frequency Green Hz Current indicator ON current LED...

Страница 32: ...eters in menu level 3 The setting of parameter is presented in decimal DEC and hexadecimal HEX format If it is set in hexadecimal format each digit of the setting is independent to one another 6 1 4 M...

Страница 33: ...on zero value exit the editing status leave the inverter for five mins without any operation and the password you just set becomes effective Press the PRG button to enter the function codes setting it...

Страница 34: ...rved Reserved P0 02 Frequency source setting Range 0 6 0 0 Digital setting 1 set by or key Initial frequency is the value of P0 04 and it can be adjusted via and keys on the keypad 1 Digital setting 2...

Страница 35: ...f freq 50 00Hz When the frequency source setting method is defined as keypad digital setting P0 02 0 1 2 P0 04 is the initial value of frequency P0 05 Digital auxiliary frequency Range 0 00 650 00Hz 0...

Страница 36: ...ge as shown in Figure 7 1 as fb Max output voltage is the inverter output voltage when the inverter outputs base frequency as shown in Figure 7 1 as Vmax This corresponds to the rated voltage of the i...

Страница 37: ...2 P0 14 Reserved Reserved 7 2 Motor Parameter P1 P1 00 Reserved Reserved P1 01 Motor poles Range 2 14 4 P1 02 Rated power Range 0 4 1000kW depending on model P1 03 Rated current Range 0 1 999 9A depen...

Страница 38: ...tly P1 01 P1 03 When starting auto tuning to a standstill motor the stator resistance rotor resistance and the leakage inductance will be measured and the measured values will be written into P1 05 P1...

Страница 39: ...motor cannot break away from the load or you don t require much on motor control performance you can use stationary auto tuning or even disable the function You may input the values on the motor name...

Страница 40: ...Stop command it will stop outputting frequency and stop gradually relying on load inertia 2 Deceleration DC braking When the inverter receives Stop command it will reduce output frequency within prese...

Страница 41: ...ed Note For the occasion of big moment of inertia and a quick stop demand this feature can be 1 and connect the matching braking resistor achieve rapid downtime P2 14 Reserved Reserved 7 4 Flux vector...

Страница 42: ...e to the percentage of the maximum output voltage Figure 7 5 User Defined V F curve When VFD worked in low frequency setting torque boost value reasonablely to counteractthe output voltage reduction i...

Страница 43: ...nsation time constant To compensate filtering constant of frequency more less this value more faster the refreshing is P3 12 AVR function Range 0 1 2 0 0 Disabled 1 Always enabled 2 Disabled during de...

Страница 44: ...ncy 2 5 MS frequency 3 6 External fault normally open input 7 External fault normally closed input 8 Reset signal 9 Forward jog 10 Reverse jog 11 Coast to stop input 12 Frequency increase UP 13 Freque...

Страница 45: ...Clear counter record 43 Signal of triggering counter 44 Reserved 45 Reserved The functions are explained as follows 1 Foreward 2 Reverse 3 5 MS terminals 26 is MS frequency 4 If any three of P5 03 P5...

Страница 46: ...g operation command Jog frequency jog interval and jog Acc Dec time are defined in P9 05 P9 08 11 Coast to stop This function is the same with P2 08 however it is realized by terminal and convenient f...

Страница 47: ...ormally closed contact Note Different from function 6 7 the external interrupt signal will not cause alarm and the inverter will resume previous running once the signal removed 19 DC Braking DB If the...

Страница 48: ...which will come into effect regardless of P0 02 Table 7 4 Frequency Setting Mode Selection X3 X2 X1 Mode OFF OFF OFF None OFF OFF ON Digital setting 1 OFF ON OFF Digital setting 2 OFF ON ON Digital s...

Страница 49: ...will coast to stop and the inverter ready to run will be prohibited to start This function is mainly used as safety protection 38 Reserved 39 Reserved 40 Clear the setting of auxiliary reference freq...

Страница 50: ...minal control mode Range 0 3 0 This parameter defines four operating modes controlled by external terminals 0 2 wire operating mode 1 K1 K2 0 0 1 0 0 1 1 1 Command Stop REV FWD Stop Xi FWD Xi REV COM...

Страница 51: ...his case the corresponding parameter should be set at 16 3 wire operation Table 7 6 P5 09 P5 11Reserved Reserved P5 12 Filter constant Range 0 01 50 00s 0 50s P5 13 Reserved Reserved P5 14 Ratio of Mi...

Страница 52: ...LU 6 External stop command EXT 7 Higher limit of frequency FHL 8 Lower limit of frequency FLL 9 Zero speed running 10 Completion of simple PLC operation 11 PLC cycle completion indication 12 Preset c...

Страница 53: ...signal is given if the preset frequency is higher than lower limit of frequency and the operating frequency reaches the lower limit of frequency 9 Zero speed running The signal is given if the inverte...

Страница 54: ...inverter total operating time PN 01 reaches preset operating time PN 00 P6 04 AO output function Range 0 12 0 P6 05 P6 06 Reserved Reserved Table 7 9 Setting Function Range 0 Output freq before compen...

Страница 55: ...t gain Range 0 0 200 0 100 0 P6 09 P6 10 Reserved Reserved P6 11 Preset counting value Range P6 12 65535 0 P6 12 Specified counting value Range 0 P6 11 0 Frequency inverter through the number 43 funct...

Страница 56: ...650 00Hz 50 00Hz P6 15 FDT1 lag Range 0 00 650 00Hz 1 00Hz P6 16 P6 17 Reserved Reserved P6 14 P6 15 is a complement to the No 2 function in Table 7 8 For example when the inverter output frequency r...

Страница 57: ...03 Input filter Range 0 01 50 00s 0 50s P7 04 Feedback filter Range 0 01 50 00s 0 50s P7 05 Digital reference input Range 0 00 10 00V 0 00 P7 06 P7 07 Reserved Reserved P7 08 Min input Range 0 0 P7 1...

Страница 58: ...cle of feedback value The PI regulator calculates once in each sampling cycle The bigger the sampling cycle the slower the response will P7 15 Error limit Range 0 0 20 2 0 P7 15 is the max error betwe...

Страница 59: ...if not will cause unnecessary downtime 7 9 MS parameters P8 P8 00 MS freq 1 Range lower limit upper limit 5 00Hz P8 01 MS freq 2 Range lower limit upper limit 10 00Hz P8 02 MS freq 3 Range lower limit...

Страница 60: ...tive logic of X2 BIT2 Positive or negative logic of X3 BIT3 Positive or negative logic of X4 BIT0 Positive or negative logic of X5 BIT1 Reserved BIT2 Reserved BIT3 Reserved BIT0 Reserved BIT1 Reserved...

Страница 61: ...downtime 1 setting frequency reset after downtime Hundred auxiliary frequency superposition of polarity 0 Positive polarity Sum of main frequency and of auxiliary frequency is defined as set frequenc...

Страница 62: ...is keypad or serial port or 3 wire terminal 1 and 2 there is no RUN command at power on 3 If there is a Stop command the inverter will not start P9 31 P9 33 Reserved Reserved P9 34 Terminal filter ti...

Страница 63: ...A BIT0 Actual speed rpm BIT1 Set speed rpm BIT2 Reserved BIT3 BIT0 Output power BIT1 Output torque Reserved Figure 7 18 LED Displayed Parameter 1 Setting PA 00 and PA 01 define the parameters that ca...

Страница 64: ...cation One Ten Hun Thou Bit0 rdference freq Bit1 extemal counting value Bit2 actual speed rpm Bit3 prest speed rpm Bit0 actual line speed Bit1 preset line speed Bit2 VCI v Bit3 CCI v Bit0 analog close...

Страница 65: ...value represents the corresponding terminal state bit0 bit12 virtual terminal X1 and X5 NC NC NC NC Y1 NC TC NC PC virtual terminal is valid the actual terminal function is invalid virtual terminal eq...

Страница 66: ...rs PD Simple PLC is a multi speed generator through which the inverter can change frequency and direction according to the running time This function is realized through PLC programmable logic control...

Страница 67: ...un command 2 Maintain value of the last stage after 1 cycle The inverter holds the frequency and direction of the last stage after single cycle 3 Continuous cycle The inverter continues running cycle...

Страница 68: ...ill not be saved when poweroff and the inverter will start from the first stage after powerup 1 save The PLC state including the stage frequency run time will be saved when poweroff and the inverter w...

Страница 69: ...is MS frequency 3 see P8 00 P8 06 1 the frequency is determined by P0 02 7 15 Constant pressure water supply PE 7 16 Protection PL 0 Disabled The overload protection is disabled Be careful to use this...

Страница 70: ...n the inverter is decelerating the motor decreasing rate may be lower than that of the inverter output frequency due to the inertia of load At this time the motor will feed the energy back to the inve...

Страница 71: ...L 09 PL 09 0 When running in constant speed auto current limit is invalid PL 09 1 When running in constant speed auto current limit is valid PL 09 2 Auto current limit is valid all the time mode 1 PL...

Страница 72: ...curacy 5 7 18 Protection of Parameters PP User password can prevent unauthorized persons from checking and modifying the parameters PL 10 PL 13 Reserved Reserved PL 14 Fault type of the first two time...

Страница 73: ...lease learn the password by heart PP 01 is to set the mode of write in protection of parameters 0 All parameters are allowed to be changed 1 No parameters can be changed except the P0 04 and PP 01 2 N...

Страница 74: ...the Acc time V F curve is not suitable Check and adjust V F curve adjust torque boost or set the motor parameters correctly to ensure the normal auto torque boost works well Low AC supply voltage Chec...

Страница 75: ...ormal AC supply voltage Check the AC supply voltage Too short Acc time Prolong the Acc time The inverter is re started with a rotating motor Start when the motor stops F oU2 Over voltage in Dec proces...

Страница 76: ...Check and re wiring Output phase loss or some other reasons result in current waveform abnormalities Check the wiring Charge voltage damaged inverter voltage undervoltage Seek service Straight bridge...

Страница 77: ...Incorrect setting of motor overload protection factor Correct the setting Motor blocked or load sudden change Check the load F Ed Emergency stop or external equipment fails Press STOP key when operati...

Страница 78: ...board are loose Check and re wire Auxiliary power supply is damaged Seek service Current detection circuit fault Seek service F CPU System disturbance Severe disturbance from outside Press STOP RESET...

Страница 79: ...e reasons Actions F LoF PID feedback break line Abnormal PID feedback siganal Modify P7 29 Alarm parameters setting inproperly Check if PID wiring and feedback signal is normal F oLL Reserved Reserved...

Страница 80: ...technical support person Parameter setting cannot be changed Cannot be changed during operating Parameter modification property is Settings of parameters can be changed in stop status Settings of part...

Страница 81: ...function Simple PLC pause Check PLC pause function terminal Interrupt signal feedback from external devices Check the configuration of external interrupt and faulty external devices Reference frequenc...

Страница 82: ...ed length or clear the actual length The operation control terminal is not closed under 3 wire control mode Reset and close this terminal Faulty alarm Clear the fault Host virtual terminal set incorre...

Страница 83: ...e unexpected accidents may occur during operation The user should perform the routine maintenance to ensure a good operation environment according to the table below A good way to prolong the lifetime...

Страница 84: ...Whether the insulating tapes around the cable lugs are stripped 5 Clean the dust on FCBs and air ducts with a vacuum cleaner 6 For inverters that have been stored for a long time it must be powered o...

Страница 85: ...ce time 1 Cooling fan Possible cause of damages wear of the bearing aging of the fan vanes Criteria After the inverter is switched off check if an abnormal condition such as crack exists on fan vanes...

Страница 86: ...nty clause is confined to the inverter only 2 The warranty is 18 months since the production date In the warranty period A TS takes the responsibility for any faults or damages under the normal operat...

Страница 87: ...rameter is the actually measured value and cannot be changed It indicates that the parameter is Factory default parameter set only by the manufacturer and forbidden for users to change Address is the...

Страница 88: ...ame Setting Scope Min Unit Defaulte d Value Addres s Chang e P0 0 2 Frequency source setting 0 Digital setting 1 Up Down key 1 Digital setting 2 Terminal UP DN 2 Digital setting3 Serial communicatio n...

Страница 89: ...l value P0 05 4 Reserved 5 AI 6 Reserved 7 Reserved 8 AI 9 Reserved 10 Reserved 11 AI 5v 12 Reserved 13 Panel potentionmeter setting 1 0 003H P0 0 4 Keypad digital setting Low limit frequency upper li...

Страница 90: ...0s 0 1s 6s 00CH P0 1 3 Dec time 1 0 1 3600s 0 1s 6s 00DH P0 1 4 Reserved 00EH F1 GROUP Motor Parameter total 11 items Code Name Setting Scope Min Unit Defaulted Value Address Change P1 00 Reserved 100...

Страница 91: ...uto tuning 0 Auto tuning disable 1 Stationary auto tuning 2 Rotating auto tuning 1 0 10AH F2 Group Start Stop Parameter Total 15 items Code Name Setting Scope Min Unit Defaulted Value Address Change P...

Страница 92: ...13 Dynamic braking 0 Disabled 1 Enable 1 0 20DH P2 14 Reserved 20EH F3 GROUP Magnetic Flux Vector Control Parameters toal 15 items Code Name Setting Scope Min Unit Defaulted Value Addres s Chang e P3...

Страница 93: ...0 50 0 0 1 10 308H P3 09 P3 10 Reserved 309H 30AH P3 11 Compensatio n time 0 1 25 0s 0 1s 0 1s 30BH P3 12 AVR function 0 null 1 Effect all long 2 Null only deceleratio n 1 0 30DH P3 13 Reserved 30EH P...

Страница 94: ...quency3 6 External fault normally open input 7 External fault normally closed input 8 Failure reset input 9 Forwardjog 10 Reversejog 11 Coast to stop input 12 Frequency increasing input 13 Frequency d...

Страница 95: ...ormally closed input 19 DC injection braking input 20 Closeloop fairlure input 21 PLC failure input 22 Frequencysettin g method 1 23 Frequencysettin g method 2 24 Frequencysettin g method3 25 Reserved...

Страница 96: ...ed 505H 507H P5 08 Terminal control mode 0 Two lines 1 1 Two lines 2 2 Three lines 1 3 Three lines 2 1 0 508H P5 09 P5 11 Reserved 509H 50B H P5 12 Filter constant 0 01 50 00 0 01 s 0 50s 50CH P5 13 R...

Страница 97: ...curve1 0 00 P0 09 1 50 00Hz 511H P5 18 P5 21 Reserved 512H 515H F6 Group Output Terminal Control Parameter total 18 Code Name Setting Scope Min Unit Defaulted Value Address Change P6 00 Open collector...

Страница 98: ...6 External stop command EXT 7 Higher limit of frequency FHL 8 Lower limit of frequency FLL 9 Zero speed running 10 Completion of simple PLC operation 11 PLC cycle completion indication 12 Preset cout...

Страница 99: ...ax Output frequency 2 Set frequency 0 Max Output frequency 3 Output current 0 2 times of rated current of Inverter 4 Output current 0 2 times of rated current of motor 5 Output torque 0 2 times of rat...

Страница 100: ...0 20mA 1 2 10V or 4 20mA 1 00 607H P6 08 AO output gain 0 0 200 0 0 1 100 0 608H P6 09 P6 10 Reserved 609H 60AH P6 11 Preset counting value P6 12 65535 1 0 60BH P6 12 Specified counting value 0 P6 11...

Страница 101: ...method 0 Digital setting P7 05 value 1 Reserved 2 Reserved 3 LED keypad potentiomet er given 4 Reserved 1 0 701H P7 02 Reserved 702H P7 03 Input filter 0 01 50 00s 0 01 s 0 5s 703H P7 04 Feedback filt...

Страница 102: ...0 050 70CH P7 13 Integral gain Ki 0 000 9 999 0 00 1 0 050 70DH P7 14 Sampling cycle Ts 0 01 50 00s 0 01 s 0 50s 70EH P7 15 Error limit 0 0 20 0 0 1 2 0 70FH P7 16 Closed loop regulation characterist...

Страница 103: ...7 50 00Hz 806H P8 07 MS freq 8 Low limit frequency Upper limit ferquency 0 01Hz 50 00Hz 807H P8 08 MS freq 9 808H P8 09 MS freq 10 809H P8 10 MS freq 11 80AH P8 11 MS freq 12 80BH P8 12 MS freq 13 80C...

Страница 104: ...c time 0 1 60 0s 0 1 6s 907H P9 08 Jog Dec time 0 1 60 0s 0 1 6s 908H P9 09 P9 14 Reserved 909H 90EH P9 15 Positvie or negative logic of terminal LED Units Bit0 Bit3 X1 X4 LED Tens Bit0 X5 Bit1 Bit3 R...

Страница 105: ...l LED Units Storage control 0 power failure storage auxiliary frequency 1 power failure no storage auxiliary frequency LED Tens Halt frequency control 0 Maintain auxiliary frequency after halt 1 Reset...

Страница 106: ...matic run 1 run when power on 1 0 916H P9 23 P9 29 Reserved 917H 91DH P9 30 Conditions of restart after power failure 0 invalid 1 valid 1 0 91EH P9 31 P9 33 Reserved 91FH 921H P9 34 Terminal filter ti...

Страница 107: ...WM model optimization LED Units Carrier selection 0 Set the carrier 1 Default carrier LED Tens Carrier force 0 No force 1 Force LED Hundreds Modulation mode 0 Fiveections sev en sectionsutomati c swic...

Страница 108: ...er selection 1 Binary set 0 No displaying 1 Displaying LED Units Bit0 Output frequency before compensation Hz Bit1 Output frequency after compensation Hz Bit2 Setting frequency Hz blink Bit3 Output cu...

Страница 109: ...FA01 LED displayed parameter selection 2 Binary set 0 No Display 1 Display LED Units Bit0 Output voltage V Bit1 Barbus voltage Bit2 Reserved Bit3 AI V LED Tens Bit0 Analog closeloop feedback Bit1 Anal...

Страница 110: ...No display 1 Display LED Units Bit0 Set frequency Hz Bit1 External count Bit2 RUN SPEED RPM Bit3 Set speed RPM LED Tens Bit0 Reserved Bit1 Reserved Bit2 Reserved Bit3 AI V LED Hundreds Bit0 Analog cl...

Страница 111: ...tion LED Tens Data format 0 1 8 2 N format RTU 1 1 8 1 E format RTU 2 1 8 1 O format RTU LED Hundreds Virtual input terminals 0 Invalid 1 Valid 1 4 B00H PB 01 Local address 0 247 0 is broadcast addres...

Страница 112: ...e Address Change PD 00 Simple PLC mode LED Units PLC run mode 0 no action 1 Stop after ending single running 2 keep the final value when single running ends 3 Continuous circulation LED Tens Start mod...

Страница 113: ...P8 00 1 Frequnecy depends on thefunction code of P0 02 LED Tens 0 Forward 1 Reverse 2 Subject to run command 1 00 D01H PD 02 Stage 1 run time 0 0 6500 s min 0 1 20 0s D02H PD 03 Stage 2 setting LED Un...

Страница 114: ...efunction code of P0 02 LEDTens 0 Forward 1 Reverse 2 Subject to run command 1 00 D05H PD 06 Stage 3 run time 0 0 6500 s min 0 1 20 0s D06H PD 07 Stage 4 setting LEDUnits 0 Select mulit frequency 4 P8...

Страница 115: ...motor low speed compensation 2 Varible frequency motor No low speed compensation 1 2 1100H PL 01 Motor overload protection factor 20 0 110 0 1 100 0 1101H PL 02 stall overvola ge 0 Disable 1 Enable 1...

Страница 116: ...PL 09 Action mode of autocurre nt limit 0 Constant speed invalid 1 Constant speed effective 2 Automatic current limit valid in run state 1 3 Reserved 4 Reserved 5 Automatic current limit valid in run...

Страница 117: ...lt type of the previous time run at acceleration F oC1 2 Overcurrent run at deceleration F oC2 3 Overcurrent run at constant speed F oC3 4 Overvoltage run at acceleration F oU1 5 Overvoltage run at de...

Страница 118: ...oad on Inverter F oL1 14 Overload on motors F oL2 15 External fault F Ed 16 EEPROM read write error F EEP 17 Serialport communication abnormal F 485 18 Reserve 19 Abnormal circuit currentin spection F...

Страница 119: ...the last fault 0 0 120 0 0 1 0 1114H PL 21 Reserved 1115H FN Group Parameter Protection total 4 Code Name Setting Scope Min Unit Defaulted Value Address Change PN 00 Preset operation time 0 65 535 kHo...

Страница 120: ...frequency and the function code can be revised 2 Only the function code can be revised 1 0 1301H PP 02 Parameter initialization 0 No action 1 Eliminate malfunction records PL 14 PL 19 2 Restore factor...

Страница 121: ...lave drive address Function code Data cheksum Modbus Data frame RTU mode End at least3 5 bytes idle time Modbus adopts Big Endian encoding firstly transmitting high byte then low byte RTU Mode In RTU...

Страница 122: ...Parameters of the inverter Function code control parameters and status parameters are mapped to Modbus read write register Read write nature and scope of function code parameters comply with specific...

Страница 123: ...protocol Data Unit Data length number of bytes Values or range Function code 1 0x03 Initial register address 2 0x0000 0xFFFF Register number 2 0x0001 0x0004 Response format as below Application layer...

Страница 124: ...e Function code 1 0x06 Register address 2 0x0000 0xFFFF Register contents 2 0x0000 0xFFFF Response format is as follows Application layer protocol Data Unit Data length number of bytes Values or range...

Страница 125: ...rol seting No 0x320A Set acceleration time 1 Yes 0x320B Set deceleration time 1 Yes DT100 inverter state parameter index Register address Parameter name 0x3300 Running status word 1 0x3301 The practic...

Страница 126: ...d 0x331C Set acceleration time 1 0x331D Set deceleration time 1 0x331E Command given channel 0 Panel control 1 Terminal control 2 Serial port control 0x331F Inverter status word 2 0x3320 Frequency giv...

Страница 127: ...celeration deceleration Bit7 1 Host computer control valid The control word sent by the current FC is effective 0 Host computer control invalid The control word sent by the current FC is invalid Bit8...

Страница 128: ...communication back to be normal 2 Inverter internal parameters P1 10 PP 03 cannot be modified through communication setting 3 Writing FP 00 can verify the user password after the success of the authe...

Страница 129: ...e 0x4F70 Read 1 Inverter output current the Inverter responds output current of 30 0 A internally donote to be 300 address Function Code Register address Register number or read number of bytes Regist...

Страница 130: ...A TS 130 https a ts cn en D Output power is its absolute value E Other issues such as input and output terminals etc please refer to the user manual The End...

Страница 131: ...7786417742 Email mktg a ts cn service a ts cn For Users or end customers please contact your local supplier or A TS service center directly Because improvements or other reasons the product specificat...

Отзывы: