5. Installation and Wiring
5.1 Installation
1. Mount the inverter vertically indoors, with good ventilative conditions.
2.Ambient temperature should be within the range of-10
℃
~ 40
℃
. If the
temperature is higher than 40
℃
, the inverter should be derated and
forced heat dissipation is required.
3. Humidity should be lower than 90
%
, non-condensing;
4. Mount in the location free of direct sunlight, dust, metal powder,
corrosive gas or combustible gas;
5.Mount in the location where vibration is less than 5.9m/s
2
( 0.6g ) ;
6. Dust-free, floating fiber and metal particles;
7. Install flat solid, no vibration;
8. Away from electromagnetic interference source.
10kV
Power
transformer
Motor
Metal
cabinet
AC input reactor
Metal cabinet
PLC
or
meters
Circuit breaker
Filter
AC output
reactor
>30cm
>50cm
Inverter
Motor cable
Control cables
>20cm
Power source
cable of inverter
Isolation transformer
Power source
cable of meters
Figure 5-1 Installation of the inverter