7. Parameters
Note
:
The contents in the“
【】
”are factory defaults.
7.1 Basic Parameters ( P0 )
P0.00 Command channel
Range: 0
~
2
【
0
】
DT100 has 3 kinds of command channels:
0: LED keypad display unit, use RUN and STOP key on the keypad to
control the inverter.
1: Terminal control: Input operating commands via terminals. Use
terminals FWD, REV, to start and stop the inverter.
2: Serial communication port control.
P0.01 Reserved
Reserved
P0.02 Frequency source setting
Range: 0
~
6
【
0
】
0: Digital setting 1,set by
▲or▼key.
Initial frequency is the value of P0.04 and it can be adjusted via
▲ and
▼keys on the keypad.
1: Digital setting 2 set by terminal UP/DN.
Initial frequency is the value of P0.02 and it can be adjusted via terminal
UP/DN.
2: Digital setting 3, set through serial communication port.
Initial frequency is the value of P0.04 and it can be adjusted via serial
communication port.
3: Reserved
4: The reference frequency is set by AI input ( 0
~
10V/0
~
20mA ) , the
frequency calculation curve is given in P5.10~P5.21
5: Reserved
6: Keypad Potentiometer Setting