frequency
650.00H
【
50.00Hz
】
P0.10 Max output
voltage
Range: 1
~
480V
【
Inverter rated
】
Figure 7-1 Characteristic parameters definition
The max frequency refers to the allowed max output frequency of the
inverter. Refer to the f
max
in Figure 7-1;
Base frequency normally corresponds with the rated frequency of the
motor. It is the Min frequency when the inverter outputs the highest
voltage, as shown in Figure 7-1 as f
b
Max output voltage is the inverter output voltage when the inverter
outputs base frequency, as shown in Figure 7-1 as V
max
. This
corresponds to the rated voltage of the inverter
The f
H
and f
L
are defined by P0.07 and P0.08 as upper limit and lower
limit of frequency respectively.
P0.11 Running direction
Range: 0, 1
【
0
】
The function is used to select motor direction of rotation when running in
keypad control mode.
0: Forward
1: Reverse
In two wire terminal control mode, you can switch motor direction of
rotation by change this parameter value.
f
max
Output voltage
f
b
f
H
f
L
V
max