36
CoDe
DeSCripTioN
reCoMMeNDeD TroUbleShooTiNG oF
loCKoUT CoDeS
NoTe
212
Invalid Preignition time setting
1.
Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2.
If fault repeats, verify electrical grounding.
3.
If fault repeats, replace module.
L
213
Invalid Prepurge rate setting
L
214
Invalid Prepurge time setting
L
215
Invalid Purge rate proving setting
L
216
Invalid Run flame failure response setting
L
217
Invalid Run stabilization time setting
L
218
Invalid Stack limit enable setting
L
219
Invalid Stack limit response setting
L
220
Unconfigured Delta T limit setpoint setting
L
221
Unconfigured DHW high limit setpoint setting
L
222
Unconfigured Outlet high limit setpoint setting
L
223
Unconfigured Stack limit setpoint setting
L
224
Invalid DHW demand source setting
L
225
Invalid Flame threshold setting
L
226
Invalid Outlet high limit setpoint setting
L
227
Invalid DHW high limit setpoint setting
L
228
Invalid Stack limit setpoint setting
L
229
Invalid Modulation output setting
L
230
Invalid CH demand source setting
L
231
Invalid Delta T limit delay setting
L
232
Invalid Pressure sensor type setting
L
233
Invalid IAS closed response setting
L
234
Invalid Outlet high limit enable setting
Contact the service professional.
L
235
Invalid Outlet connector type setting
Contact the service professional.
L
236
Invalid Inlet connector type setting
Contact the service professional.
L
237
Invalid DHW connector type setting
Contact the service professional.
L
238
Invalid Stack connector type setting
Contact the service professional.
L
239
Invalid S2 (J8-6) connector type setting
Contact the service professional.
L
240
Invalid S5 (J8-11) connector type setting
Contact the service professional.
L
241
Exchanger sensor not allowed with stack
connector setting
Not Applicable.
L
242
Invalid DHW auto detect configuration
Not Applicable.
L
243
Invalid UV with spark interference not compatible
with Ignitor on throughout PFEP
Contact the service professional.
L
244
Internal fault: Safety relay test invalid state
Contact the service professional.
L
245
Invalid Outlet connector type setting for Trise
Contact the service professional.
L
246
4-20mA cannot be used for both modulation and
setpoint control
Contact the service professional.
L
247
Invalid ILK bounce detection enable
Not Applicable.
L
248
Invalid forced recycle interval
Not Applicable.
L
249
STAT cannot be demand source when Remote
Stat is enabled
Not Applicable.
L
250
Invalid Fan speed error response
1.
Check fan cables secured properly. If fault
persists contact the service professional.
L
251-255
RESERVED