To support the recommended Troubleshooting, the R7910 has an Alert File. Review the Alert history for possible trends that may have
been occurring prior to the actual Lockout.
Note Column: H= Hold message; L=Lockout message; H or L= either Hold or Lockout depending on Parameter Configuration.
TAble 9. TroUbleShooTiNG CoDeS
CoDe
DeSCripTioN
reCoMMeNDeD TroUbleShooTiNG oF
loCKoUT CoDeS
NoTe
Safety Data Faults
1
Unconfigured safety data
1.
New Device, complete device configuration and
safety verification.
2.
If fault repeats, replace module.
L
2
Waiting for safety data verification
1.
Device in Configuration mode and safety
parameters need verification and a device needs
reset to complete verification.
2.
Configuration ended without verification, re enter
configuration, verify safety parameters and reset
device to complete verification.
3.
If fault repeats, replace module.
L
Internal Operation Errors
3
Internal fault: Hardware fault
Internal Fault.
1.
Reset Module.
2.
If fault repeats, replace module.
H
4
Internal fault: Safety Relay key feedback error
H
5
Internal fault: Unstable power (DCDC) output
H
6
Internal fault: Invalid processor clock
H
7
Internal fault: Safety relay drive error
H
8
Internal fault: Zero crossing not detected
H
9
Internal fault: Flame bias out of range
H
10
Internal fault: Invalid Burner control state
L
11
Internal fault: Invalid Burner control state flag
L
12
Internal fault: Safety relay drive cap short
H
13
Internal fault: PII shorted to ILK
H or L
14
Internal fault: HFS shorted to LCI
H or L
15
Internal fault: Safety relay test failed due to
feedback ON
L
16
Internal fault: Safety relay test failed due to safety
relay OFF
L
17
Internal fault: Safety relay test failed due to safety
relay not OFF
L
18
Internal fault: Safety relay test failed due to
feedback not ON
L
19
Internal fault: Safety RAM write
L
20
Internal fault: Flame ripple and overflow
H
21
Internal fault: Flame number of sample mismatch
H
22
Internal fault: Flame bias out of range
H
23
Internal fault: Bias changed since heating cycle
starts
H
24
Internal fault: Spark voltage stuck low or high
H
25
Internal fault: Spark voltage changed too much
during flame sensing time
H
26
Internal fault: Static flame ripple
H
27
Internal fault: Flame rod shorted to ground
detected
H
28
Internal fault: A/D linearity test fails
H
29
Internal fault: Flame bias cannot be set in range
H
TroUbleShooTiNG