35
CoDe
DeSCripTioN
reCoMMeNDeD TroUbleShooTiNG oF
loCKoUT CoDeS
NoTe
164
Block intake ON
OEM Specific
1.
Check wiring and correct any errors.
2.
Inspect the Block Intake Switch to make sure it is
working correctly.
3.
Reset and sequence the module.
4.
During Standby and Purge, measure the voltage
across the switch. Supply voltage should
be present. If not, the Block Intake Switch is
defective and needs replacing.
5.
If the fault persists, replace the relay module.
L
165
Block intake OFF
L
166-171 RESERVED
Feedback
172
Main relay feedback incorrect
Internal Fault.
1.
Reset Module.
2.
If fault repeats, replace module.
L
173
Pilot relay feedback incorrect
L
174
Safety relay feedback incorrect
L
175
Safety relay open
L
176
Main relay ON at safe start check
L
177
Pilot relay ON at safe start check
L
178
Safety relay ON at safe start check
L
179-183 RESERVED
Parameter Faults
184
Invalid BLOWER/HSI output setting
1.
Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2.
If fault repeats, verify electrical grounding.
3.
If fault repeats, replace module.
L
185
Invalid Delta T limit enable setting
L
186
Invalid Delta T limit response setting
L
187
Invalid DHW high limit enable setting
L
188
Invalid DHW high limit response setting
L
189
Invalid Flame sensor type setting
L
190
Invalid interrupted air switch enable setting
L
191
Invalid interrupted air switch start check enable
setting
L
192
Invalid igniter on during setting
L
193
Invalid ignite failure delay setting
L
194
Invalid ignite failure response setting
1.
Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2.
If fault repeats, verify electrical grounding.
3.
If fault repeats, replace module.
L
195
Invalid ignite failure retries setting
L
196
Invalid ignition source setting
L
197
Invalid interlock open response setting
L
198
Invalid interlock start check setting
L
199
Invalid LCI enable setting
L
200
Invalid lightoff rate setting
L
201
Invalid lightoff rate proving setting
L
202
Invalid Main Flame Establishing Period time
L
203
Invalid MFEP flame failure response setting
L
204
Invalid NTC sensor type setting
L
205
Invalid Outlet high limit response setting
L
206
Invalid Pilot Flame Establishing Period setting
L
207
Invalid PII enable setting
L
208
Invalid pilot test hold setting
L
209
Invalid Pilot type setting
L
210
Invalid Postpurge time setting
L
211
Invalid Power up with lockout setting
L