background image

16

leAD lAG (ll) MASTer GeNerAl operATioN

The XP Boiler is a multiple burner application and it works on 

the basis of the Lead Lag Operation. The XB Boiler is factory 

configured for Hydronic/Central Heating application, whereas the 

XW Boiler is factory configured for Domestic Hot Water application. 

 

The LL master coordinates the firing of its slave Control Systems. 

To do this it adds and drops stages to meet changes in load, and 

it sends firing rate commands to those that are firing.
The LL master turns the first stage on and eventually turns the 

last  stage  off  using  the  same  criteria  as  for  any  modulation 

control loop:
• 

When  the  operating  point  reaches  the  Setpoint  minus  the 

On hysteresis, then the first Control System is turned on.

• 

When the operating point reaches the Setpoint plus the Off 

hysteresis then the last slave Control System (or all slave 

Control Systems) are turned off.

The  LL  master  PID  operates  using  a  percent  rate:  0%  is  a 

request for no heat at all, and 100% means firing at the maximum 

modulation rate.
This firing rate is sent to the slaves as a percentage, but this is

apportioned to the slave Control Systems according to the rate 

allocation  algorithm  selected  by  the  Rate  allocation  method 

parameter.
For  some  algorithms,  this  rate  might  be  common  to  all  slave 

Control Systems that are firing. For others it might represent the 

total system capacity and be allocated proportionally.
For example, if there are 4 slaves and the LL master's percent 

rate is 30%, then it might satisfy this by firing all four slaves at 

30%, or by operating the first slave at 80% (20% of the system’s 

capacity)  and  a  second  slave  at  40%  (10%  of  the  system’s 

capacity).
The LL master may be aware of slave Control System’s minimum 

firing  rate  and  use  this  information  for  some  of  its  algorithms, 

but when apportioning rate it may also assign rates that are less 

than this. In fact, the add-stage and drop-stage algorithms may 

assume this and be defined in terms of theoretical rates that are 

possibly lower than the actual minimum rate of the Burner Control 

System. A Control System that is firing and is being commanded 

to fire at less than its minimum modulation rate will operate at 

its minimum rate: this is a standard behavior for a Buner control 

system in stand-alone (non-slave) mode.

If any slave under LL Master control is in a Run-Limited condition, 

then  for  some  algorithms  the  LL  master  can  apportion  to  that 

stage  the  rate  that  it  is  actually  firing  at.  Additionally  when  a 

slave imposes its own Run-limited rate, this may trigger the LL 

Master to add a stage, if it needs more capacity, or drop a stage 

if  the  run-limiting  is  providing  too  much  heat  (for  example  if  a 

stage is running at a higher-than commanded rate due to anti-

condensation).
By  adjusting  the  parameters  in  an  extreme  way  it  is  possible 

to  define  add-stage  and  drop-stage  conditions  that  overlap  or 

even cross over each other. Certainly it is incorrect to do this, 

and  it  would  take  a  very  deliberate  and  non-accidental  act  to 

accomplish it. But there are two points in this:

1. 

LL master does not prevent it, and more important;

2. 

It will not confuse the LL master because it is implemented 

as a state machine that is in only one state at a time;

DoMeSTiC hoT WATer

Start-up sequence DHW-request (system in standby):

1. 

Heat  request  detected  (either  DHW  Sensor  Only,  DHW 

Sensor  and  Remote  Command  or  DHW  Switch  and  Inlet 

Sensor, whichever applies).

2. 

The pump is switched on (after the DHW Pump Start Delay).

3. 

After a system Safe Start Check, the Blower (fan) is switched 

on after a dynamic ILK switch test (if enabled).

4. 

After the ILK switch is closed and the purge rate proving fan 

RPM is achieved (or High Fire Switch is closed) - prepurge 

time is started.

5. 

When  the  purge  time  is  complete,  the  purge  fan  RPM  is 

changed to the Lightoff Rate or if used, the damper motor is 

driven to the Low Fire Position.

6. 

As soon as the fan-rpm is equal to the light-off rpm (or the 

Low Fire Switch closes), the Trial for Ignition or Pre-Ignition 

Time is started (depending on configuration).

7.  Pre-Ignition  Time  will  energize  the  ignitor  and  check  for 

flame.

8. 

Trial for Ignition. Specifics for timings and device actions are 

defined by the OEM or installer.

9. 

The ignition and the gas valve are switched on.

10. 

The  ignition  is  turned  off  at  the  end  of  the  direct  burner 

ignition  period,  or  for  a  system  that  does  use  a  pilot,  at 

the  end  (or  optionally  at  the  middle)  of  the  Pilot  Flame 

Establishing Period (PFEP). For an interrupted pilot system 

this is followed by a Main Flame Establishing Period (MFEP) 

where the pilot ignites the main burner. For an intermittent 

pilot there is no MFEP.

11. 

The  fan  is  kept  at  the  lightoff  rate  during  the  stabilization 

timer, if any.

12. 

Before  the  release  to  modulation,  the  fan  is  switched  to 

minimum  RPM  for  the  DHW  Forced  Rate  and  Slow  Start 

Enable, if the water is colder than the threshold.

13. 

At the end of the DHW-heat request the burner is switched 

off and the fan stays on until post purge is complete.

14. 

A new DHW-request is blocked for the forced off time set by 

the Anti Short Cycle (if enabled).

15. 

The  pump  stays  on  during  the  pump  overrun  time  (if 

enabled).

16. 

At  the  end  of  the  pump  overrun  time  the  pump  will  be 

switched off.

leAD lAG

Burner Control System devices contain the ability to be a stand-

alone control, operate as a Lead Lag Master control (which also 

uses  the  burner  control  function  as  one  of  the  slaves),  or  to 

operate solely as a slave to the lead lag system.
Control  System  devices  utilize  two  ModBus™  ports  (MB1 

and  MB2)  for  communications.  One  port  is  designated  to 

support  a  system  S7999B  display  and  the  other  port  supports 

communications from the LL Master with its slaves. 
The Lead Lag master is a software service that is hosted by a 

Control System. It is not a part of that control, but is an entity 

that is “above” all of the individual burner controls (including the 

one that hosts it). The Lead Lag master sees the controls as a 

set of Modbus devices, each having certain registers, and in this 

regard it is entirely a communications bus device, talking to the 

slave buner controls via Modbus.
The LL master uses a few of the host Buner Control's sensors 

(header  temperature  and  outdoor  temperature)  and  also  the 

STAT electrical inputs in a configurable way, to provide control 

information.

Содержание XB-1000

Страница 1: ...damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any ap...

Страница 2: ...hanger Maintenance 46 Handling Ceramic Fiber Materials 47 Replacement Parts 47 NOTES 48 LIMITED WARRANTY 49 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFE INSTALLATION USE AND SERVICE 3 APPROVALS 3 GENERA...

Страница 3: ...rt symbol indicates a potentially hazardous situation which if not avoided could result in property damage All safety messages will generally tell you about the type of hazard what can happen if you d...

Страница 4: ...etup and instructions before lighting Failure to implement the proper setup will result in improper and inefficient operation of the appliance resulting in production of increased levels of carbon mon...

Страница 5: ...on Institute INTRODUCTION Qualifications Qualified Installer or Service Agency Installation and service of this boiler requires ability equivalent to that of a Qualified Agency as defined by ANSI belo...

Страница 6: ...ion circulation pump control fan control boiler control sequencing and electric ignition function It will also provide status and error reporting Figure 1 BURNER Control System SPARK IGNITER The spark...

Страница 7: ...E SENSORS All models have two inlet and two outlet temperature sensors for each heat exchanger factory installed to monitor the water temperature entering and leaving the boiler The Inlet Probe is a t...

Страница 8: ...s drain valve by turning handle clockwise 2 Open a nearby hot water faucet to permit the air to escape 3 Fully open the cold water inlet pipe valve allowing the boiler and piping to be filled 4 Close...

Страница 9: ...a local code or state law requiring a specific temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfie...

Страница 10: ...10 LIGHTING AND OPERATING INSTRUCTIONS...

Страница 11: ...d gas air control and gas safety shut off control valves The valve functions in parallel with the variable speed combustion blower to supply the correct gas air ratio for optimum performance and effic...

Страница 12: ...M as described below Check combustion readings using a combustion analyzer If combustion readings are not in accordance with the chart shown below adjust as follows remove the cap on the gas regulator...

Страница 13: ...tion with the primary system heat loop Priority assignment to each heat loop can be configured to specify which loop gets serviced first CONTROL SYSTEM Burner Control System Figure 15 R7910A1138 contr...

Страница 14: ...after programmed number of retry attempts d Main valve terminal is energized e Internal system fault occurred Communications and displays Two modes of communications are available to the R7910 1 The...

Страница 15: ...16 At the end of the pump overrun time the pump will be switched off 6 MAIN FLAME ESTABLISHING PERIOD MFEP a Lockout Interlock opens if enabled b Pilot valve terminal is not energized c Main valve ter...

Страница 16: ...1 LL master does not prevent it and more important 2 It will not confuse the LL master because it is implemented as a state machine that is in only one state at a time Domestic Hot Water Start up sequ...

Страница 17: ...ntime or Use Last If one or more Control Systems are in the Use First category then one of these the one with the lowest sequence number will always be the first boiler to fire If there is no Control...

Страница 18: ...ns 1 Electrical Ratings 12 VDC input maximum of 500 mA current drain Included Power Supply for S7999B Inputs 85 to 264 VAC 47 to 63 Hz 120 to 370 VDC Output 12 VDC 0 to 2 1 A Power 25 W 2 Operating Te...

Страница 19: ...Function see Figure 20 The page descriptions are provided below so that you can understand the purpose of each and view the selections parameters and information that is available or required on each...

Страница 20: ...20 Figure 21 s7999B display page flow...

Страница 21: ...ters The parameter name is displayed on the left and the current setting is displayed in the text box on the right Status or Home Page A status summary page Figure 22 is displayed when the S7999B disp...

Страница 22: ...ord Three levels of access to Burner Control parameters are permitted Each access level has defined rights when interfacing with configuration and status parameters within the controls End user The en...

Страница 23: ...of all parameters in each safety block must be verified to save them in the control When the installer is done changing safety parameters pressing the Verify button on the configuration screen begins...

Страница 24: ...ontrol Alert Log DATA COMMENT Alert Line Set by display Alert Code Unique Code defining which fault occured Description Alert description History Button The History button on the Home page serves not...

Страница 25: ...the history page lockout history and alert log The entire 15 fault code history is displayed in a scrollable list with the most recent fault displayed first followed by the next most recent fault Sum...

Страница 26: ...unciation information and switch between hydronic heating loops Central Heat and Domestic Hot Water as shown in Figure 37 If a password is required to change any of the settings on this page the user...

Страница 27: ...al I O status of the Burner Control A snapshot of the diagnostic status is displayed and updated once per second as it changes in the control The digital I O data is displayed as LEDs that are either...

Страница 28: ...A O Smith Each functional group is displayed on the Configuration menu page Parameters in functional groups that are not applicable for the installation can be ignored In some cases features in a func...

Страница 29: ...tput H 6 Internal fault Invalid processor clock H 7 Internal fault Safety relay drive error H 8 Internal fault Zero crossing not detected H 9 Internal fault Flame bias out of range H 10 Internal fault...

Страница 30: ...not match application s model ID Contact the service professional L 55 Application configuration data block CRC errors Contact the service professional L 56 57 RESERVED 58 Internal fault HFS shorted t...

Страница 31: ...nd Outlet sensors and pump circuits for proper operation 2 Recheck the Delta T Limit to confirm proper setting 3 If previous steps are correct and fault persists replace the module H or L 82 Stack lim...

Страница 32: ...at the flame detector is wired to the correct terminal 3 Make sure the F G wires are protected from stray noise pickup 4 Reset and sequence the module if code reappears replace the flame detector 5 Re...

Страница 33: ...ignition H or L 131 Fan movement detected during standby H 132 Fan speed failed during run H 133 135 RESERVED Start Check Faults 136 Interrupted Airflow Switch failed to close 1 Check wiring and corr...

Страница 34: ...present If not the lockout switch is defective and needs replacing 5 If the fault persists replace the relay module H or L 153 Combustion pressure Off H or L 154 Purge Fan switch On OEM Specific 1 Pu...

Страница 35: ...ting L 186 Invalid Delta T limit response setting L 187 Invalid DHW high limit enable setting L 188 Invalid DHW high limit response setting L 189 Invalid Flame sensor type setting L 190 Invalid interr...

Страница 36: ...nvalid Outlet high limit enable setting Contact the service professional L 235 Invalid Outlet connector type setting Contact the service professional L 236 Invalid Inlet connector type setting Contact...

Страница 37: ...overridden due to sensor fault 70 No demand source was set due to demand priority conflicts 71 73 RESERVED Code Description EE Management Faults 0 None No alert 1 Alert PCB was restored from factory d...

Страница 38: ...source parameter was invalid 151 Minimum water temperature parameter was greater than setpoint Code Description Fan Parameter Errors 74 Periodic Forced Recycle 75 Absolute max fan speed was out of ra...

Страница 39: ...225 226 RESERVED 227 DHW priority override time was not derated due to invalid outdoor temperature 228 Warm weather shutdown was not checked due to invalid outdoor temperature 229 Lead Lag slave commu...

Страница 40: ...Abnormal Recycle Ignition failed due to interrupted air flow switch was off 303 Abnormal Recycle ILK off during Drive to Purge Rate Code Description 231 Lead Lag CH setpoint was invalid 232 Lead Lag...

Страница 41: ...cle Hardware flame bias dynamic low 380 Abnormal Recycle Fan Speed Not Proven 381 Abnormal Recycle Fan Speed Range Low Code Description 304 Abnormal Recycle ILK off during Measured Purge Time 305 Abno...

Страница 42: ...Mix S10 J10 7 temperature was invalid 522 Mix outlet temperature was invalid 523 Mix inlet temperature was invalid 524 Mix S5 J8 11 temperature was invalid 525 Mix modulation sensor type was invalid...

Страница 43: ...alid 541 Delta T exchanger outlet enable was invalid 542 Delta T inlet exchanger enable was invalid 543 Delta T inlet outlet degrees was out of range 544 Delta T exchanger outlet degrees was out of ra...

Страница 44: ...eration during initial ignition operation and extinction Cause no excessive lifting of flame from burner ports MAINTENANCE PROCEDURES Maintenance schedules Yearly procedures for Qualified Service Agen...

Страница 45: ...main burners from unit 3 Check that burner ports are free of foreign matter 4 Clean burner with vacuum cleaner Do not distort burner ports 5 Reinstall burners in unit Ensure that all the screws on the...

Страница 46: ...condensate drains and tubes at least once a month and insure they will allow the free flow of condensate at all times The system must be inspected more frequently in cold weather if the drain system i...

Страница 47: ...fiber materials Removal of combustion chamber lining The combustion chamber insulation in this appliance contains ceramic fiber material Ceramic fibers can be converted to cristobalite in very high t...

Страница 48: ...48 NOTES...

Страница 49: ...er under state or provincial law are limited to one 1 year duration for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warrant y lasts so the...

Страница 50: ...25589 Highway 1 McBee SC 29101 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: