Instruction manual SGE
33
is
Concentric roof flue terminal specifications C33
3.10.4
Parallel connections
The table states the maximum pipe lengths for parallel systems. The maximum
pipe length depends on the chosen diameter.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre towards
the water heater.
Chimney flue requirements for parallel systems
You must use the longest pipe when calculating the pipe length. For example, if
the chimney pipe is 4 metres and the air supply pipe is 3 metres, use 4 metres
as the length for the calculation. Next, add the L
equivalent
for
every
90° and 45°
bend to this 4 metres, in
both
the air supply and flue gas outlet. The following
practical example illustrates how to use the table.
Practical example of parallel flue gas discharge
Example
The figure shows a SGE 60 installation. This has to be fitted with a 4
m parallel
pipe 100
mm in diameter, plus four 90-degree bends. The configuration must be
checked for compliance with the requirements stated in the table.
Subject
Description
Roof flue terminal set:
•
1x roof flue terminal
(incl.
clamping ring)
•
1x pipe 1000 mm
•
1x
m
ounting flange
Art. No.
0304 423
1
Construction
Concentric
Manufacturer
Muelink & Grol
Model
M2000 DDV HR-C
Pipe material
Construction
Concentric
Flue gas discharge
Thick-walled aluminium with lip ring seal
Air supply
Thin-walled galvanised sheet steel
Pipe diameters
Flue gas discharge
Ø 100 mm
Air supply
Ø 150 mm
(1)
No other roof flue terminal may be used. Use this item number to order the roof flue terminal set from the
supplier
, manufacturer or wholesalor.
Appliance
Diameter
1
Maximum
total
length
L
equivalent
90
o
bend
L
equivalent
45
o
bend
SGE 40
100
55 m
4.6 m
1.2 m
SGE 60
100
55 m
4.6 m
1.2 m
SGE 40
130
100 m
2.4 m
1.4 m
SGE 60
130
100 m
2.4 m
1.4 m
1) Parallel systems with diameter of 100
mm. If the maximum total length when
using a diameter of 130
mm is insufficient, a diameter of 150
mm must be
used.
Any diameter enlargement must be carried out on both air supply and
flue gas
outlet.
Содержание SGE - 40
Страница 7: ...4 Instruction manual SGE gis ...
Страница 11: ...Contents 8 Instruction manual SGE ...
Страница 33: ...Installation 30 Instruction manual SGE 3 is Installation types IMD 0789 R0 C43 C13 C53 B23 C33 ...
Страница 51: ...Conversion to a different gas category 48 Instruction manual SGE 4 is ...
Страница 59: ...Draining 56 Instruction manual SGE 6 gis ...
Страница 65: ...Status of the water heater 62 Instruction manual SGE 8 gis ...
Страница 69: ...Shutting down 66 Instruction manual SGE 10 gis ...
Страница 83: ...Instruction manual SGE 80 is ...
Страница 99: ...is Instruction manual SGE 96 ...
Страница 101: ...Service interval 98 Instruction manual SGE 14 is ...
Страница 110: ...Instruction manual SGE 107 is ...
Страница 115: ...Appendices 112 Instruction manual SGE 17 is 17 5 Declaration of conformity Declaration of conformity ...
Страница 117: ...Instruction manual SGE 114 ...