background image

7

IMPORTANT: When making condensation connections 
to the primary connection DO NOT over tighten. 
Overtightening could crack or damage the condensate 
drain pan.
• 

Plastic pipe or tubing must be used to connect the 
condensate drain to a suitable drain or condensate 
pump. 

• 

Condensate drain lines should be installed in 
conditioned areas only. Install approved insulation on 
the condensate drain lines to prevent condensation 
from forming on the outside of the drain lines. 
Condensation drain lines installed in areas that are 
subject to freezing temperatures should be wrapped 
with a nationally recognized/listed heat tape. Install per 
manufacturer’s instructions. 

• 

Do not connect condensate drain lines with other drain 
or discharge lines into a single (common) pipe or line. 
Each line (condensate drain line, temperature and 
pressure relief valve discharge pipe, etc) should be 
independently run to an adequate drain.

• 

Slope the condensate drain lines toward the inside 
floor drain or condensate pump.

• 

The condensate drain lines and connections to the 
drain piping must comply with all local codes.

• 

Use appropriate fittings, primer and glue to cement the 
condensate drain lines to the heat pump drain pan.

• 

If a condensate pump is installed it should shut off the 
heat pump in the event the condensate pump fails or  
the float switch in the pump activates. (See section 
on Condensate Pump Overflow Shut Off Switch in the 
Electrical Requirements section.)

Closed System/Thermal Expansion

Explosion Hazard

If the temperature and pressure relief valve 
is dripping or leaking, have a qualified 
person replace it.

Examples of a qualified person include:
licensed plumbers, authorized electric 
company personnel, and authorized service 
personnel.

Do not plug valve.

Do not remove valve.

Failure to follow these instructions can 
result in death or explosion.

WARNING

Most public water systems in North America are required 
to prevent water flowing from points of use (residences, 
businesses, etc.) back into the supply system in order 
to maintain water quality. To accomplish this, back flow 
preventers such as check valves, are installed in the water 
line going to each point of use. Typically the back flow 
preventer will be installed at the water meter or inside a 
building where the supply line enters the building. This 
device allows water to flow into the residence but does 
not allow it to flow back into the water supply. This creates 
what is known as a “Closed System”. As water is heated 
by the water heater, the water in the system attempts to 
expand, but has nowhere to go resulting in an increase 
in pressure. This increase in pressure in the system may 
cause the temperature-pressure relief valve to open to 
relieve the pressure. Water will drip from the temperature 
and pressure relief valve. Premature tank failure will result 
if this condition is not corrected. To prevent this condition, a 
properly-sized thermal expansion tank should be installed 
in the cold water supply to the water heater as shown in 
Figure 4. Failure to install a properly sized expansion tank 
in a closed system will void the warranty on the water 
heater in the event of tank failure. It is important to follow 
the thermal expansion tank manufacturers’ installation 
instructions and to adjust the expansion tank pressure 
to match the water supply pressure. Contact a plumbing 
service agency or your retail supplier regarding the 
installation of a thermal expansion tank.

Figure 8
Temperature and Pressure
Relief Valve Installation

Temperature and 
Pressure Relief Valve

Discharge Pipe
(Do Not Plug or Cap)

Drain Pan 2 1/2”
Depth Maximum and 
2” wider than the 
water heater

Drain Line 3/4”
ID Minimum

Drain

6” Maximum 
Air Gap

Temperature and Pressure 
Relief Valve

Содержание Hybrid ElectricHeat Pump Water Heater

Страница 1: ...on 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Water System Piping 5 6 Temperature Pressure Relief Valve 7 8 Electrical Requirements 8 9 Installation Checklist 10...

Страница 2: ...not been used for a long period of time 2 weeks or more Hydrogen gas is extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened fo...

Страница 3: ...When referring to your water heater always have the information listed on the data plate readily available to include the model and serial number Retain your original receipt as proof of purchase Basi...

Страница 4: ...e and install this product After installation dispose of recycle all packaging materials Location Requirements Site location Select a location near the center of the water piping system The unit must...

Страница 5: ...water heater in a closed water system install an expansion tank in the cold water line as specified under Closed System Thermal Expansion 6 Install a shut off valve in the cold water inlet line It sh...

Страница 6: ...7 8 Turn on electrical power to the water heater 9 Select the efficiency mode After about 8 minutes the user interface module will display repetitively during this period the heat pump will turn on if...

Страница 7: ...valve Failure to follow these instructions can result in death or explosion WARNING Most public water systems in North America are required to prevent water flowing from points of use residences busin...

Страница 8: ...te of the water heater The Discharge Line Shall not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Shall not be capped blocked plugged...

Страница 9: ...ces rated at 30 amperes Figure 10 Junction Box Power Supply Connector Black Wire Red Wire Green Ground Wire 1 2 Conduit Opening Green Ground Screw The conduit or tubing is terminated in fittings appro...

Страница 10: ...roperly installed and free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section...

Страница 11: ...cess panel Reset the ECO by firmly pushing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature R...

Страница 12: ...not operate Similarly if the water temperature in the tank is less than 59 F 15 C the heat pump will not operate The unit will operate in electric mode until ambient and water temperatures return to...

Страница 13: ...ounts of noise and may cause premature tank failure Drain and flush the tank as directed under the Draining and Flushing section 3 The heat pump compressor or fan running Stacking Stacking occurs when...

Страница 14: ...the water tank 3 Drain approximately 5 gallons of water from the tank Refer to Draining and Flushing for proper procedures Close drain valve 4 Remove old anode rod 5 Use Teflon tape or approved pipe...

Страница 15: ...the water heater annually After servicing this water heater check to make sure it is working properly See Operating Your Water Heater section of this manual IMPORTANT If you lack the necessary skills...

Страница 16: ...the ones specified for the upper and or lower element IMPORTANT Using an element greater than 4500 watts will damage the water heater and void the warranty 1 Turn off the power to the water heater 2...

Страница 17: ...r E11 Heat Pump Coil Temperature Sensor is not functioning E40 or E41 Heat Pump Discharge Temperature Sensor is not functioning Edr Not enough water in the tank tank not full Fill completely Open all...

Страница 18: ...connection is at the top 5 Insulate exposed piping 6 Repair hot water leaks 7 Call qualified person for service 8 Drain and flush tank Water conditioning may be necessary to minimize build up HIGH OPE...

Страница 19: ...perature Sensor 13 Upper Lower Tank Temperature Sensor 14 Fan Shroud 15 Condensate Drain Connection Cover 16 Electronic Expansion Valve Coil 17 Start Capacitor 18 Relay Kit REPAIR PARTS Repair parts m...

Страница 20: ...20 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2014 Inc All Rights Reserved...

Отзывы: