background image

17

DIAGNOSTIC CODES 

DISPLAY SHOWS

INDICATES

CORRECTIVE ACTION

EUC

Upper element is not functioning

1.  Turn off power at the circuit breaker/fuse box and check for 

a loose connection at the element. For access directions 

see “Heating Element Replacement” section. If error persists 

proceed to the next step.

2.  Replace non-functioning element. See “Heating Element 

Replacement” section.

ELC

Lower element is not functioning

1.  Turn off power at the circuit breaker/fuse box and check for 

a loose connection at the element. For access directions 

see “Heating Element Replacement” section. If error persists 

proceed to the next step.

2. Replace 

non-functioning

 element. See “Heating Element 

Replacement” section. 

SF

The air filter is dirty.

1.  Turn off power at the circuit breaker/fuse box.

2.    Clean the air filter. See “Air Filter Cleaning/Replacement” 

section. 

ECF

The heat pump compressor is 

starting/stopping frequently.

1.  Turn off power at the circuit breaker/fuse box.

2.  Clean the air filter. See “Air Filter Cleaning/Replacement” 

section.

3.  If error persist, please contact a qualified person to check the 

fan wire connection.

E20 or E21

Upper Temperature Sensor is not 

functioning.

Contact a qualified person to service the unit.

E30 or E31

Lower Temperature Sensor is not 

functioning.

E50 or E51

Heat Pump Suction Temperature 

Sensor is not functioning.

E10 or E11

Heat Pump Coil Temperature 

Sensor is not functioning.

E40 or E41

Heat Pump Discharge  

Temperature Sensor is not 

functioning.

Edr

Not enough water in the tank 

(tank not full).

Fill completely-Open all hot water taps in home and run until water 

(uninterupted) flows from all open hot water taps.

EPL

Power supply voltage is too low.

Check the power supply to the unit and make sure it is higher than 

204V

EDH

Heat Pump Discharge 

Temperature is too high.

Contact a qualified technician to service the unit. 

EoF
(If Accessory Condensate 
Pump is installed)

Condensate pump failure.

1.  Check to see if accessory condensate pump is plugged in and 

has power. Also check circuit breaker/fuse box and GFCI (if 

used). If error persists, proceed to the next step.

2.  Check condensate pump outlet tube for blockage. If error 

persists, proceed to the next step.

3.  Check control wire connections to condensate pump. If error 

persists, proceed to the next step.

4.  Replace accessory condensate pump. If error persists, contact 

a qualified technician to service the unit.

ECL

Heat pump suction pressure is 

too low.

Contact a qualified technician to service the unit

EEE

EEPROM failure

ECC

Heat pump compressor is not 

functioning.

“-”,”--”,”---”

Unit is doing a system diagnostic.

No action is necessary.

ICE

Heat pump is in defrosting cycle.

HPO

Heat pump is out of operation 

envelope.

NOTE:

 The diagnostic codes listed above are the most common. If a diagnostic code not listed above is displayed, 

contact Residential Technical Assistance referencing the number on the front of this manual.

Содержание Hybrid ElectricHeat Pump Water Heater

Страница 1: ...on 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Water System Piping 5 6 Temperature Pressure Relief Valve 7 8 Electrical Requirements 8 9 Installation Checklist 10...

Страница 2: ...not been used for a long period of time 2 weeks or more Hydrogen gas is extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened fo...

Страница 3: ...When referring to your water heater always have the information listed on the data plate readily available to include the model and serial number Retain your original receipt as proof of purchase Basi...

Страница 4: ...e and install this product After installation dispose of recycle all packaging materials Location Requirements Site location Select a location near the center of the water piping system The unit must...

Страница 5: ...water heater in a closed water system install an expansion tank in the cold water line as specified under Closed System Thermal Expansion 6 Install a shut off valve in the cold water inlet line It sh...

Страница 6: ...7 8 Turn on electrical power to the water heater 9 Select the efficiency mode After about 8 minutes the user interface module will display repetitively during this period the heat pump will turn on if...

Страница 7: ...valve Failure to follow these instructions can result in death or explosion WARNING Most public water systems in North America are required to prevent water flowing from points of use residences busin...

Страница 8: ...te of the water heater The Discharge Line Shall not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Shall not be capped blocked plugged...

Страница 9: ...ces rated at 30 amperes Figure 10 Junction Box Power Supply Connector Black Wire Red Wire Green Ground Wire 1 2 Conduit Opening Green Ground Screw The conduit or tubing is terminated in fittings appro...

Страница 10: ...roperly installed and free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section...

Страница 11: ...cess panel Reset the ECO by firmly pushing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature R...

Страница 12: ...not operate Similarly if the water temperature in the tank is less than 59 F 15 C the heat pump will not operate The unit will operate in electric mode until ambient and water temperatures return to...

Страница 13: ...ounts of noise and may cause premature tank failure Drain and flush the tank as directed under the Draining and Flushing section 3 The heat pump compressor or fan running Stacking Stacking occurs when...

Страница 14: ...the water tank 3 Drain approximately 5 gallons of water from the tank Refer to Draining and Flushing for proper procedures Close drain valve 4 Remove old anode rod 5 Use Teflon tape or approved pipe...

Страница 15: ...the water heater annually After servicing this water heater check to make sure it is working properly See Operating Your Water Heater section of this manual IMPORTANT If you lack the necessary skills...

Страница 16: ...the ones specified for the upper and or lower element IMPORTANT Using an element greater than 4500 watts will damage the water heater and void the warranty 1 Turn off the power to the water heater 2...

Страница 17: ...r E11 Heat Pump Coil Temperature Sensor is not functioning E40 or E41 Heat Pump Discharge Temperature Sensor is not functioning Edr Not enough water in the tank tank not full Fill completely Open all...

Страница 18: ...connection is at the top 5 Insulate exposed piping 6 Repair hot water leaks 7 Call qualified person for service 8 Drain and flush tank Water conditioning may be necessary to minimize build up HIGH OPE...

Страница 19: ...perature Sensor 13 Upper Lower Tank Temperature Sensor 14 Fan Shroud 15 Condensate Drain Connection Cover 16 Electronic Expansion Valve Coil 17 Start Capacitor 18 Relay Kit REPAIR PARTS Repair parts m...

Страница 20: ...20 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2014 Inc All Rights Reserved...

Отзывы: