background image

6

Please note the following: 
• 

The system should be installed only with piping that is 
suitable for potable (drinkable) water such as copper, 
CPVC, PEX or polybutylene. This water heater must 
not be installed using iron piping or PVC water piping.

• 

Use only pumps, valves, or fittings that are compatible 
with potable water.

• 

Use only full flow ball or gate valves. The use of valves 
that may cause excessive restriction to water flow is 
not recommended.  

• 

Use only 95/5 tin-antimony or other equivalent solder. 
Any lead based solder must not be used.

• 

Piping that has been treated with chromates, boiler 
seal, or other chemicals must not be used.

• 

Chemicals that may contaminate the potable water 
supply must not be added to the piping system.

Connecting the Condensate Pump 
Optional Overfl ow Shut Off Switch 

1.  Determine if you have a floor drain, if not a condensate 

pump will be required.

2.  Turn off power to the electrical wiring for the water 

heater at the circuit breaker/fuse box.

3.  Locate the white 18 AWG wire loop close to the drain 

connections (Figure 5).

4.  Cut the loop and strip insulation off of the two ends.

5.  Measure the distance from the condensate drain pan 

cover to the condensate pump, and cut two 18 AWG or 
larger wires to correct length and strip the insulation at 
both ends of each wire (Figure 7). 

6.  Remove the condensate drain pan cover by removing 

the four screws, pull these two wires through the 
grommet on the drain pan cover. Connect these two 
wires to the two wires on the water heater using wire 
nuts or other connectors. Reinstall the drain pan cover 
and keep the connection joint inside of the cover.

7.  Connect the free ends of the two wires to the shut off 

switch on the condensate pump in accordance with the 
condensate pump manufacturers recommendations 
(Figure 7). 

8.  Turn on electrical power to the water heater.

9. S

elect the efficiency mode. After about 8 minutes 

(the user interface module will display “-”, “--”, “---” 
repetitively during this period), the heat pump will turn 
on if the ambient temperature and water temperature 
meet the heat pump requirement.

10.  Test the operation of the shut off switch by unplugging 

the condensate pump and filling the condensate 
reservoir with water until the float switch opens the 
circuit.

11.  The heat pump should turn off and the error code “EoF” 

will appear on the display screen.

12.  Plug the condensate pump in and verify that the pump 

operates and pumps the water out of the condensate 
reservoir.

13.  The error code on the display should clear and the heat 

pump should operate after 8 minutes.

Condensate Drain Line Installation

The condensate drain lines consist of one 3/4" PVC line as 
the primary condensate drain line and one 1/2" clear rubber 
tubing for the condensate over flow. These condensate 
lines are located on the upper right rear section of your 
water heater. The lines should terminate a maximum of 
six inches above an adequate drain. Do not discharge 
the condensate drain lines into the metal drain pan. If no 
floor drain is available or the drain is above the level of the 
condensate line, a condensate pump should be installed. 
These pumps are available from local distributors. 
When installing the drain line, note the following:

Figure 5
Condensate Pump Wiring 

Overflow Slot 

Main Drain Connection 

Condensate Drain 
Access Cover 

Condensate Pump Wiring 
Loop 18 AWG-White
(Loop Located Close to the Drain Connections)

Red

Black

Approved Connectors

Figure  6
Wiring Diagram

Overload
Protection

To 240v

1 Phase

Power supply

Electrical
Service ground

L1

L2

Circuit
Breaker

Ground
Wire

Green

Figure 7
Condensate Pump Wiring 

Condensate Pump Wiring Loop

22 AWG - White

(Loop Located Close to the Drain Connections)

White Wires

From Water Heater

 Wires to Condensate 

Pump Overflow 

Shut Off Switch

(22 AWG or Larger)

Содержание Hybrid ElectricHeat Pump Water Heater

Страница 1: ...on 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Water System Piping 5 6 Temperature Pressure Relief Valve 7 8 Electrical Requirements 8 9 Installation Checklist 10...

Страница 2: ...not been used for a long period of time 2 weeks or more Hydrogen gas is extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened fo...

Страница 3: ...When referring to your water heater always have the information listed on the data plate readily available to include the model and serial number Retain your original receipt as proof of purchase Basi...

Страница 4: ...e and install this product After installation dispose of recycle all packaging materials Location Requirements Site location Select a location near the center of the water piping system The unit must...

Страница 5: ...water heater in a closed water system install an expansion tank in the cold water line as specified under Closed System Thermal Expansion 6 Install a shut off valve in the cold water inlet line It sh...

Страница 6: ...7 8 Turn on electrical power to the water heater 9 Select the efficiency mode After about 8 minutes the user interface module will display repetitively during this period the heat pump will turn on if...

Страница 7: ...valve Failure to follow these instructions can result in death or explosion WARNING Most public water systems in North America are required to prevent water flowing from points of use residences busin...

Страница 8: ...te of the water heater The Discharge Line Shall not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Shall not be capped blocked plugged...

Страница 9: ...ces rated at 30 amperes Figure 10 Junction Box Power Supply Connector Black Wire Red Wire Green Ground Wire 1 2 Conduit Opening Green Ground Screw The conduit or tubing is terminated in fittings appro...

Страница 10: ...roperly installed and free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section...

Страница 11: ...cess panel Reset the ECO by firmly pushing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature R...

Страница 12: ...not operate Similarly if the water temperature in the tank is less than 59 F 15 C the heat pump will not operate The unit will operate in electric mode until ambient and water temperatures return to...

Страница 13: ...ounts of noise and may cause premature tank failure Drain and flush the tank as directed under the Draining and Flushing section 3 The heat pump compressor or fan running Stacking Stacking occurs when...

Страница 14: ...the water tank 3 Drain approximately 5 gallons of water from the tank Refer to Draining and Flushing for proper procedures Close drain valve 4 Remove old anode rod 5 Use Teflon tape or approved pipe...

Страница 15: ...the water heater annually After servicing this water heater check to make sure it is working properly See Operating Your Water Heater section of this manual IMPORTANT If you lack the necessary skills...

Страница 16: ...the ones specified for the upper and or lower element IMPORTANT Using an element greater than 4500 watts will damage the water heater and void the warranty 1 Turn off the power to the water heater 2...

Страница 17: ...r E11 Heat Pump Coil Temperature Sensor is not functioning E40 or E41 Heat Pump Discharge Temperature Sensor is not functioning Edr Not enough water in the tank tank not full Fill completely Open all...

Страница 18: ...connection is at the top 5 Insulate exposed piping 6 Repair hot water leaks 7 Call qualified person for service 8 Drain and flush tank Water conditioning may be necessary to minimize build up HIGH OPE...

Страница 19: ...perature Sensor 13 Upper Lower Tank Temperature Sensor 14 Fan Shroud 15 Condensate Drain Connection Cover 16 Electronic Expansion Valve Coil 17 Start Capacitor 18 Relay Kit REPAIR PARTS Repair parts m...

Страница 20: ...20 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2014 Inc All Rights Reserved...

Отзывы: