If you lack the necessary skills required to properly install the 
electrical wiring to this water heater, do not proceed but have a 
quali

fi

 ed electrician perform the installation.

When making the electrical connections, always make sure:

• 

The electrical service provides 240 VAC to the water heater 
for proper operation. DO NOT use 208 VAC.

• 

Wire sizes and connections comply with all applicable 
codes or in the absence of local or state codes follow 
NFPA-70, the National Electrical Code-current edition.

• 

Wiring enclosed in approved conduit (if required by local 
codes).

• 

The water heater and electrical supply are properly  
grounded.

• 

The electrical supply has the proper overload fuse or 
breaker protection.

Always reference the wiring diagram located on the water 
heater for the correct electrical connections and 

connect the 

electrical supply to the water heater in accordance with local 
utility requirements and codes.

When installing the electrical wiring to the water heater:

1.  Although this water heater is equipped with “Dry Fire” 

protection, be sure tank is completely filled with water, and 
all air is purged from the tank before making any electrical 
connections. See “Draining and Flushing Section”.

2.  Turn off power to the electrical wiring for the water heater at 

the circuit breaker/fuse box.

3.  If metal conduit is used for the grounding conductor: 

A.  The grounding electrode conductor shall be of copper, 

aluminum, or copperclad aluminum. The material shall 
be of one continuous length without a splice or joint.

B.  Rigid metal conduit, intermediate metal conduit, 

or electrical, metallic tubing may be used for the 
grounding means if conduit or tubing is terminated in 
fittings approved for grounding.

C.  Flexible metal conduit or flexible metallic tubing shall 

be permitted for grounding if all the following conditions 
are met:
•   The length in any ground return path does not 
exceed 6 feet.
•    The circuit conductors contained therein are 
protected by overcurrent devices rated at 30 amperes.

Figure 10
Junction Box

Power Supply
Connector

Black Wire 

Red Wire

Green
Ground

Wire

1/2” Conduit
Opening

Green Ground Screw

•    The conduit or tubing is terminated in fittings 
approved for grounding.

For complete grounding details and all allowable exceptions, 
refer to the current edition of the National Electrical Code NFPA 
70.
4.  A standard 1/2" conduit opening has been made in the 

water heater junction box for the conduit connections.

5.  Use wire nuts and connect the power supply wiring to the 

wires inside the water heater's junction box (Figure 10).

6.  The water heater must be electrically "grounded" by the 

installer. A green ground screw has been provided on the 
water heater's junction box. Connect ground wire to this 
location.

7.  Replace the wiring junction box cover using the screw 

provided. 

8.  Turn on electrical power to the water heater.

9.  Press the Efficiency button to set the operating mode. 

NOTE:

 The water heater will conduct a system diagnostic  

(approximately 8 minutes) prior to returning to operation.

10.  Once the diagnostic sequence has finished, the fan should 

turn on.  

NOTE:

 The heat pump’s fan will not turn on if the 

incoming water temperature is less than 59°F / 15

°C 

and/

or the ambient air temperature is above 120°F / 15

°C

 

or below   45°F / 7.2

°C

. Should the internal diagnostics 

detect a problem with the heat pump, an error code will be 
displayed. 

11.  Set the desired operational mode. For typical installations, 

the Hybrid Mode offers the best combination of efficiency 
and hot water delivery. For detailed descriptions of all 
operational modes see “Adjusting the User Interface 
Module/Operational Modes” section.

Insulation Blankets

The use of an insulation blanket on this water heater is not 
needed or recommended. The purpose of an insulation 
blanket is to reduce the standby heat loss encountered with 
storage tank heaters. Your water heater meets or exceeds 
the National Appliance Energy Conservation Act standards 
with respect to insulation and standby loss requirements, 
making an insulation blanket unnecessary. If an insulation 
blanket is installed, make sure it does not block airflow into 
or out of the compressor assembly.

Содержание Hybrid ElectricHeat Pump Water Heater

Страница 1: ...on 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Water System Piping 5 6 Temperature Pressure Relief Valve 7 8 Electrical Requirements 8 9 Installation Checklist 10...

Страница 2: ...not been used for a long period of time 2 weeks or more Hydrogen gas is extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened fo...

Страница 3: ...When referring to your water heater always have the information listed on the data plate readily available to include the model and serial number Retain your original receipt as proof of purchase Basi...

Страница 4: ...e and install this product After installation dispose of recycle all packaging materials Location Requirements Site location Select a location near the center of the water piping system The unit must...

Страница 5: ...water heater in a closed water system install an expansion tank in the cold water line as specified under Closed System Thermal Expansion 6 Install a shut off valve in the cold water inlet line It sh...

Страница 6: ...7 8 Turn on electrical power to the water heater 9 Select the efficiency mode After about 8 minutes the user interface module will display repetitively during this period the heat pump will turn on if...

Страница 7: ...valve Failure to follow these instructions can result in death or explosion WARNING Most public water systems in North America are required to prevent water flowing from points of use residences busin...

Страница 8: ...te of the water heater The Discharge Line Shall not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Shall not be capped blocked plugged...

Страница 9: ...ces rated at 30 amperes Figure 10 Junction Box Power Supply Connector Black Wire Red Wire Green Ground Wire 1 2 Conduit Opening Green Ground Screw The conduit or tubing is terminated in fittings appro...

Страница 10: ...roperly installed and free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section...

Страница 11: ...cess panel Reset the ECO by firmly pushing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature R...

Страница 12: ...not operate Similarly if the water temperature in the tank is less than 59 F 15 C the heat pump will not operate The unit will operate in electric mode until ambient and water temperatures return to...

Страница 13: ...ounts of noise and may cause premature tank failure Drain and flush the tank as directed under the Draining and Flushing section 3 The heat pump compressor or fan running Stacking Stacking occurs when...

Страница 14: ...the water tank 3 Drain approximately 5 gallons of water from the tank Refer to Draining and Flushing for proper procedures Close drain valve 4 Remove old anode rod 5 Use Teflon tape or approved pipe...

Страница 15: ...the water heater annually After servicing this water heater check to make sure it is working properly See Operating Your Water Heater section of this manual IMPORTANT If you lack the necessary skills...

Страница 16: ...the ones specified for the upper and or lower element IMPORTANT Using an element greater than 4500 watts will damage the water heater and void the warranty 1 Turn off the power to the water heater 2...

Страница 17: ...r E11 Heat Pump Coil Temperature Sensor is not functioning E40 or E41 Heat Pump Discharge Temperature Sensor is not functioning Edr Not enough water in the tank tank not full Fill completely Open all...

Страница 18: ...connection is at the top 5 Insulate exposed piping 6 Repair hot water leaks 7 Call qualified person for service 8 Drain and flush tank Water conditioning may be necessary to minimize build up HIGH OPE...

Страница 19: ...perature Sensor 13 Upper Lower Tank Temperature Sensor 14 Fan Shroud 15 Condensate Drain Connection Cover 16 Electronic Expansion Valve Coil 17 Start Capacitor 18 Relay Kit REPAIR PARTS Repair parts m...

Страница 20: ...20 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2014 Inc All Rights Reserved...