TROUBLESHOOTING CHART

PROBLEM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

NO HOT WATER

1.  No power to the water heater (No 

lights on the unit are on).

2.  Unit in Vacation mode

3.  High temperature limit switch open

4.  Hot water usage pattern exceeds the 

capability of the water heater in 

current mode

5.  Non-functioning upper temperature 

sensor

1.  Check for blown fuse or tripped breaker.

Restore power to unit.

2.  Press Mode/Enter button and return to desired 

operating mode.

3.  Reset the high temperature limit switch; see 

“Safety shut-off” section for more information.

4.  Change to different mode or modify usage pat-

terns.

5.  Contact a qualified person for service.

INSUFFICIENT HOT WATER/ 
SLOW HOT WATER 
RECOVERY

1.  Temperature set-point too low

2.  Air filter dirty

3.  Hot water usage pattern exceeds the 

capability of the water heater in 

current mode

4.  Water connections to unit reversed

5.  Heat lost through long run of exposed 

pipe

6.  Hot water leak at faucet or piping

7.  Non-functioning heating element

8.  Sediment or scale build up in tank

1.  Increase set point temperature; see “Adjusting 

the User Interface Module” section

2.  Clean air filter

3.  Change to different mode or modify usage 

patterns (For example if in Efficiency Mode 

switch to Hybrid Mode)

4.  Ensure the cold connection is at the bottom 

and that the hot connection is at the top

5.  Insulate exposed piping

6.  Repair hot water leaks

7.  Call qualified person for service

8.  Drain and flush tank.  Water conditioning may 

be necessary to minimize build up

HIGH OPERATION COSTS

1.  Temperature set-point too high

2.  Air filter dirty

3.  Electric mode selected

4.  Water connections to unit reversed

5.  Heat lost thru long run of exposed 

pipe

6.  Hot water leak at faucet or piping

7.  Sediment or scale build up in tank

1.  Decrease set point temperature; see “Adjusting 

the User Interface Module”

2.  Clean air filter

3.  Change to Efficiency or Hybrid mode for re-

duced energy costs

4.  Ensure the cold connection is at the bottom 

and that the hot connection is at the top

5.  Insulate exposed piping

6.  Repair hot water leaks

7.  Drain and flush tank.  Water conditioning may 

be required to minimze build up

DRIP FROM TEMPERATURE & 
PRESSURE RELIEF VALVE
(Warning: Do not plug or cap 
T&P discharge pipe.)

1.  Excessive water pressure

2.  Add or service a thermal expansion 

tank.

3. Non-functioning 

Temperature 

Pressure Relief Valve

1.  Check water supply inlet pressure. If higher than 

80 PSIG, install a  pressure reducing valve (50-

60 PSIG is the recommended pressure.)

2.  See “Closed System/Thermal Expansion” section

3.  Replace the Temperature & PressureRelief 

Valve

OTHER

1.  The water heater does not 

immediately start 

2.  The heat pump does not run in 

Efficiency mode.

1.  When first started the water heater takes about 8 

minutes to complete a diagnostic routine

2.  Contact a qualified person for service

Содержание Hybrid ElectricHeat Pump Water Heater

Страница 1: ...on 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Water System Piping 5 6 Temperature Pressure Relief Valve 7 8 Electrical Requirements 8 9 Installation Checklist 10...

Страница 2: ...not been used for a long period of time 2 weeks or more Hydrogen gas is extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened fo...

Страница 3: ...When referring to your water heater always have the information listed on the data plate readily available to include the model and serial number Retain your original receipt as proof of purchase Basi...

Страница 4: ...e and install this product After installation dispose of recycle all packaging materials Location Requirements Site location Select a location near the center of the water piping system The unit must...

Страница 5: ...water heater in a closed water system install an expansion tank in the cold water line as specified under Closed System Thermal Expansion 6 Install a shut off valve in the cold water inlet line It sh...

Страница 6: ...7 8 Turn on electrical power to the water heater 9 Select the efficiency mode After about 8 minutes the user interface module will display repetitively during this period the heat pump will turn on if...

Страница 7: ...valve Failure to follow these instructions can result in death or explosion WARNING Most public water systems in North America are required to prevent water flowing from points of use residences busin...

Страница 8: ...te of the water heater The Discharge Line Shall not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Shall not be capped blocked plugged...

Страница 9: ...ces rated at 30 amperes Figure 10 Junction Box Power Supply Connector Black Wire Red Wire Green Ground Wire 1 2 Conduit Opening Green Ground Screw The conduit or tubing is terminated in fittings appro...

Страница 10: ...roperly installed and free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section...

Страница 11: ...cess panel Reset the ECO by firmly pushing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature R...

Страница 12: ...not operate Similarly if the water temperature in the tank is less than 59 F 15 C the heat pump will not operate The unit will operate in electric mode until ambient and water temperatures return to...

Страница 13: ...ounts of noise and may cause premature tank failure Drain and flush the tank as directed under the Draining and Flushing section 3 The heat pump compressor or fan running Stacking Stacking occurs when...

Страница 14: ...the water tank 3 Drain approximately 5 gallons of water from the tank Refer to Draining and Flushing for proper procedures Close drain valve 4 Remove old anode rod 5 Use Teflon tape or approved pipe...

Страница 15: ...the water heater annually After servicing this water heater check to make sure it is working properly See Operating Your Water Heater section of this manual IMPORTANT If you lack the necessary skills...

Страница 16: ...the ones specified for the upper and or lower element IMPORTANT Using an element greater than 4500 watts will damage the water heater and void the warranty 1 Turn off the power to the water heater 2...

Страница 17: ...r E11 Heat Pump Coil Temperature Sensor is not functioning E40 or E41 Heat Pump Discharge Temperature Sensor is not functioning Edr Not enough water in the tank tank not full Fill completely Open all...

Страница 18: ...connection is at the top 5 Insulate exposed piping 6 Repair hot water leaks 7 Call qualified person for service 8 Drain and flush tank Water conditioning may be necessary to minimize build up HIGH OPE...

Страница 19: ...perature Sensor 13 Upper Lower Tank Temperature Sensor 14 Fan Shroud 15 Condensate Drain Connection Cover 16 Electronic Expansion Valve Coil 17 Start Capacitor 18 Relay Kit REPAIR PARTS Repair parts m...

Страница 20: ...20 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2014 Inc All Rights Reserved...

Отзывы: