therMal eXpansIon

As water is heated, it expands (thermal expansion). In a closed system 

the volume of water will grow when it is heated. As the volume of water 

grows there will be a corresponding increase in water pressure due to 

thermal expansion. Thermal expansion can cause premature tank failure 

(leakage). This type of failure is not covered under the limited warranty. 

Thermal  expansion  can  also  cause  intermittent Temperature-Pressure 

Relief  Valve  operation:  water  discharged  from  valve  due  to  excessive 

pressure build up. This condition is not covered under the limited warranty. 

The Temperature-Pressure Relief Valve is not intended for constant relief 

of thermal expansion.
A  properly  sized  thermal  expansion  tank  must  be  installed  on 

all  closed  systems  to  control  the  harmful  effects  of  thermal 

expansion. Contact a local plumbing service agency to have a 

thermal expansion tank installed.

note: to protect against untimely corrosion of hot and cold water 

fittings, it is strongly recommended that di-electric unions or couplings 

be installed on this water heater when connected to copper pipe.

All gas piping must comply with local codes and ordinances or with the 

National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper and brass tubing 

and fittings (except tin lined copper tubing) should not be used.

fIGure 10.

Figure 10 shows typical attachment of  water piping to the water heater. 

The water heater is equipped with 3/4 inch NPT water connections.

note:

 

If using copper tubing, solder tubing to an adapter before 

attaching the adapter to the water heater connections.  do not solder 

the water lines directly to the water heater connections.  It will harm 

the dip tube and damage the tank.
t & p valve and pipe Insulation

1.  Locate the temperature and pressure relief valve on the water heater 

(also known as a T&P relief valve).  See Figure 11.

2.  Locate the slit running the length of the T&P relief valve insulation.

3.  Spread the slit open and fit the insulation over the T&P relief valve.  See 

Figure 11.  Apply gentle pressure to the insulation to ensure that it is fully 

seated on the T&P Relief Valve. Once seated, secure the insulation with 

duct tape, electrical tape, or equivalent.  IMPORTANT:  The insulation 

and tape must not block the discharge opening or hinder access to the 

manual relief lever (Figure 11).  Ensure a discharge pipe is installed into 

the T&P valve discharge opening per the instructions in this manual.

4.  Locate the hot water (outlet) & cold water (inlet) pipes to the water heater.

5.  Locate the slit running the length of a section of pipe insulation.

6.  Spread the slit open and slip the insulation over the cold water (inlet) 

pipe. Apply gentle pressure along the length of the insulation to ensure 

that it is fully seated around the pipe. Also, ensure that the base of 

the insulation is flush with the water heater.  Once seated, secure the 

insulation with duct tape, electrical tape, or equivalent.  

7.  Repeat steps 5 and 6 for the hot water (outlet) pipe.

8.  Add additional sections of pipe insulation as needed.

fIGure 11.

teMperature-pressure relIef valve

Explosion Hazard

Temperature-Pressure Relief Valve

must  comply  with  ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized Temperature-Pressure 

Relief Valve must be installed in 

opening provided.
Can  result  in  overheating  and

excessive  tank  pressure.
Can cause serious injury or death.

This water heater is provided with a properly rated/sized and certified 

combination Temperature-Pressure  Relief  Valve  (T&P  valve)  by  the 

manufacturer. The valve is certified by a nationally recognized testing 

laboratory  that  maintains  periodic  inspection  of  production  of  listed 

equipment of materials as meeting the requirements for Relief Valves 

for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code 

requirements of ASME.
If replaced, the new T&P valve must meet the requirements of local 

codes, but not less than a combination Temperature-Pressure Relief 

Valve rated/sized and certified as indicated in the above paragraph. 

The new valve must be marked with a maximum set pressure not to 

exceed the marked hydrostatic working pressure of the water heater 

(150 psi = 1,035 kPa) and a discharge capacity not less than the water 

heater Btu/hr or kW input rate as shown on the water heater’s model 

rating plate.
Note: In addition to the factory installed Temperature-Pressure Relief 

Valve on the water heater, each remote storage tank that may be 

installed and piped to a water heating appliance must also have its 

own properly sized, rated and approved Temperature-Pressure Relief 

Valve installed. Call the toll free technical support phone number listed 

on the back cover of this manual for technical assistance in sizing a 

Temperature-Pressure Relief Valve for remote storage tanks.
For safe operation of the water heater, the Temperature-Pressure 

Relief Valve must not be removed from its designated opening nor 

plugged. The Temperature-Pressure Relief Valve must be installed 

directly into the fitting of the water heater designed for the relief 

valve. Install discharge piping so that any discharge will exit the 

pipe  within  6  inches  (15.2  cm)  above  an  adequate  floor  drain, 

or  external  to  the  building.  In  cold  climates  it  is  recommended 

that it be terminated at an adequate drain inside the building. Be 

certain that no contact is made with any live electrical part. The 

Содержание GPHE 50 Series

Страница 1: ...DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER RESIDENTIAL GAS WATER HEATERS For Your Safety AN ODO...

Страница 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Страница 3: ...3 GENERAL SAFETY INFORMATION...

Страница 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Страница 5: ...tion Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local codes the National Electrical Code...

Страница 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Страница 7: ...ting 4 Places Shown DD Plastic Top EE On Off Switch FF Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual...

Страница 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1A...

Страница 9: ...time to burn relationship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring...

Страница 10: ...talled Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or p...

Страница 11: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Страница 12: ...size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air should be provided to replace the exhausted air When an exhaust fan is installed...

Страница 13: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 18 27 fo...

Страница 14: ...e requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water...

Страница 15: ...n 6 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure along the length of the insulation to ensure that it is fully seated around the pipe Also ensure t...

Страница 16: ...xcessive temperatures and pressures in the storage tank The T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all close...

Страница 17: ...losing its individual manual Shuttoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Страница 18: ...PVC parts should be assembled with ASTM D 2564 grade cement Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assem...

Страница 19: ...L Clearance above paved sidewalk or paved driveway located on public property 7 feet 2 13 m F Clearance to outside corner 2 feet 60 cm M Clearance under veranda porch deck or balcony 12 inches 30 cm G...

Страница 20: ...r signs of sagging or other stresses in joints as a result of misalignment of any components in system If any of these conditions are found they must be corrected in accordance with venting instructio...

Страница 21: ...tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower housing 6 Make su...

Страница 22: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Страница 23: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Страница 24: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4...

Страница 25: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Страница 26: ...above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PV...

Страница 27: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Страница 28: ...28...

Страница 29: ...located in an area where the general public does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasf...

Страница 30: ...riod of time generally two weeks or more Hydrogen gas is extremely flammable and explosive To prevent the possibility of injury under these conditions we recommend the hot water faucet located farthes...

Страница 31: ...od which will slowly deplete due to electrolysis prolonging the life of the water heater by protecting the glass lined tank from corrosion Adverse water quality hotter water temperatures high hot wate...

Страница 32: ...essure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death DRAINING AND FLUSHING It is recommended that the water...

Страница 33: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Страница 34: ...heet 34 Wire Screen 3 35 Wire Screen 4 36 Wall Plate 4 37 Flexible Tubing REPAIR PARTS LIST Nowthatyouhavepurchasedthiswaterheater shouldaneedeverexistfor repairpartsorservice simplycontactthecompanyi...

Страница 35: ...3 Ensure maximum number of elbows or maximum equivalent feet of vent or intake air pipe has not been exceeded per the installation instructions in the manual that came with the water heater 4 Ensure...

Страница 36: ...alve s immersion probe is either open or shorted 1 Turn the power off for 10 20 seconds then on again to clear these error codes 2 Replace the gas control valve thermostat if the error code persists 1...

Страница 37: ...37 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Страница 38: ...38 TROUBLESHOOTING GUIDELINES NOTES...

Страница 39: ...of it in a modified form or any attempt to repair tank leaks or parts will void this warranty servIce and laBor responsIBIlItY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLY A REPLACEMEN...

Страница 40: ...40 Copyright 2010 A O Smith Corporation All rights reserved 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: