background image

12

Such a condition often will result in a yellow, luminous burner 

flame, causing sooting of the combustion chamber, burners and 

flue tubes and creates a risk of asphyxiation.

Do  not  install  the  water  heater  in  a  confined  space  unless  an 

adequate supply of air for combustion and ventilation is brought in 

to that space using the methods described in the Confined Space 

section that follows. 

Never obstruct the flow of ventilation air. If you have any doubts or 

questions at all, call your gas supplier. Failure to provide the proper 

amount of combustion air can result in a fire or explosion and cause 

property damage, serious bodily injury or death.

unconfIned space

An Unconfined Space is one whose volume is not less than 50 cubic 

feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input 

rating of all appliances installed in the space. Rooms communicating 

directly with the space, in which the appliances are installed, through 

openings  not  furnished  with  doors,  are  considered  a  part  of  the 

unconfined space.

Makeup air requirements for the operation of exhaust fans, kitchen 

ventilation systems, clothes dryers and fireplaces should also be 

considered  in  determining  the  adequacy  of  a  space  to  provide 

combustion, ventilation and dilution air.

unusuallY tIGht constructIon

In unconfined spaces in buildings, infiltration may be adequate to 

provide air for combustion, ventilation and dilution of flue gases. 

However, in buildings of unusually tight construction (for example, 

weather  stripping,  heavily  insulated,  caulked,  vapor  barrier,  etc.) 

additional air must be provided using the methods described in the 

Confined Space section that follows.

confIned space

A Confined Space is one whose volume is less than 50 cubic feet 

per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating 

of all appliances installed in the space.

Openings  must  be  installed  to  provide  fresh  air  for  combustion, 

ventilation and dilution in confined spaces. The required size for the 

openings is dependent on the method used to provide fresh air to 

the confined space and the total Btu/hr input rating of all appliances 

installed in the space.

dIrect vent applIances

Appliances  installed  in  a  Direct  Vent configuration  that derive  all 

air  for  combustion  from  the  outdoor  atmosphere  through  sealed 

intake air piping are not factored in the total appliance input Btu/hr 

calculations used to determine the size of openings providing fresh 

air into confined spaces.

eXhaust fans

Where exhaust fans are installed, additional air should be provided 

to replace the exhausted air. When an exhaust fan is installed in 

the same space with a water heater, sufficient openings to provide 

fresh air must be provided that accommodate the requirements for 

all appliances in the room and the exhaust fan. Undersized openings 

will cause air to be drawn into the room through the water heater’s 

vent system causing poor combustion. Sooting, serious damage to 

the water heater and the risk of fire or explosion may result. It can 

also create a risk of asphyxiation.

louvers and GrIlles

The free areas of fresh air openings in instructions that follow do not take 

in to account presence of louvers, grilles or screens in openings.
The required size of openings for combustion, ventilation and dilution 

air should be based on the “net free area” of each opening. Where 

the free area through a design of louver or grille or screen is known, it 

should be used in calculating the size of opening required to provide the 

free area specified. Where the louver and grille design and free area 

are not known, it should be assumed that wood louvers will have 25% 

free area and metal louvers and grilles will have 75% free area. Non 

motorized louvers and grilles should be fixed in the open position.

fresh aIr openInGs for confIned spaces

The  following  instructions  should  be  used  to  calculate  the  size, 

number and placement of openings providing fresh air for combustion, 

ventilation and dilution in confined spaces. The illustrations shown in 

this section of the manual are a reference for the openings that provide 

fresh air into confined spaces only. Do not refer to these illustrations 

for the purpose of vent installation. See Installation of Vent System on 

pages 18-27 for complete venting installation instructions.

outdoor aIr throuGh two openInGs

fIGure 6.

The  confined  space  should  be  provided  with  two  permanent 

openings, one commencing within 12 inches (300 mm) of the top 

and one commencing within 12 inches (300 mm) of the bottom of 

the enclosure. The openings should communicate directly with 

the outdoors. See Figure 6.
Each opening should have a minimum free area of 1 square inch 

per 4,000 Btu/hr (550 mm

2

 per kW) of the aggregate input rating 

of all appliances installed in the enclosure. Each opening should 

not be less than 100 square inches (645 cm

2

).

outdoor aIr throuGh one openInG

fIGure 7.

Alternatively a single permanent opening, commencing within 12 

inches (300 mm) of the top of the enclosure, should be provided. See 

Содержание GPHE 50 Series

Страница 1: ...DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER RESIDENTIAL GAS WATER HEATERS For Your Safety AN ODO...

Страница 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Страница 3: ...3 GENERAL SAFETY INFORMATION...

Страница 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Страница 5: ...tion Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local codes the National Electrical Code...

Страница 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Страница 7: ...ting 4 Places Shown DD Plastic Top EE On Off Switch FF Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual...

Страница 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1A...

Страница 9: ...time to burn relationship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring...

Страница 10: ...talled Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or p...

Страница 11: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Страница 12: ...size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air should be provided to replace the exhausted air When an exhaust fan is installed...

Страница 13: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 18 27 fo...

Страница 14: ...e requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water...

Страница 15: ...n 6 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure along the length of the insulation to ensure that it is fully seated around the pipe Also ensure t...

Страница 16: ...xcessive temperatures and pressures in the storage tank The T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all close...

Страница 17: ...losing its individual manual Shuttoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Страница 18: ...PVC parts should be assembled with ASTM D 2564 grade cement Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assem...

Страница 19: ...L Clearance above paved sidewalk or paved driveway located on public property 7 feet 2 13 m F Clearance to outside corner 2 feet 60 cm M Clearance under veranda porch deck or balcony 12 inches 30 cm G...

Страница 20: ...r signs of sagging or other stresses in joints as a result of misalignment of any components in system If any of these conditions are found they must be corrected in accordance with venting instructio...

Страница 21: ...tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower housing 6 Make su...

Страница 22: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Страница 23: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Страница 24: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4...

Страница 25: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Страница 26: ...above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PV...

Страница 27: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Страница 28: ...28...

Страница 29: ...located in an area where the general public does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasf...

Страница 30: ...riod of time generally two weeks or more Hydrogen gas is extremely flammable and explosive To prevent the possibility of injury under these conditions we recommend the hot water faucet located farthes...

Страница 31: ...od which will slowly deplete due to electrolysis prolonging the life of the water heater by protecting the glass lined tank from corrosion Adverse water quality hotter water temperatures high hot wate...

Страница 32: ...essure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death DRAINING AND FLUSHING It is recommended that the water...

Страница 33: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Страница 34: ...heet 34 Wire Screen 3 35 Wire Screen 4 36 Wall Plate 4 37 Flexible Tubing REPAIR PARTS LIST Nowthatyouhavepurchasedthiswaterheater shouldaneedeverexistfor repairpartsorservice simplycontactthecompanyi...

Страница 35: ...3 Ensure maximum number of elbows or maximum equivalent feet of vent or intake air pipe has not been exceeded per the installation instructions in the manual that came with the water heater 4 Ensure...

Страница 36: ...alve s immersion probe is either open or shorted 1 Turn the power off for 10 20 seconds then on again to clear these error codes 2 Replace the gas control valve thermostat if the error code persists 1...

Страница 37: ...37 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Страница 38: ...38 TROUBLESHOOTING GUIDELINES NOTES...

Страница 39: ...of it in a modified form or any attempt to repair tank leaks or parts will void this warranty servIce and laBor responsIBIlItY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLY A REPLACEMEN...

Страница 40: ...40 Copyright 2010 A O Smith Corporation All rights reserved 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: