background image

37

Checking these four (4) items first will often result in a timely solution 

to the service call.

  

WARNING

JUMPING  OUT  COMPONENTS AND/OR  CIRCUITS  DURING 

TROUBLESHOOTING CAN CAUSE SERIOUS PROBLEMS WITH 

THE UNIT’S OPERATING SEQUENCE AND IGNITION SAFETY. 

IF YOU DO NOT HAVE THE PROPER TEST EQUIPMENT, I.E. A 

VOLT-OHM METER AND A MICROMETER, DO NOT ATTEMPT TO 

TROUBLESHOOT OR REPAIR A.O. SMITH EQUIPMENT.

ALTERING THE CONTROLLER AND/OR CONTROLLER WIRING 

IN ANY WAY COULD RESULT IN INTERNAL DAMAGE TO THE 

MODULE  CIRCUITS,  POSSIBLY ALTERING  THE  IGNITION 

SEQUENCE ALLOWING GAS VALVES TO OPEN BEFORE THE 

HOT SURFACE IGNITER IS UP TO IGNITION TEMPERATURE.

NOTE: ANY BYPASS OR ALTERATION OF THE UNITS SAFETIES 

WILL RESULT IN VOIDING THE APPLIANCE WARRANTY.

Before performing any troubleshooting familiarize yourself with the 

particular appliance.

Refer  to  the  SEQUENCE  OF  OPERATION  and  the  connection 

diagram before continuing.

Make sure the appliance is connected to a 120V AC power supply, 

manual gas valve is in the ON position, and all electrical connections 

are secure before continuing to troubleshoot this appliance.

  

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING 

ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRAL 

WIRE TO GROUND CHECK INDICATES ZERO VOLTAGE.

MOTOR WILL NOT RUN

1.  Confirm 120V AC. Also, to verify correct polarity, check for 120 V 

AC between hot supply and ground. If there is no voltage, check 

for a loose connection.

2.  For  BTH  400  and  500  a  VFD  (Variable  Frequency  Drive)  is 

used.  "rdy"  (stands  for  ready)  will  be  shown  on  display  in 

standby heating mode. "155" (155 output Hz) shall be shown 

on VFD display during heater running for BTH 400. "196" will be 

displayed on VFD during BTH 500 running. Any other display 

on the VFD indicates a faulty VFD or wrong speed reference, 

call A.O. Smith Tech Center for assistance.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT 

MAIN FLAME NOT ESTABLISHED

1.  Check to see if main manual gas valve is open.

2.  Check for a loose connection at the transformer, or a defective 

transformer.

3.  Check for a loose connection at the gas valve.

4.  Check for open pressure switches or open reset button. Check for 

blockage in the intake and exhaust venting or at the vent hoods. 

If no blockage is found, check vinyl tubing for cuts or crimps. If 

this tubing is damaged it must be replaced. If these steps do not 

eliminate the problem, replace the pressure switches.

5.  Check to see if there is resistance across the igniter terminal 

with an OHM meter. If there is no continuity, the igniter is 

broken and should be replaced.

  If the igniter appears to function properly, then verify that the 

inlet pressure is 11.0" Natural Gas (2.74 kPa).  The gas valve 

supplied on this appliance is not designed to open against a 

higher pressure. At this time also check that the inlet pressure 

is not lower than the minimal gas supply pressure, as shown 

in Table 4: that is, for Natural Gas, 5.2" (1.29 kPa) W.C. If 

the inlet pressure is not within these limits then adjust the 

supply pressure accordingly.

  If the inlet pressure falls within the allowable limits, then verify 

that the manifold pressure, when the gas is fully open, with 

the heater running, is as called out in Table 4:  that is, for 

Natural Gas, 4.0" (0.996 kPa)  W.C.  If the manifold pressure 

is not correct then adjust accordingly.  See ADJUSTMENT 

PROCEDURE  in  OPERATING  INSTRUCTIONS  for  the 

manifold pressure adjustment procedure.

6.  If  the  inlet  and  manifold  pressures  are  within  the  limits 

specified in step 5, then reset the appliance. Verify 24V AC 

at the gas valve during the three (3) second ignition trial, after 

the igniter reaches operating temperature. If 24V AC at the 

gas valve is not seen during this period, the controller must 

be replaced.

  If there is 24V AC at the gas valve during the four second 

ignition  trial  and  the  manifold  pressure  does  not  increase 

above 0" W.C. then verify that the manual gas control valve 

is in the “ON” position. If the valve is in the “ON” position and 

the previous voltage and gas pressure conditions are met, 

then the gas valve is defective and must be replaced.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY, 

THEN LOCKS OUT

1.  Reset the appliance two more times to ensure that all of the 

air has been purged from the gas line.

2. If  the  burner  lights  momentarily  but  does  not  sustain 

ignition, verify that the inlet pressure is not greater than 

11.0"  (2.74  kPa)  W.C.  or  lower  than  the  minimal  gas 

supply pressure, as shown in Table 4: that is, for Natural 

Gas,  5.2"  (1.29  kPa)  W.C.    pressure.  Also,  the  manifold 

pressure should rise during the three (3) second trial for 

ignition  to  the  manifold  pressure  value  for  the  individual 

unit listed in Table 4: that is, for Natural Gas, 4.0" (0.996 

kPa)  W.C.  If  the  manifold  pressure  is  not  correct  then 

adjust  accordingly.  See  ADJUSTMENT  PROCEDURE  in 

OPERATING  INSTRUCTIONS  section  for  the  manifold 

pressure adjustment procedure.

3.  Check  for  the  reversed  polarity  in  the  supply  wiring.  This 

controller  is  polarity  sensitive.  If  the  hot  and  neutral  supply 

wires are reversed, the controller will not sense flame. Reverse 

the supply wires and try to fire the unit. 

Содержание CYCLONE Xi BTH 500A

Страница 1: ...PERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death D...

Страница 2: ...the National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 FOREWORD ROUGH IN DIMENSIONS Recovery capacities are based on heater performance at 96 thermal efficiency for BTH 300A 400A...

Страница 3: ...s 22 23 Access to the Current Fault or Warning 23 Viewing the Fault History 24 Viewing Information About the Heater 24 PRIOR TO START UP REQUIRED ABILITY 25 OPERATING INSTRUCTIONS 25 Adjustment Proced...

Страница 4: ...AT A GLANCE BTH 300 400 500 QUICK INSTALLATION TIPS Horizontal Sidewall Venting Vertical Rooftop Venting...

Страница 5: ...conds 120 F 49 C More than 5 minutes FIGURE 1 Valves for reducing point of use temperature by mixing cold and hot water are available see Figure 2 Also available are inexpensive devices that attach to...

Страница 6: ...in conjunction with the heater Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current edition of the National Electrical Code NFPA...

Страница 7: ...ck or stone construction unconfined spaces may provide adequate air for combustion and ventilation If the unconfined space is within a building of tight construction buildings using the following cons...

Страница 8: ...ad in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The state or local gas inspector of the side wall horizontally vented gas fuel...

Страница 9: ...ECT VENT CANADIAN DIRECT VENT FIGURE 5 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOM...

Страница 10: ...NTAL VENT CANADIAN HORIZONTAL VENT FIGURE 6 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS...

Страница 11: ...PORTANT Plan the layout of the vent system backwards from the vent termination to the appliance WARNING USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT TERMINATIONOFAVENTSYSTEMWITHADEVICEOTHERTHAN...

Страница 12: ...VC pipe about 3 5 8 9 cm longer than the wall thickness at the opening 5 Glue the intake vent terminal to the section of the pipe 6 Slide the wall plate over the pipe to stop against intake vent termi...

Страница 13: ...of 4 inch pipe for the exhaust venting arrangement of 15 equivalent feet This is the minimum amount of pipe required for the exhaust venting arrangement The intake venting arrangement is certified to...

Страница 14: ...ver Switch is provided on the heater to verify that the fan is operating It is a positive pressure switch whose electrical contacts are normally open When the fan increases the pressure in the burner...

Страница 15: ...GAS PIPE IS CLEAN ON THE INSIDE TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE A DIRT LEG SOMETIMES CALLED A SEDIMENT TRAP OR DRIP LEG MUST BE INCORPORATED IN THE PIPING SEE FIG 14 THE DI...

Страница 16: ...e relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE WATER HEATER THE RELIEF VALVE S MUST NOT BE REMOVED OR PLUGGED In addition to the appliance relief valve ea...

Страница 17: ...ELECTRICITY FOR PROPER OPERATION INSTALLING THE HEATER ON A BRANCH CIRCUIT THAT HAS ELECTRONIC NOISE IS SUBJECT TO FLUCTUATIONS IN VOLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFE...

Страница 18: ...18 FIGURE 15 BTH 300 WIRING DIAGRAM...

Страница 19: ...19 FIGURE 16 BTH 400 AND 500 WIRING DIAGRAM...

Страница 20: ...run for the duration of the post purge cycle to purge the system of all combustion gases When the post purge cycle is complete the blower is de energized and will coast to a stop 11 The control will n...

Страница 21: ...water heater determines the regulated temperature for the water in the tank This parameter is adjusted in the Temperature menu Items in this menu allow you to monitor different temperature readings in...

Страница 22: ...that occurs the water heater controls will detect this condition and determine the appropriate action Part of this is displaying the information on the LCD in plain text that accurately describes the...

Страница 23: ...d information can be found in the control By pressing the Advanced button detailed information can be found regarding diagnosing and resolving the problem WARNING Usage of the Advanced information req...

Страница 24: ...an be accessed at any time 8 Viewing Information About the Heater The electronic control for this water heater monitors many different aspects of the water to ensure safe and optimal operation Much of...

Страница 25: ...R TO START UP REQUIRED ABILITY INSTALLATIONORSERVICEOFTHISWATERHEATERREQUIRES ABILITY EQUIVALENT TO THAT OFALICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRIC...

Страница 26: ...ERSONAL INJURY OR LOSS OF LIFE 1 STOP Read the safety information above on this label 2 Set thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped wit...

Страница 27: ...ALTITUDES UP TO 10 000 FEET INSTALLATIONS ABOVE 10 000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800 527 1953 FOR REQUIREMENTS Some gas utility compa...

Страница 28: ...about 1 2 5cm of lime buildup if it has reached the drain valve opening A schedule for deliming should be set up based on the amount of time it would take for a 1 2 5cm buildup of lime Example 1 Init...

Страница 29: ...D MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT THE VALVE DURING THIS CHECKING OPERATION If the temperature and pressure relief valve on the heater discharges periodically or continuously it may b...

Страница 30: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Страница 31: ...DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPU...

Страница 32: ...CIFICATIONS PAGE 35 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Страница 33: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Страница 34: ...TE 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAG...

Страница 35: ...ting and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters ass...

Страница 36: ...brush 10 Condensate hose may be blocked where it connects to the exhaust elbow Verify the condensate drains from the unit without restriction WATER IS TOO HOT 1 Refer to WATER TEMPERATURE CONTROL WAT...

Страница 37: ...igniter terminal with an OHM meter If there is no continuity the igniter is broken and should be replaced If the igniter appears to function properly then verify that the inlet pressure is 11 0 Natura...

Страница 38: ...immediately NOISY BURNER OPERATION The exhaust of this unit produces some noise during ignition period When combustion is too lean or too rich start up noise will get worse Check for flue gas CO2 read...

Страница 39: ...n is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warra...