These designs comply with the current edition of the American
National Standard for Gas Water Heaters, Volume III,
ANSI Z21.10.3 / CSA 4.3 as an automatic circulating tank water
heater, and automatic storage water heaters.
Detailed installation diagrams are found in this manual. These
diagrams will serve to provide the installer with a reference for the
materials and methods of piping necessary. It is highly essential
that all water, gas piping and wiring be installed as shown on the
diagrams.
Particular attention should be given to the installation of thermometers
at the locations indicated on the diagrams as these are necessary
for checking the proper functioning of the heater.
In addition to these instructions, the equipment shall be installed in
accordance with those installation regulations in force in the local
area where the installation is to be made. These shall be carefully
followed in all cases. Authorities having jurisdiction should be
consulted before installations are made.
In the absence of local codes, the installation must comply
with the current editions of the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and the National Electrical Code,
NFPA 70 or CAN/CSA-B149.1, the Natural Gas and Propane
Installation Code and CSA C22.1, the Canadian Electrical Code. All
documents are available from the Canadian Standards Association,
8501 East Pleasant Valley Road, Cleveland, OH 44131. NFPA
documents are also available from the National Fire Protection
Association, 1 Batterymarch Park, Quincy, MA 02269.
FOREWORD
ROUGH-IN-DIMENSIONS
Recovery capacities are based on heater performance at 96% thermal efficiency for BTH 300A, 400A, and 95% thermal efficiency for BTH 500A.
GAS VALVE PIPING
BTH-300 1 1/4" NPT
BTH-400 1 1/4" NPT
BTH-500 1 1/2" NPT
U.S. Gallons/Hr and Litres/Hr at TEMPERATURE RISE INDICATED
TYPE OF
INPUT
Approx.
F°
20F°
30F° 40F° 50F° 60F° 70F° 80F° 90F° 100F° 110° 120F° 130F° 140F°
MODEL
GAS
BTUH
KW
Capacity
C°
11C° 17C° 22C° 28C° 33C° 39C° 44C° 50C° 56C° 61C° 67C° 72C° 78C°
300,000
130 US Gals. GPH
1746
1164
873
699
582 499 436 388 349
318
291
269
250
88
492 Litres
LPH
6610
4406 3304 2644 2203 1888 1652 1469 1322 1201 1102 1017 945
300,000
130 US Gals. GPH
1746
1164
873
699
582 499 436 388 349
318
291
269
250
88
492 Litres
LPH
6610
4406 3304 2644 2203 1888 1652 1469 1322 1201 1102 1017 945
399,900
130 US Gals. GPH
2328
1552 1164
931
776 665 582 517 466
423
388
359
332
117
492 Litres
LPH
8813
5875 4406 3525 2938 2518 2203 1958 1763 1602 1469 1356 1259
399,900
130 US Gals. GPH
2328
1552 1164
931
776 665 582 517 466
423
388
359
332
117
492 Litres
LPH
8813
5875 4406 3525 2938 2518 2203 1958 1763 1602 1469 1356 1259
499,900
130 US Gals. GPH
2878
1919 1439 1151
959 822 720 640 576
523
480
443
411
146
492 Litres
LPH 10894 7263 5447 4358 3631 3113 2724 2421 2179 1981 1816 1676 1556
499,900
130 US Gals. GPH
2878
1919 1439 1151
959 822 720 640 576
523
480
443
411
146
492 Litres
LPH 10894 7263 5447 4358 3631 3113 2724 2421 2179 1981 1816 1676 1556
TABLE 1 RECOVERY CAPACITIES.
NATURAL
NATURAL
PROPANE
BTH-300
BTH-300
BTH-400
BTH-400 PROPANE
BTH-500
BTH-500
NATURAL
PROPANE