FLUSHING

1.  Turn off the heater electrical disconnect switch.

2.  Open the drain valve and allow water to flow until it runs clean.

3.  Close the drain valve when finished flushing.

4.  Turn on the heater electrical disconnect switch.

DRAINING

The heater must be drained if it is to be shut down and exposed to 

freezing temperatures. Maintenance and service procedures may 

also require draining the heater.

1.  Turn off the heater electrical disconnect switch.

2.  Close the cold water inlet valve to heater.

3.  Open a nearby hot water faucet to vent the system.

4.  Open the heater drain valve.

5.  If  the  heater  is  being  drained  for  an  extended  shutdown,  it  is 

suggested the drain valve be left open during this period.

  •  Follow FILLING instructions when restoring hot water service.

SEDIMENT REMOVAL

Waterborne impurities consist of the particles of soil and sand which 

settle out and form a layer of sediment on the bottom of the tank.

For convenience, sediment removal and lime scale removal should 

be performed at the same time.

LIME SCALE REMOVAL

The  amount  of  calcium  carbonate  (lime)  released  from  water  is 

in  direct  proportion  to  water  temperature  and  usage. The  higher 

the water temperature or water usage, the more lime deposits are 

dropped out of the water. This is the lime scale which forms in pipes, 

heaters and on cooking utensils.

Lime accumulation not only reduces the life of the equipment but also 

reduces efficiency of the heater and increases fuel consumption.

The  usage  of  water  softening  equipment  greatly  reduces  the 

hardness of the water. However, this equipment does not always 

remove all of the hardness (lime). For this reason it is recommended 

that a regular schedule for deliming be maintained.

The depth of lime buildup should be measured periodically. Heaters 

will have about 3" (7.6cm) of lime buildup when the level of lime has 

reached the bottom of the cleanout opening or about 1" (2.5cm) of 

lime buildup if it has reached the drain valve opening. A schedule 

for deliming should be set up, based on the amount of time it would 

take for a 1" (2.5cm) buildup of lime.

Example 1:

  Initial  inspection  shows  1/2"  (1.3cm)  of  lime  accumulation. 

Therefore, the heater can be delimed once a year.

Example 2 :

   Initial inspection shows 2" (5cm) of lime accumulation. Therefore, 

the heater should be delimed every 3 months.

Sediment and lime scale removal may be accomplished through 

the cleanout opening furnished on the heater, see Figure 24. The 

heater must be drained, see DRAINING, before removing cleanout 

cover on tank.

FIGURE 24.

To  dissolve  and  remove  the  more  stubborn  mineral  deposits, 

 

A.O. Smith UN•LIME® Professional Delimer should be used. 

NOTE: 

UN•LIME is not available in Canada. Please call Customer Service 

at 1-800-265-8520 for approved alternatives. 

A.O. Smith UN•LIME® Professional Delimer is an easy to handle 

patented  food  grade  acid  formulated  specifically  for  lime  scale 

removal  from  all  types  of  water  using  equipment. Available  in  1 

gallon  (3.8L)  (part  no.  4763)  and  5  gallon  (19L)  (part  no.  4813) 

sizes. Hydrochloric base acids are not recommended for use on 

glass-lined tanks.

A.O. Smith Form No. 4800 Rev. 8, entitled “Why, When and How”, 

describes  tank  cleaning  methods  and  materials.  UN•LIME  and 

the  booklet  may  be  obtained  through  your A.O.  Smith  dealer  or 

distributor.

The cleanout opening is shown in Figure 24. To clean heater through 

cleanout opening, proceed as follow:

1.  Turn off water inlet valve, the heater electrical disconnect switch 

and open drain valve.

2.  Remove outer cover plate from lower side of heater jacket.

3.  Remove cover from cleanout opening.

4.  Remove lime, scale or sediment using care not to damage the 

glass-lining.

5.  Inspect cleanout plate gasket: If new gasket is required, replace 

with A. O. Smith part no. 99038.

6.  Install cleanout plate.  Be sure to draw plate up tight by tightening 

screws securely.

7.  Close drain valve, open water inlet line and turn on the power 

burner electrical disconnect switch.

8.  Check for water leakage.

9.  Replace outer jacket cover plate.

Содержание CYCLONE Xi BTH 500A

Страница 1: ...PERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death D...

Страница 2: ...the National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 FOREWORD ROUGH IN DIMENSIONS Recovery capacities are based on heater performance at 96 thermal efficiency for BTH 300A 400A...

Страница 3: ...s 22 23 Access to the Current Fault or Warning 23 Viewing the Fault History 24 Viewing Information About the Heater 24 PRIOR TO START UP REQUIRED ABILITY 25 OPERATING INSTRUCTIONS 25 Adjustment Proced...

Страница 4: ...AT A GLANCE BTH 300 400 500 QUICK INSTALLATION TIPS Horizontal Sidewall Venting Vertical Rooftop Venting...

Страница 5: ...conds 120 F 49 C More than 5 minutes FIGURE 1 Valves for reducing point of use temperature by mixing cold and hot water are available see Figure 2 Also available are inexpensive devices that attach to...

Страница 6: ...in conjunction with the heater Refer to the piping diagrams at rear of manual for electrical hookup information and install in accordance with the current edition of the National Electrical Code NFPA...

Страница 7: ...ck or stone construction unconfined spaces may provide adequate air for combustion and ventilation If the unconfined space is within a building of tight construction buildings using the following cons...

Страница 8: ...ad in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The state or local gas inspector of the side wall horizontally vented gas fuel...

Страница 9: ...ECT VENT CANADIAN DIRECT VENT FIGURE 5 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOM...

Страница 10: ...NTAL VENT CANADIAN HORIZONTAL VENT FIGURE 6 CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS...

Страница 11: ...PORTANT Plan the layout of the vent system backwards from the vent termination to the appliance WARNING USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT TERMINATIONOFAVENTSYSTEMWITHADEVICEOTHERTHAN...

Страница 12: ...VC pipe about 3 5 8 9 cm longer than the wall thickness at the opening 5 Glue the intake vent terminal to the section of the pipe 6 Slide the wall plate over the pipe to stop against intake vent termi...

Страница 13: ...of 4 inch pipe for the exhaust venting arrangement of 15 equivalent feet This is the minimum amount of pipe required for the exhaust venting arrangement The intake venting arrangement is certified to...

Страница 14: ...ver Switch is provided on the heater to verify that the fan is operating It is a positive pressure switch whose electrical contacts are normally open When the fan increases the pressure in the burner...

Страница 15: ...GAS PIPE IS CLEAN ON THE INSIDE TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE A DIRT LEG SOMETIMES CALLED A SEDIMENT TRAP OR DRIP LEG MUST BE INCORPORATED IN THE PIPING SEE FIG 14 THE DI...

Страница 16: ...e relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE WATER HEATER THE RELIEF VALVE S MUST NOT BE REMOVED OR PLUGGED In addition to the appliance relief valve ea...

Страница 17: ...ELECTRICITY FOR PROPER OPERATION INSTALLING THE HEATER ON A BRANCH CIRCUIT THAT HAS ELECTRONIC NOISE IS SUBJECT TO FLUCTUATIONS IN VOLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFE...

Страница 18: ...18 FIGURE 15 BTH 300 WIRING DIAGRAM...

Страница 19: ...19 FIGURE 16 BTH 400 AND 500 WIRING DIAGRAM...

Страница 20: ...run for the duration of the post purge cycle to purge the system of all combustion gases When the post purge cycle is complete the blower is de energized and will coast to a stop 11 The control will n...

Страница 21: ...water heater determines the regulated temperature for the water in the tank This parameter is adjusted in the Temperature menu Items in this menu allow you to monitor different temperature readings in...

Страница 22: ...that occurs the water heater controls will detect this condition and determine the appropriate action Part of this is displaying the information on the LCD in plain text that accurately describes the...

Страница 23: ...d information can be found in the control By pressing the Advanced button detailed information can be found regarding diagnosing and resolving the problem WARNING Usage of the Advanced information req...

Страница 24: ...an be accessed at any time 8 Viewing Information About the Heater The electronic control for this water heater monitors many different aspects of the water to ensure safe and optimal operation Much of...

Страница 25: ...R TO START UP REQUIRED ABILITY INSTALLATIONORSERVICEOFTHISWATERHEATERREQUIRES ABILITY EQUIVALENT TO THAT OFALICENSED TRADESMAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRIC...

Страница 26: ...ERSONAL INJURY OR LOSS OF LIFE 1 STOP Read the safety information above on this label 2 Set thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped wit...

Страница 27: ...ALTITUDES UP TO 10 000 FEET INSTALLATIONS ABOVE 10 000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800 527 1953 FOR REQUIREMENTS Some gas utility compa...

Страница 28: ...about 1 2 5cm of lime buildup if it has reached the drain valve opening A schedule for deliming should be set up based on the amount of time it would take for a 1 2 5cm buildup of lime Example 1 Init...

Страница 29: ...D MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT THE VALVE DURING THIS CHECKING OPERATION If the temperature and pressure relief valve on the heater discharges periodically or continuously it may b...

Страница 30: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Страница 31: ...DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPU...

Страница 32: ...CIFICATIONS PAGE 35 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Страница 33: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Страница 34: ...TE 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAG...

Страница 35: ...ting and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters ass...

Страница 36: ...brush 10 Condensate hose may be blocked where it connects to the exhaust elbow Verify the condensate drains from the unit without restriction WATER IS TOO HOT 1 Refer to WATER TEMPERATURE CONTROL WAT...

Страница 37: ...igniter terminal with an OHM meter If there is no continuity the igniter is broken and should be replaced If the igniter appears to function properly then verify that the inlet pressure is 11 0 Natura...

Страница 38: ...immediately NOISY BURNER OPERATION The exhaust of this unit produces some noise during ignition period When combustion is too lean or too rich start up noise will get worse Check for flue gas CO2 read...

Страница 39: ...n is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warra...

Страница 40: ...40 www hotwater com...

Отзывы: