background image

4

The temperature may be adjusted from 80°F/27°C to 180°F/82°C.
The thermostat was adjusted to 120°F/49°C before the heater was
shipped from the factory. It is recommended that lower water
temperatures be used to avoid the risk of scalding. It is further
recommended, in all cases, that the water temperature be set for
the lowest temperature which satisfies your hot water needs. This
will also provide the most energy efficient operation of the water
heater and minimize scale formation.

SETTING THE WATER HEATER TEMPERATURE AT 120°F/49°C
WILL REDUCE THE RISK OF SCALDS. Some states require
settings at specific lower temperatures.

Figure 1 shows the approximate time-to-burn relationship for normal
adult skin. Short repeated heating cycles caused by small hot water
uses can cause temperatures at the point of use to exceed the
thermostat setting by up to 20°F (11C°). If you experience this type
of use, you should consider using lower temperature settings to
reduce scald hazards.

           

Temperature

Time to Produce 2nd & 3rd

Setting

Degree Burns on Adult Skin

180°F / 82°C

Nearly instantaneous

170°F / 77°C

Nearly instantaneous

160°F / 71°C

About 1/2 second

150°F / 66°C

About 1-1/2 seconds

140°F / 60°C

Less than 5 seconds

130°F / 54°C

About 30 seconds

120°F / 49°C

More than 5 minutes

FIGURE 1

Valves for reducing point-of-use temperature by mixing cold and
hot water are available (see Figure 2). Also available are inexpensive
devices that attach to faucets to limit hot water temperatures.
Contact a licensed plumber or the local plumbing authority.

FIGURE 2

HIGH LIMIT SWITCH (E.C.O.)

The top immersion well of the dual bulb controller also contains
the high limit (energy cutoff) sensor.  The high limit switch interrupts
the main burner gas flow should the water temperature reach
approximately 202°F/94°C.

Should the high limit switch activate, it must be manually reset by
depressing the Temperature Adjustment Button/Reset Button on

the display board. The water temperature must drop below 160°F/
71°C before the controller can be reset.

Continued manual resetting of high limit control, preceded by higher
than usual water temperature is evidence of high limit switch
operation.  The following is a possible reason for high limit switch
operation.

A malfunction in the thermostatic controls would allow the gas
valve to remain open causing water temperature to exceed the
thermostat setting.  The water temperature would continue to
rise until high limit switch operation.

Contact your dealer or servicer if continued high limit switch
operation occurs.

DISHWASHING MACHINE REQUIREMENT

All dishwashing machines meeting the National Sanitation
Foundation requirements are designed to operate with water flow
pressures between 15 and 25 pounds per square inch (103 Kpa
and 173 Kpa).  Flow pressures above 25 pounds per square inch
(173 Kpa), or below 15 pounds per square inch (103 Kpa), will
result in improperly sanitized dishes.  Where pressures are high, a
water pressure reducing or flow regulating control valve should be
used in the 180°F (82°C) line to the dishwashing machine, and
should be adjusted to deliver water between these limits.

The National Sanitation Foundation also recommends circulation
of 180°F (82°C) water.  Where this is done, the circulation should
be very gentle so that it does not cause any unnecessary turbulence
inside the water heater.  The circulation should be just enough to
provide 180°F (82°C) water at the point of take-off to the dishwashing
machine.  Adjust flow by means of the plug cock in the circulating
line. (See installation diagrams.)

CIRCULATING PUMP

A circulating pump is used when a system requires a circulating
loop or there is a storage tank used in conjunction with the heater.
Refer to the piping diagrams at rear of manual for electrical hookup
information and install in accordance with the latest version of the
National Electric Code ANSI/NFPA No. 70 or Canadian Code CSA
C22.1.

All bronze circulators are recommended for used with commercial
water heaters.

Although circulators are oiled and operated by the manufacturer
some circulators must be oiled again before operated. Please refer
to manufacturer's instructions.

INSTALLATION INSTRUCTIONS

REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER
REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED
TRADESMAN IN THE FIELD INVOLVED.  PLUMBING, AIR
SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK ARE
REQUIRED.

INSULATION BLANKETS

Insulation blankets available to the general public for external use
on gas water heaters are not approved for use on your A.O. Smith
water heater. The purpose of an insulation blanket is to reduce the
standby heat loss encountered with storage tank water heaters.
Your A.O. Smith water heater meets or exceeds the ASHRAE/IES
90.1b 1992 standards with respect to insulation and standby loss
requirements, making an insulation blanket unnecessary.

Содержание CYCLONE Xi BTH 400A

Страница 1: ...ETY PLEASE READ THOROUGHLY BEFORE INSTALLINGAND USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactl...

Страница 2: ...SA B149 1 and CSA C22 1 The former is available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 and both documents are available from the National Fire Protec...

Страница 3: ...iagnostic Controller 15 Gas Value LEDs Flashing 15 Error Codes 16 Fault Conditions 16 No Incoming Line Voltage 16 No Low Voltage 16 Temperature Probe Fault 16 E C O Switch Open 17 Control Bad 17 Combu...

Страница 4: ...ter temperature to exceed the thermostat setting The water temperature would continue to rise until high limit switch operation Contact your dealer or servicer if continued high limit switch operation...

Страница 5: ...cover the instruction manual Keep it on the side of the water heater or nearby for future reference Do obtain new labels from A O Smith for placement on the blanket directly over the existing labels...

Страница 6: ...of all appliances in the enclosure If horizontal ducts are used each opening shall have a free area of not less than one square inch per 2000 Btuh 1 102mm2 kW of the total input of all appliances in t...

Страница 7: ...VER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD ON DIRECT VENT INSTALLATIONS INLET VENT HOOD MUST BE LOCATED 1 30 5cm MINIMUM FROM ANY OPENING IN BUILDING ON DIRECT VENT INSTALL...

Страница 8: ...T TERMINALS AN INTAKE VENT TERMINAL AND AN EXHAUST VENT TERMINAL THE INTAKE VENT TERMINAL IS A 3 45 PVC ELBOW WITH A DOME SHAPE SCREEN AND THE EXHAUST VENT TERMINAL IS A 3 45 PVC ELBOW WITH A MESH WIR...

Страница 9: ...TERMINAL INTAKE VENT TERMINAL FIGURE 10 VERTICAL VENT TERMINAL INSTALLATION IMPORTANT WHEN TERMINATING THROUGH A ROOF THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED 1 Pr...

Страница 10: ...The fittings other than the TERMINATIONS should be equivalent to PVC DWV fittings meeting ASTM D 2665 Use CPVC fittings ASTM F 438 for CPVC pipe and ABS fittings ASTM D 2661 3311 for ABS pipe If CPVC...

Страница 11: ...SWITCH SEE FIGURE 13 The Blocked Outlet Prover Switch is set up to shut the unit off when a build up of positive pressure in the exhaust vent pipe occurs This switch is a positive pressure switch that...

Страница 12: ...DAMAGE PERSONAL INJURY OR LOSS OF LIFE The Gas Leak Test is performed as follows Paint pipe connections upstream of gas control with a rich soap and water solution to test for leaks before operating m...

Страница 13: ...be used in conjunction with this appliance shall also be installed with a properly sized rated and approved temperature ANSI and pressure ASME relief valve s This relief valve shall comply with the st...

Страница 14: ...OLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFERENCE CAN CAUSE THE CONTROLLER TO MALFUNCTION A HIGH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST MALFUN...

Страница 15: ...Dirty burner 10 Clean burner be closed and the blower will continue to run for approximately 10 seconds The control will then return to step 2 9 If a flame is confirmed the control will enter the heat...

Страница 16: ...Not Implemented h s 240 Executed State 4 Not Implemented h s 210 Executed State 10 Not Implemented h s 213 Executed State 13 Not Implemented h s 214 Executed State 14 Not Implemented h s 216 Executed...

Страница 17: ...ntrol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe Possible Cause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring sho...

Страница 18: ...SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMANIN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLYANDELECTRICALWORKAREREQUIRED Before attempting start...

Страница 19: ...ur hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may re...

Страница 20: ...ATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 2000 FEET INSTALLATIONS ABOVE 2000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800...

Страница 21: ...nance and service procedures may also require draining the heater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to ve...

Страница 22: ...MANUALLY OPERATING THE VALVE MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TO AN OPEN DRAIN FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT...

Страница 23: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Страница 24: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD A...

Страница 25: ...CIFICATIONS PAGE 28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Страница 26: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Страница 27: ...TE 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAG...

Страница 28: ...er heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold k...

Страница 29: ...ED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater an...

Страница 30: ...ot greater than 11 0 2 74 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 6 2 1 54 kPa W C pressure Also the manifold pressure should rise during the...

Страница 31: ...on is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warr...

Страница 32: ...32 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E mail parts hotwater com...

Отзывы: