background image

30

MOTOR WILL NOT RUN

1. Confirm 120V AC to the controller. Also, to verify correct polarity,

check for 120 V AC between hot supply and ground.

If there is no voltage, check for a loose connection where it
connects to the controller.

2. If there is 120 volts to the controller, check for loose connections

or a locked rotor. If the rotor cannot be freed the motor and
blower assembly must be replaced.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT

MAIN FLAME NOT ESTABLISHED.

1. Check to see if main manual gas valve is open.

2. Check for a loose connection at the transformer, or a defective

transformer.

3. Check for a loose connection at the gas valve.

4. Check for open pressure switches or open reset button. Check

for blockage in the intake and exhaust venting or at the vent
hoods. If no blockage is found, check vinyl tubing for cuts or
crimps. If this tubing is damaged it must be replaced. If these
steps do not eliminate the problem, replace the pressure
switches.

5. Check to see if there is resistance across the igniter terminal

with an OHM meter. If there is no continuity, the igniter is broken
and should be replaced.

If the igniter appears to function properly, then verify that the
inlet pressure is 11.0" Natural Gas (2.74 kPa).  The gas valve
supplied on this appliance is not designed to open against a
higher pressure. At this time also check that the inlet pressure
is not lower than the minimal gas supply pressure, as shown in
Table 4: that is, for Natural Gas, 6.2" (1.5 kPa) W.C. If the inlet
pressure is not within these limits then adjust the supply pressure
accordingly.

If the inlet pressure falls within the allowable limits, then verify
that the manifold pressure, when the gas is fully open, with the
heater running, is as called out in Table 4:  that is, for Natural
Gas, 5.0" (1.25 kPa)  W.C.  If the manifold pressure is not correct
then adjust accordingly.  See ADJUSTMENT PROCEDURE in
OPERATING INSTRUCTIONS selection, page 18, for the
manifold pressure adjustment procedure.

6. If the inlet and manifold pressures are within the limits specified

in step 5, then reset the appliance. Verify 24V AC at the gas
valve during the three (3) second ignition trial, after the igniter
reaches operating temperature. If 24V AC at the gas valve is
not seen during this period, the controller must be replaced.

If there is 24V AC at the gas valve during the four second ignition
trial and the manifold pressure does not increase above 0" W.C.
then verify that the manual gas control valve is in the “ON”
position (see page 20). If the valve is in the “ON” position and
the previous voltage and gas pressure conditions are met, then
the gas valve is defective and must be replaced.

Note that a positive manifold pressure reading of approximately
1.5" (.38 kPa) W.C. is normal during the prepurge portion of the
ignition cycle due to the location of the gas orifice.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY,

THEN LOCKS OUT

1. Reset the appliance two more times to ensure that all of the air

has been purged from the gas line.

2. If the burner lights momentarily but does not sustain ignition,

verify that the inlet pressure is not greater than 11.0" (2.74 kPa)
W.C. or lower than the minimal gas supply pressure, as shown

in Table 4: that is, for Natural Gas, 6.2" (1.54 kPa) W.C.  pressure.
Also, the manifold pressure should rise during the three (3)
second trial for ignition to the manifold pressure value for the
individual unit listed in Table 4: that is, for Natural Gas,
5.0" (1.25 kPa) W.C. If the manifold pressure is not correct then
adjust accordingly. See ADJUSTMENT PROCEDURE in
OPERATING INSTRUCTIONS section, page 18, for the manifold
pressure adjustment procedure.

3. Check for the reversed polarity in the supply wiring. This controller

is polarity sensitive. If the hot and neutral supply wires are
reversed, the controller will not sense flame. Reverse the supply
wires and try to fire the unit.

NOTE:  Always turn off and disconnect main supply wiring before
servicing the unit.

4. Check connecting wire to the flame sensor. Verify that the flame

sensor has not been damaged in any way.

5. Verify that the air supply is adequate. The air inlet screen or

blower wheel may be restricted. Also, check the installation for
proper ventilation. See AIR REQUIREMENTS.

6. Check the venting system for the correct sizing, excess or

insufficient. See VENTING.

7. Check for a maximum inlet pressure of 11" Natural Gas

(2.74 kPa) W.C. and the manifold pressure as listed in Table 4:
that is, for Natural Gas, 5.0" (1.25 kPa) W.C. Please note that
the manifold pressure listed is the maximum value for the
manifold pressure. Do not set the manifold pressure higher than
the value shown for your heater in Table 4. Overfiring the heater
will result in rough ignition and/or noisy operation.

8. Confirm that the air inlet screen (see Figures 7 & 8) is free of

obstructions.

  

CAUTION

Do not reach into the burner housing or combustion chamber if the
heater is still hot. Allow the heater to cool and always use gloves
as the combustion chamber and the burner sleeve and housing
can become very hot after operation. Overfiring is a dangerous
condition that must be corrected immediately.

NOISY BURNER OPERATION

The exhaust of this unit produces some noise. This noise may be
objectionable if the exhaust terminal is located too close to the
opening of an occupied space. The noise may also be objectionable
if the exhaust is located in the confined space between two buildings
such as an alley or walkway. Since everyone's perception and
tolerance for background noise varies, there is no standard
recommendation. The best option when the noise is a concern is
to locate the exhaust as far away from any occupied spaces as
practical.

If noise becomes more than one can tolerate, a dampening muffler
is available through our Product Service Division. See
“REPLACEMENT PARTS” segment below.

GAS FAILS TO SHUT OFF

Check for defective gas valve or thermostat. If operation is incorrect,
replace.

REPLACEMENT PARTS

Replacement parts may be ordered through A.O. Smith dealers,
authorized servicers or distributors. Refer to the Yellow Pages for
where to call or contact the A.O. Smith Water Products Company,
5621 W. 115th Street, Alsip, IL  60803, 1-800-433-2545. When
ordering parts be sure to state the quantity, part number and
description of the items including the complete model and serial
number as it appears on the product. Refer to the parts list for
more information.

Содержание CYCLONE Xi BTH 400A

Страница 1: ...ETY PLEASE READ THOROUGHLY BEFORE INSTALLINGAND USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactl...

Страница 2: ...SA B149 1 and CSA C22 1 The former is available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 and both documents are available from the National Fire Protec...

Страница 3: ...iagnostic Controller 15 Gas Value LEDs Flashing 15 Error Codes 16 Fault Conditions 16 No Incoming Line Voltage 16 No Low Voltage 16 Temperature Probe Fault 16 E C O Switch Open 17 Control Bad 17 Combu...

Страница 4: ...ter temperature to exceed the thermostat setting The water temperature would continue to rise until high limit switch operation Contact your dealer or servicer if continued high limit switch operation...

Страница 5: ...cover the instruction manual Keep it on the side of the water heater or nearby for future reference Do obtain new labels from A O Smith for placement on the blanket directly over the existing labels...

Страница 6: ...of all appliances in the enclosure If horizontal ducts are used each opening shall have a free area of not less than one square inch per 2000 Btuh 1 102mm2 kW of the total input of all appliances in t...

Страница 7: ...VER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD ON DIRECT VENT INSTALLATIONS INLET VENT HOOD MUST BE LOCATED 1 30 5cm MINIMUM FROM ANY OPENING IN BUILDING ON DIRECT VENT INSTALL...

Страница 8: ...T TERMINALS AN INTAKE VENT TERMINAL AND AN EXHAUST VENT TERMINAL THE INTAKE VENT TERMINAL IS A 3 45 PVC ELBOW WITH A DOME SHAPE SCREEN AND THE EXHAUST VENT TERMINAL IS A 3 45 PVC ELBOW WITH A MESH WIR...

Страница 9: ...TERMINAL INTAKE VENT TERMINAL FIGURE 10 VERTICAL VENT TERMINAL INSTALLATION IMPORTANT WHEN TERMINATING THROUGH A ROOF THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED 1 Pr...

Страница 10: ...The fittings other than the TERMINATIONS should be equivalent to PVC DWV fittings meeting ASTM D 2665 Use CPVC fittings ASTM F 438 for CPVC pipe and ABS fittings ASTM D 2661 3311 for ABS pipe If CPVC...

Страница 11: ...SWITCH SEE FIGURE 13 The Blocked Outlet Prover Switch is set up to shut the unit off when a build up of positive pressure in the exhaust vent pipe occurs This switch is a positive pressure switch that...

Страница 12: ...DAMAGE PERSONAL INJURY OR LOSS OF LIFE The Gas Leak Test is performed as follows Paint pipe connections upstream of gas control with a rich soap and water solution to test for leaks before operating m...

Страница 13: ...be used in conjunction with this appliance shall also be installed with a properly sized rated and approved temperature ANSI and pressure ASME relief valve s This relief valve shall comply with the st...

Страница 14: ...OLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFERENCE CAN CAUSE THE CONTROLLER TO MALFUNCTION A HIGH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST MALFUN...

Страница 15: ...Dirty burner 10 Clean burner be closed and the blower will continue to run for approximately 10 seconds The control will then return to step 2 9 If a flame is confirmed the control will enter the heat...

Страница 16: ...Not Implemented h s 240 Executed State 4 Not Implemented h s 210 Executed State 10 Not Implemented h s 213 Executed State 13 Not Implemented h s 214 Executed State 14 Not Implemented h s 216 Executed...

Страница 17: ...ntrol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe Possible Cause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring sho...

Страница 18: ...SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMANIN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLYANDELECTRICALWORKAREREQUIRED Before attempting start...

Страница 19: ...ur hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may re...

Страница 20: ...ATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 2000 FEET INSTALLATIONS ABOVE 2000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800...

Страница 21: ...nance and service procedures may also require draining the heater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to ve...

Страница 22: ...MANUALLY OPERATING THE VALVE MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TO AN OPEN DRAIN FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT...

Страница 23: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Страница 24: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD A...

Страница 25: ...CIFICATIONS PAGE 28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Страница 26: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Страница 27: ...TE 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAG...

Страница 28: ...er heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold k...

Страница 29: ...ED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater an...

Страница 30: ...ot greater than 11 0 2 74 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 6 2 1 54 kPa W C pressure Also the manifold pressure should rise during the...

Страница 31: ...on is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warr...

Страница 32: ...32 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E mail parts hotwater com...

Отзывы: