5

  WARNING

THIS WATER HEATER IS A CONDENSING UNIT AND REQUIRES
A DRAIN TO BE LOCATED IN CLOSE PROXIMITY TO ALLOW
THE CONDENSATE TO DRAIN SAFELY. THE CONDENSATE
DRAINS FROM THE UNIT AT THE EXHAUST ELBOW LOCATED
AT THE BOTTOM OF THE UNIT. NOTE: IT IS IMPORTANT THAT
THE CONDENSATE HOSE NOT BE ELEVATED ABOVE THE
EXHAUST ELBOW (SEE FIGURE 3). THE CONDENSATE BUILD-
UP WILL BLOCK THE EXHAUST OUTLET, WHICH WILL CAUSE
IMPROPER OPERATION.

FIGURE 3

  WARNING

DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER
WATER. IMMEDIATELY CALL A QUALIFIED SERVICE
TECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACE
ANY PART OF THE CONTROL SYSTEM AND ANY GAS
CONTROL WHICH HAS BEEN UNDER WATER.

CLEARANCES

These heaters are approved for installation on combustible flooring
in an alcove when the minimum clearances from any combustion
construction are followed as indicated in Figure 4.

In all installations the minimum combustible clearances from any
vent piping shall be 0". Vent piping passing through a combustible
wall or ceiling must be a continuous run (no joints).

A service clearance of 24" (61 cm) should be maintained from
serviceable parts such as relief valves, thermostats, cleanout
openings, drain valves and venting connections.

Always disconnect electrical power before servicing the unit

   

*ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES IN AN ALCOVE.

FIGURE 4

HARD WATER

Where hard water conditions exist, water softening or the threshold
type of water treatment is recommended. This will protect the
dishwashers, coffee urns, water heaters, water piping and other
equipment.

 

 WARNING

Should you choose to apply an insulation blanket to this heater,
you should follow these instructions.  Failure to follow these
instructions can result in fire, asphyxiation, serious personal injury
or death.

Do not apply insulation to the top, or the upper 15" (38 cm) of
the water heater, as this will interfere with safe operation.

Do not cover the temperature & pressure relief valve.

Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.

Do obtain new labels from A.O. Smith for placement on the
blanket directly over the existing labels.

LOCATING THE HEATER

  

WARNING

THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH
AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER
AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR
ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED,
OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY
AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY
THE HEATER’S IGNITER OR MAIN BURNER FLAMES CAUSING
FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT
OPERATION OF GAS APPLIANCES IF INSTALLED 18 INCHES
(46 cm) OR MORE ABOVE THE FLOOR. THIS MAY REDUCE
THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED.

THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.

DO NOT LOCATE THE HEATER WHERE NOISE FROM THE
EXHAUST OR INTAKE WILL BE OBJECTIONABLE. THIS
INCLUDES LOCATIONS CLOSE TO OR ACROSS FROM
WINDOWS AND DOORS. AVOID ANCHORING THE VENT AND
INTAKE PIPES DIRECTLY TO FRAMED WALLS, FLOORS OF
CEILINGS UNLESS RUBBER ISOLATION PIPE HANGERS ARE
USED. THIS PREVENTS ANY VIBRATIONS FROM BEING
TRANSMITTED INTO THE LIVING SPACES.

  WARNING

FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN
CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE
STORED OR USED IN THE SAME ROOM WITH THE HEATER.

When installing the heater, consideration must be given to proper
location. Location selected should be as close to the intake and
exhaust termination points as practicable, with adequate air supply
and as centralized with the piping system as possible.

THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT
WILL BE SUBJECT TO FREEZING.

LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE
LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER
OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE
ADJACENT AREA OR TO LOWER FLOORS OF THE STRUCTURE.

When such locations cannot be avoided, it is recommended that a
suitable drain pan, adequately drained, be installed under the
appliance.

Содержание CYCLONE Xi BTH 400A

Страница 1: ...ETY PLEASE READ THOROUGHLY BEFORE INSTALLINGAND USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactl...

Страница 2: ...SA B149 1 and CSA C22 1 The former is available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 and both documents are available from the National Fire Protec...

Страница 3: ...iagnostic Controller 15 Gas Value LEDs Flashing 15 Error Codes 16 Fault Conditions 16 No Incoming Line Voltage 16 No Low Voltage 16 Temperature Probe Fault 16 E C O Switch Open 17 Control Bad 17 Combu...

Страница 4: ...ter temperature to exceed the thermostat setting The water temperature would continue to rise until high limit switch operation Contact your dealer or servicer if continued high limit switch operation...

Страница 5: ...cover the instruction manual Keep it on the side of the water heater or nearby for future reference Do obtain new labels from A O Smith for placement on the blanket directly over the existing labels...

Страница 6: ...of all appliances in the enclosure If horizontal ducts are used each opening shall have a free area of not less than one square inch per 2000 Btuh 1 102mm2 kW of the total input of all appliances in t...

Страница 7: ...VER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD ON DIRECT VENT INSTALLATIONS INLET VENT HOOD MUST BE LOCATED 1 30 5cm MINIMUM FROM ANY OPENING IN BUILDING ON DIRECT VENT INSTALL...

Страница 8: ...T TERMINALS AN INTAKE VENT TERMINAL AND AN EXHAUST VENT TERMINAL THE INTAKE VENT TERMINAL IS A 3 45 PVC ELBOW WITH A DOME SHAPE SCREEN AND THE EXHAUST VENT TERMINAL IS A 3 45 PVC ELBOW WITH A MESH WIR...

Страница 9: ...TERMINAL INTAKE VENT TERMINAL FIGURE 10 VERTICAL VENT TERMINAL INSTALLATION IMPORTANT WHEN TERMINATING THROUGH A ROOF THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED 1 Pr...

Страница 10: ...The fittings other than the TERMINATIONS should be equivalent to PVC DWV fittings meeting ASTM D 2665 Use CPVC fittings ASTM F 438 for CPVC pipe and ABS fittings ASTM D 2661 3311 for ABS pipe If CPVC...

Страница 11: ...SWITCH SEE FIGURE 13 The Blocked Outlet Prover Switch is set up to shut the unit off when a build up of positive pressure in the exhaust vent pipe occurs This switch is a positive pressure switch that...

Страница 12: ...DAMAGE PERSONAL INJURY OR LOSS OF LIFE The Gas Leak Test is performed as follows Paint pipe connections upstream of gas control with a rich soap and water solution to test for leaks before operating m...

Страница 13: ...be used in conjunction with this appliance shall also be installed with a properly sized rated and approved temperature ANSI and pressure ASME relief valve s This relief valve shall comply with the st...

Страница 14: ...OLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFERENCE CAN CAUSE THE CONTROLLER TO MALFUNCTION A HIGH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST MALFUN...

Страница 15: ...Dirty burner 10 Clean burner be closed and the blower will continue to run for approximately 10 seconds The control will then return to step 2 9 If a flame is confirmed the control will enter the heat...

Страница 16: ...Not Implemented h s 240 Executed State 4 Not Implemented h s 210 Executed State 10 Not Implemented h s 213 Executed State 13 Not Implemented h s 214 Executed State 14 Not Implemented h s 216 Executed...

Страница 17: ...ntrol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe Possible Cause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring sho...

Страница 18: ...SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMANIN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLYANDELECTRICALWORKAREREQUIRED Before attempting start...

Страница 19: ...ur hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may re...

Страница 20: ...ATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 2000 FEET INSTALLATIONS ABOVE 2000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800...

Страница 21: ...nance and service procedures may also require draining the heater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to ve...

Страница 22: ...MANUALLY OPERATING THE VALVE MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TO AN OPEN DRAIN FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT...

Страница 23: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Страница 24: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD A...

Страница 25: ...CIFICATIONS PAGE 28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Страница 26: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Страница 27: ...TE 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAG...

Страница 28: ...er heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold k...

Страница 29: ...ED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater an...

Страница 30: ...ot greater than 11 0 2 74 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 6 2 1 54 kPa W C pressure Also the manifold pressure should rise during the...

Страница 31: ...on is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warr...

Страница 32: ...32 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E mail parts hotwater com...

Отзывы: