background image

11

F.

Contact the manufacturer, supplier, or competent consulting
agency if you have any questions about the application or
installation of PVC, PVC cellular core, ABS or CPVC pipe.

G. Take the time and effort to do a professional job. Shortcuts

will only cause you problems and delays in start-up. The
majority of failures in these systems are the result of
shortcuts and/or improper joining techniques.

2.  SELECTION OF MATERIALS

PRIMER
It is recommended that Tetrahydrofuran (THF) be used to prepare
the surfaces of pipe and fittings for solvent welding. Do not use
water, rags, gasoline or any other substitutes for cleaning PVC
cellular core, ABS or CPVC surfaces. A chemical cleaner such as
MEK may be used.

CEMENT
The cement should be a bodied cement of approximately 500 to
1600 centipoise viscosity containing 10-20% (by weight) virgin PVC
material solvated with tetrahydrofuran (THF). Small quantities of
dimethyl formamide (DMF) may be included to act as a retarding
agent to extend curing time.  Select the proper cement; Schedule
40 cement should be used for Schedule 40 pipe. Never use
all-purpose cements, commercial glues and adhesives or
ABS cement to join PVC or CPVC pipe and fittings.

SAFETY PRECAUTION: PRIMERS AND CEMENTS ARE
EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR
USED NEAR HEAT OR OPEN FLAME.  ALSO, USE ONLY IN A
WELL-VENTILATED AREA.

CONTROLS AND SWITCHES

The BTH-300 & 400 are equipped with four pressure switches.
These switches are essential to the safe and proper operation of
the unit.  All switches are wired in series.  The controller is set up to
shut the unit down whenever there is a failure of any of the switches.
It is important to understand the purpose of each switch.

BLOWER PROVER SWITCH

(SEE FIGURE 13)

The Blower Prover Switch is provided on the heater to verify that
the fan is operating. It is a positive pressure switch whose electrical
contacts are normally open. When the fan increases the pressure
in the burner, the pressure switch will allow the electrical contacts
to close. The pressure switch is connected to the burner tap by a
piece of tygon tubing. This tubing must be connected in order for
the switch to change the electrical contacts. The controller requires
that the electrical contacts on this air flow switch  be open before it

will allow the blower to come on.

BLOCKED OUTLET PROVER SWITCH

(SEE FIGURE 13)

The Blocked Outlet Prover Switch is set up to shut the unit off
when a build-up of positive pressure in the exhaust vent pipe occurs.
This switch is a positive pressure switch that requires an increase
in pressure to change the electrical contacts from normally closed
to open. When this switch prevents the unit from igniting, most
likely the exhaust is blocked by some means. Check to see if the
condensate is allowed to flow freely from the exhaust elbow and
for obstructions in the exhaust venting and exhaust vent terminal.

BLOCKED INLET PROVER SWITCH

(SEE FIGURE 13)

The Blocked Inlet Prover Switch is set up to shut the unit off when
a build-up of negative pressure in the intake vent pipe occurs. This
switch is a negative pressure switch that requires an increase in
negative pressure to change the electrical contacts from normally
closed to open. The switch is connected to the pressure tap on the
flange connected to the inlet of the blower. When this switch prevents
the unit from igniting, most likely the intake is blocked by some
means. Check to see if there is no more than eighty (80) equivalent
feet (24.8m) of four inch PVC vent pipe on the intake. Also verify
that the intake and intake vent terminal is free of obstructions that
may prevent air from entering the unit.

LOW GAS PRESSURE SWITCH

(SEE FIGURE 13)

The Low Gas Switch (LGS) is a single-pole, normally open pressure
switch that will close its contacts when a rising pressure of 5.0 in.
W.C. (1.25Kpa) is encountered. The contacts will open when the
pressure falls below the fixed set point of 5.0 in. W.C. (1.25Kpa)
The LGS monitors the gas supply pressure to the  heater. If the gas
supply falls below 5.0 in. W.C. (1.25Kpa), the main burner is
extinguished (if heater is running) or the heater will not start up.

FIGURE 13

ON/OFF SWITCH

The ON/OFF Switch is a single-pole, single-throw rocker switch.
This switch provides 120V from the line source to the heater.

  

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE
APPLYING ELECTRICITY TO THIS HEATER BE CERTAIN THAT
SUPPLY NEUTRAL WIRE TO GROUND CHECK INDICATES
ZERO VOLTAGE.

HOT SURFACE IGNITER

The Hot Surface Igniter is a device that ignites the main burner by
high temperature (>1800°F or >982°C). When 120VAC is applied
to the igniter, sufficient heat is generated to ignite the main burner.
Although improvements have been made to strengthen the igniter,
it is fragile and care must be taken when handling the igniter to
prevent breakage.

NOTE: LOW GAS IS
LOCATED ON INLET
SIDE OF GAS VALVE.

Содержание CYCLONE Xi BTH 400A

Страница 1: ...ETY PLEASE READ THOROUGHLY BEFORE INSTALLINGAND USING THIS APPLIANCE INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactl...

Страница 2: ...SA B149 1 and CSA C22 1 The former is available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 and both documents are available from the National Fire Protec...

Страница 3: ...iagnostic Controller 15 Gas Value LEDs Flashing 15 Error Codes 16 Fault Conditions 16 No Incoming Line Voltage 16 No Low Voltage 16 Temperature Probe Fault 16 E C O Switch Open 17 Control Bad 17 Combu...

Страница 4: ...ter temperature to exceed the thermostat setting The water temperature would continue to rise until high limit switch operation Contact your dealer or servicer if continued high limit switch operation...

Страница 5: ...cover the instruction manual Keep it on the side of the water heater or nearby for future reference Do obtain new labels from A O Smith for placement on the blanket directly over the existing labels...

Страница 6: ...of all appliances in the enclosure If horizontal ducts are used each opening shall have a free area of not less than one square inch per 2000 Btuh 1 102mm2 kW of the total input of all appliances in t...

Страница 7: ...VER PUBLIC AREA WHERE CONDENSATE OR VAPOR CAN CAUSE NUISANCE OR HAZARD ON DIRECT VENT INSTALLATIONS INLET VENT HOOD MUST BE LOCATED 1 30 5cm MINIMUM FROM ANY OPENING IN BUILDING ON DIRECT VENT INSTALL...

Страница 8: ...T TERMINALS AN INTAKE VENT TERMINAL AND AN EXHAUST VENT TERMINAL THE INTAKE VENT TERMINAL IS A 3 45 PVC ELBOW WITH A DOME SHAPE SCREEN AND THE EXHAUST VENT TERMINAL IS A 3 45 PVC ELBOW WITH A MESH WIR...

Страница 9: ...TERMINAL INTAKE VENT TERMINAL FIGURE 10 VERTICAL VENT TERMINAL INSTALLATION IMPORTANT WHEN TERMINATING THROUGH A ROOF THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED 1 Pr...

Страница 10: ...The fittings other than the TERMINATIONS should be equivalent to PVC DWV fittings meeting ASTM D 2665 Use CPVC fittings ASTM F 438 for CPVC pipe and ABS fittings ASTM D 2661 3311 for ABS pipe If CPVC...

Страница 11: ...SWITCH SEE FIGURE 13 The Blocked Outlet Prover Switch is set up to shut the unit off when a build up of positive pressure in the exhaust vent pipe occurs This switch is a positive pressure switch that...

Страница 12: ...DAMAGE PERSONAL INJURY OR LOSS OF LIFE The Gas Leak Test is performed as follows Paint pipe connections upstream of gas control with a rich soap and water solution to test for leaks before operating m...

Страница 13: ...be used in conjunction with this appliance shall also be installed with a properly sized rated and approved temperature ANSI and pressure ASME relief valve s This relief valve shall comply with the st...

Страница 14: ...OLTAGE LEVEL OR HAS AN APPLIANCE WHICH GENERATES EMF OF RFI INTERFERENCE CAN CAUSE THE CONTROLLER TO MALFUNCTION A HIGH QUALITY POWER CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST MALFUN...

Страница 15: ...Dirty burner 10 Clean burner be closed and the blower will continue to run for approximately 10 seconds The control will then return to step 2 9 If a flame is confirmed the control will enter the heat...

Страница 16: ...Not Implemented h s 240 Executed State 4 Not Implemented h s 210 Executed State 10 Not Implemented h s 213 Executed State 13 Not Implemented h s 214 Executed State 14 Not Implemented h s 216 Executed...

Страница 17: ...ntrol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe Possible Cause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring sho...

Страница 18: ...SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMANIN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLYANDELECTRICALWORKAREREQUIRED Before attempting start...

Страница 19: ...ur hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may re...

Страница 20: ...ATERS ARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 2000 FEET INSTALLATIONS ABOVE 2000 FEET MAY REQUIRE REPLACEMENT OF THE BURNER ORIFICE CALL THE TECHNICAL INFORMATION CENTER AT 800...

Страница 21: ...nance and service procedures may also require draining the heater 1 Turn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to ve...

Страница 22: ...MANUALLY OPERATING THE VALVE MAKE SURE THAT A DRAIN LINE HAS BEEN ATTACHED TO THE VALVE TO DIRECT THE DISCHARGE TO AN OPEN DRAIN FAILURE TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH EXTREMELY HOT...

Страница 23: ...R SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS...

Страница 24: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD A...

Страница 25: ...CIFICATIONS PAGE 28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST B...

Страница 26: ...ECT CIRCULATING LINE OF 180 F 82 C OR BOOSTED WATER IF USED TO INLET WATER LINE TO BOOSTER INSTALL IN ACCORDANCE WITH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR...

Страница 27: ...TE 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAG...

Страница 28: ...er heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold k...

Страница 29: ...ED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater an...

Страница 30: ...ot greater than 11 0 2 74 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 6 2 1 54 kPa W C pressure Also the manifold pressure should rise during the...

Страница 31: ...on is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warr...

Страница 32: ...32 A O SMITH WATER PRODUCTS CO INC 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www hotwater com E mail parts hotwater com...

Отзывы: