Installation
38
Instruction manual BFC
3
is
3.11.3
Adjusting the pressure
1. Remove the cap (4) from the burner pressure regulator (3).
2. Correct the burner pressure by turning the adjusting screw (5), depending
on the correction required:
-
Adjustment screw anticlockwise: burner pressure decreases.
-
Adjustment screw clockwise: burner pressure increases.
3. Cover the opening of the adjusting screw and check the burner pressure
against the value given in the gas table
(3.4.3 "Gas data")
.
4. If the pressure is not set correctly, repeat the preceding steps until the
correct pressure is attained.
5. Fit the cap (4) back on the burner pressure regulator.
6. Activate the "OFF mode" of the electronic controller:
7. If the
MENU
is not displayed:
press .
-
Use and to place the cursor beside
OFF
.
-
Confirm with
.
8. Wait until the fan has stopped, and switch the electronic controller off.
Caution
Failure to wait until the fan stops can cause damage to the appliance.
9. Finish off
(3.11.4 "Finalising")
.
3.11.4
Finalising
1. Shut off the gas supply.
2. Disconnect the two pressure gauges and retighten the sealing screws in the
test nipples.
3. Replace the cover.
Note
Before starting-up the appliance, take time to fill in the warranty card
supplied with the appliance. This enables us to guarantee the quality of our
systems, and to further enhance our warranty procedure.
Please return this card as soon as possible. Your customer will then receive a
warranty certificate with our warranty conditions.
MENU
»OFF
^ ON
È WEEK PROGRAM
Содержание cyclone BFC - 80
Страница 2: ...www aosmithinternational com your installer...
Страница 4: ...4 Instruction manual BFC gis...
Страница 8: ...Table of contents 8 Instruction manual BFC...
Страница 12: ...Introduction 12 Instruction manual BFC 1 gis...
Страница 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Страница 46: ...Draining 46 Instruction manual BFC 6 gis...
Страница 52: ...Status of the appliance 52 Instruction manual BFC 8 gis...
Страница 56: ...Shutting down 56 Instruction manual BFC 10 gis...
Страница 64: ...Main menu 64 Instruction manual BFC 11 gis The relevant display appears REGULATION INTERVAL 40_80 C...
Страница 82: ...Maintenance frequency 82 Instruction manual BFC 14 is...
Страница 92: ...Appendices 92 Instruction manual BFC 17 is...
Страница 94: ...Instruction manual BFC 94...