Installation
32
Instruction manual BFC
3
is
Appliance with parallel flue gas discharge material
The longest pipe must be used to check the maximum length. In this case, the
chimney pipe is the longest. This is 35 metres. This 35 metres is the sum of pipe
sections 1, 2, 3, 4 and 5. The length of the transition piece can be ignored. The
total number of bends used
in the flue gas discharge and air supply
is 8. The
bend in the transition piece can be ignored. According to the table, 2.4 metres
per bend must be added. This brings the total pipe length to:
(2.4 x 8) + 35 = 19.2 + 35 = 54.2m.
This is less than the maximum length of 60 metres stated in the table. The
installation therefore fulfils the requirements.
3.10 Electrical
connection
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations
(1.3 "Regulations")
.
3.10.1
Introduction
Topics covered in this paragraph:
•
Preparation
;
•
Connecting the mains voltage
;
1
2
3
4
5
IMD-0285 R2
Содержание cyclone BFC - 80
Страница 2: ...www aosmithinternational com your installer...
Страница 4: ...4 Instruction manual BFC gis...
Страница 8: ...Table of contents 8 Instruction manual BFC...
Страница 12: ...Introduction 12 Instruction manual BFC 1 gis...
Страница 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Страница 46: ...Draining 46 Instruction manual BFC 6 gis...
Страница 52: ...Status of the appliance 52 Instruction manual BFC 8 gis...
Страница 56: ...Shutting down 56 Instruction manual BFC 10 gis...
Страница 64: ...Main menu 64 Instruction manual BFC 11 gis The relevant display appears REGULATION INTERVAL 40_80 C...
Страница 82: ...Maintenance frequency 82 Instruction manual BFC 14 is...
Страница 92: ...Appendices 92 Instruction manual BFC 17 is...
Страница 94: ...Instruction manual BFC 94...