Instruction manual BFC
15
gis
•
the
Pressure switch
;
•
the
Flame probe
.
2.4.2
Water temperature protection
The electronic controller uses temperatures sensors T1 (7) and T2 (13) to
monitor three temperatures that are important for safety. The table explains the
functioning of the temperature sensors.
Temperature protection
2.4.3
Gas valve
The electronic controller opens the gas valve so that gas can be supplied to the
burner. As a safety measure, the gas valve has a double shut-off. The double
shut-off guarantees complete isolation of the appliance from the gas supply.
To help ensure smooth ignition, the gas valve opens gradually ('softlite").
2.4.4
Fan
The fan (18) provides an optimum air supply when there is a heat demand. As
a safety feature, the fan ensures that any gases present in the combustion
chamber are removed, both before and after combustion. We refer to this as
pre- and post-purge.
The fan speed is continuously monitored by the electronic controller (4). The
electronic controller takes control if the speed of rotation varies too much from
the set value.
2.4.5
Pressure switch
The pressure switch ensures the discharge of flue gases and the supply of
incoming air during the pre-purge and normal running of the appliance. The
default state of the pressure switch is open. When sufficient pressure difference
is reached, the pressure switch closes. However, in the event of a fault, the
pressure switch is tripped open, and the heating cycle is interrupted. The table
shows the trip point per appliance.
Note
The trip point of the pressure switch is not adjustable.
Pressure switch trip points
Protection
Description
Against frost
(T1 < 5°C or T2 < 5°C)
The frost protection cuts in. The water is heated to 20°C.
For maximum water temperature
(T1 > 85°C or T2 > 85°C)
The high-limit safeguard serves to prevent overheating and/or excessive
formation of scale in the appliance. If the high-limit safeguard is activated, the
heating is stopped. This causes the water in the tank to cool down. Once the
water has cooled sufficiently (T1 < 78°C), the electronic controller resets the
appliance.
For extra safety
(T1 > 93°C or T2 > 93°C)
A lockout error of the water heater controller takes place. The controller must
be manually reset before the appliance can resume operation
(8.3 "Error
conditions")
. The reset may only be performed if T
1
<78°C.
Appliance Closing pressure difference Opening pressure difference
BFC 80
> 1005 Pa
< 975 Pa
BFC 100
> 1145 Pa
< 1115 Pa
Содержание cyclone BFC - 80
Страница 2: ...www aosmithinternational com your installer...
Страница 4: ...4 Instruction manual BFC gis...
Страница 8: ...Table of contents 8 Instruction manual BFC...
Страница 12: ...Introduction 12 Instruction manual BFC 1 gis...
Страница 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Страница 46: ...Draining 46 Instruction manual BFC 6 gis...
Страница 52: ...Status of the appliance 52 Instruction manual BFC 8 gis...
Страница 56: ...Shutting down 56 Instruction manual BFC 10 gis...
Страница 64: ...Main menu 64 Instruction manual BFC 11 gis The relevant display appears REGULATION INTERVAL 40_80 C...
Страница 82: ...Maintenance frequency 82 Instruction manual BFC 14 is...
Страница 92: ...Appendices 92 Instruction manual BFC 17 is...
Страница 94: ...Instruction manual BFC 94...