Instruction manual BFC
68
13.2 Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General errors
Symptom
Cause
Solution
Remark
Gas smell
Gas leak
Warning
Close the main gas valve immediately.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Warning
Contact your installation engineer or local gas company
immediately.
Display is off
Appliance is turned off
Start the appliance up
(9 "Starting and running")
No supply voltage
present
1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
See the BFC electrical diagram
(17 "Appendices")
If the error persists, consult your installation engineer.
Defective fuse(s)
Replace fuse(s)
To replace the fuses, you must contact your installation engineer.
Содержание cyclone BFC - 80
Страница 2: ...www aosmithinternational com your installer...
Страница 4: ...4 Instruction manual BFC gis...
Страница 8: ...Table of contents 8 Instruction manual BFC...
Страница 12: ...Introduction 12 Instruction manual BFC 1 gis...
Страница 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Страница 46: ...Draining 46 Instruction manual BFC 6 gis...
Страница 52: ...Status of the appliance 52 Instruction manual BFC 8 gis...
Страница 56: ...Shutting down 56 Instruction manual BFC 10 gis...
Страница 64: ...Main menu 64 Instruction manual BFC 11 gis The relevant display appears REGULATION INTERVAL 40_80 C...
Страница 82: ...Maintenance frequency 82 Instruction manual BFC 14 is...
Страница 92: ...Appendices 92 Instruction manual BFC 17 is...
Страница 94: ...Instruction manual BFC 94...