Installation
36
Instruction manual BFC
3
is
3.11 Checking the supply
pressure and burner
pressure
Note
Before starting the appliance and/or checking the supply pressure and
burner pressure, you must fill
(5 "Filling")
the appliance.
Attention
Before starting up for the first time or after conversion, you must always
check the supply pressure and burner pressure.
Note
The easiest way to check the gas pressures is by using two pressure
gauges. This procedure assumes that these two gauges are available.
Gas control
3.11.1
Preparation
To check the supply pressure and burner pressure, proceed as follows:
1. Isolate
(10.3 "Electrically isolating the appliance")
the water heater from the
power supply.
2. Undo the screws of the plastic covers.
3. Carefully remove the covers from the top of the appliance. The electrical
section is now visible.
Legend
Only applicable numbers are
mentioned.
1. supply pressure test nipple
2. burner pressure test nipple
3. burner pressure regulator
4. burner pressure control cap
5. burner pressure control
adjusting screw
1
2
3
5
4
IMD-0079a R2
Содержание Cyclone BFC - 30
Страница 2: ...www aosmithinternational com your installer...
Страница 4: ...4 Instruction manual BFC gis...
Страница 8: ...Table of contents 8 Instruction manual BFC...
Страница 27: ...Instruction manual BFC 27 is Types of appliances IMD 0468 R0 C43 C13 C53 B23 C33...
Страница 42: ...Conversion to a different gas category 42 Instruction manual BFC 4 is...
Страница 48: ...Draining 48 Instruction manual BFC 6 gis...
Страница 54: ...Status of the appliance 54 Instruction manual BFC 8 gis...
Страница 58: ...Shutting down 58 Instruction manual BFC 10 gis...
Страница 82: ...is Instruction manual BFC 82...
Страница 84: ...Maintenance frequency 84 Instruction manual BFC 14 is...
Страница 94: ...Appendices 94 Instruction manual BFC 17 is...
Страница 96: ...Instruction manual BFC 96...