Instruction manual BFC
29
is
Appliance with concentric flue gas discharge material
According to the table, the maximum length allowed is 40 metres, and there may
be up to seven 90 degree bends. Both requirements are fulfilled.
Specifications
Attention
For type C13 and C33 installations,A.O. Smith prescribes the use of a roof
or wall-mounted terminal, exclusively of a type approved for the appliance. Use
of an incorrect roof or wall-mounted flue terminal can cause the installation to
malfunction.
IMD-0284 R1