background image

21

plannInG the vent sYsteM

Plan the route of the vent system from the discharge of the blower 

to the planned location of the vent terminal. Refer to VAA instruction 

on page 25 while planning the vent system.
1.  Layout total vent system to use a minimum of vent pipe and elbows.
2.  This water heater is capable of venting  flue gases equivalent to 

25’ (7.6 m) of 2” pipe, 65’ (19.8 m) of 3” pipe, or 128’ (39.0 m) of 

4” pipe as listed in Table 1.

taBle 1

 

Number of 

2” Maximum 

3” Maximum 

4” Maximum

  90° Elbows  Pipe - ft. (m) 

Pipe - ft. (m) 

Pipe - ft. (m)

 

20 (6.1) 

60 (18.3) 

120 (36.6)

 

15 (4.6) 

55 (16.8) 

112 (34.1)

 

10 (3.0) 

50 (15.2) 

104 (31.7)

 

-- 

45 (13.7) 

96 (29.3)

 

-- 

40 (12.2) 

88 (26.8)

 

-- 

35 (10.7) 

80 (24.3)

The minimum vent lengths for each of the pipe sizes is one 90° on top of  

the unit plus 2’ (61cm) of straight pipe and the appropriate termination.

  note:

  The equivalent feet (m) of pipe listed above are exclusive 

of  the  termination. That is, the termination, with an installed 

screen, is assumed to be in the system and the remainder of the 

system must not exceed the lengths discussed above.

3.  The blower discharge adapter is made to accept only straight 

sections of 2”  pipe.  To start, a minimum of 2 inches (5.1 cm) of 2” 

pipe must be attached to the blower discharge, see Figure 17.

  If using 2” inch vent pipe:

  A minimum of 2 inches (5.1 cm) must be attached to the blower 

before  the  first  elbow. After  the  first  elbow  add  the  additional 

venting  required  for  the  installation. The  total  system  cannot 

exceed the lengths discussed above, where each elbow is equal 

to 5 feet (1.5 m) of straight pipe.

  If using 3” or 4” inch vent pipe:

  Two inches (5.1 cm) of pipe must be attached to blower discharge before 

adding a reducer to acquire desired pipe diameter. An appropriately 

sized 45 degree schedule 40 DWV elbow (field supplied) vent terminal 

must be obtained with an equivalent screen (supplied in vent kit). 

The total system cannot exceed equivalent pipe lengths discussed 

above where each elbow is equal to 5 feet (1.5 m) of straight pipe  

(3” vent pipe) or 8 feet (2.4 m) of straight pipe (4” vent pipe).

u.s. Installations

note: 

This  unit  can  be  vented  with  PVC  pipe  materials  (DWV 

ASTM-D2665 or CSA B181.2; Schedule 40, 80, 120 ASTM-D1785 

or CSA B137.3; or SDR Series ASTM-D2241 or CSA B137.3), CPVC 

pipe materials (CPVC41 ASTM-D2846 or CSA B137.6; Schedule 40, 

80 ASTM-F441 or CSA B137.6; or SDR Series ASTM-F442), ABS pipe 

materials (Schedule 40 DWV ASTM-D2661 or CSA B181.1). Fittings, 

other than TERMINATION should be equivalent to PVC-DWV fittings 

meeting ASTM D-2665 (Use CPVC fittings, ASTM F-438 for CPVC pipe 

and ABS fittings, ASTM D-2661/3311 for ABS pipe). If CPVC or ABS 

pipe and fittings are used, then proper cement must be used for all joints, 

including joining pipe to Termination (PVC Material). If local codes do not 

allow use of PVC termination when a material other than PVC is used 

for venting, then an equivalent fitting of that material may be substituted 

if screen in PVC terminal is removed and inserted into new fitting.
PVC  Materials  should  use ASTM  D-2564  Grade  Cement;  CPVC 

Materials should use ASTM F-493 Grade Cement and ABS Materials 

should use ASTM D-2235 Grade Cement.

canadian Installations

Installation of this water heater must comply with CAN/CSA B149.1 

- Natural Gas and Propane Installation Code which requires the vent 

system components be certified to ULC S636.
This water heater has been design certified to be vented with PVC 

pipe certified and marked as complying with ULC S636. This water 

heater is supplied with a 2 inch 22.5 degree termination elbow that is a 

special fitting that must be used with this appliance. Any outlet piping, 

fittings and glue used to vent this appliance that is not supplied by the 

manufacturer must comply with the ULC S636 requirements.
If water heater is being installed as a replacement for an existing power 

vented heater in pre-existing venting, a thorough inspection of existing 

venting system must be performed prior to any installation work. Verify 

that correct material as detailed above has been used, and that minimum 

or maximum vent lengths and terminal location as detailed in this manual 

have been met. Carefully inspect entire venting system for any signs 

of cracks or fractures, particularly at joints between elbows and other 

fittings and straight runs of vent pipe. Check system for signs of sagging 

or other stresses in joints as a result of misalignment of any components 

in system. If any of these conditions are found, they must be corrected in 

accordance with venting instructions in this manual before completing  

installation and putting water heater into service.

note:

 

a.

  For  water  heaters  in  locations  with  high  ambient 

temperatures  (above  100°F)  it  is  recommended  that  CPVC  pipe 

and fittings be used. 

B.

 A 22.5 degree elbow (2” vent pipe) or a 45 

degree elbow (3” and 4” vent pipe) with an installed screen VENT 

TERMINAL must be used in all cases.
4.  There will be some installations where condensate will be formed 

in the horizontal runs of the vent system. This condensate will 

run into the condensate boot attached to the blower and out the 

fitting. The water heater is shipped with condensate hose that 

attaches to the fitting on the condensate boot. No other Tee or 

fitting is required. See Figures 17, 20 and 21.

condensate

This water heater is a condensing unit and requires a drain to be located 

in close proximity to allow condensate to drain safely. One hose from 

blower housing, two flexible hoses from blower outlet adaptor, along with 

another flexible hose from VAA if installed, run to barb fittings on vent 

pipe assembly #2. Hose is clamped by rubber clips and flexible hoses 

by a clamp on jacket top cover. See Figure 17. Condensate drains from 

the unit at the exhaust tee located at the bottom of the unit (see figure 

16). Condensate from this water heater is mildly acidic. Please note 

that some local codes require that condensate is treated by using a pH 

neutralizing filter prior to disposal.
NOTE:  It  is  important  that  the  field  supplied  drain  lines  beyond 

the  1/2”  adaptor  of  vent  pipe  assembly  #1  should  be  installed 

continuously tilted downward toward an appropriate drain. See Figure 

16. If these instructions are not followed or if condensate drain line 

is blocked, water will spill from condensate trap. Do not block the 

holes in the hex plug on top of a small tee in vent pipe assembly 

#1. As with every water heater installation, a drain pan should be 

used to prevent water damage to surrounding area. If necessary, 

a condensate pump with an incorporated reservoir may be used to 

pump water to an appropriate drain. To avoid condensate spillage, 

select a pump with an overflow switch.
Caution must be used to ensure that drain is free and clear of debris 

and  will  not  allow  backflow  through  the  condensate  drain  line. 

Consideration must be given to avoid freezing of the condensate 

lines which could result in excessive build up of condensate inside 

the water heater. Waterproof heat tape may be required to prevent 

freezing  of  condensate  lines.  Please  ensure  that  the  outlet  of 

condensate drain does not create a slippery condition which could 

lead to personal injury. Care should be taken to ensure there is no 

kink or twist in any condensate hose. If a VAA is not installed, the 

unused barb fitting in vent pipe assembly #2 should be plugged using 

one of the break-away plugs.

Breathing Hazard - Carbon Monoxide Gas

• 

Do NOT block the holes in the hex plug of vent pipe 

  assembly #1.

• 

Do NOT elevate any portion of the field supplied drain 

  line beyond the 1/2" adaptor above the adaptor. This 

  must be true for entire length of the drain line including 

  the exit into an appropriate drain.

• 

Condensate lines must be free and clear of debris and 

 

must not allow back flow through drain line. Condensate 

 

lines must be able to flow freely to an appropriate drain.

• 

Do not allow condensate lines to become crimped closed.

• 

Analyze entire vent system to make sure that condensate

  will not become trapped in a section of vent pipe and 

  therefore reduce open cross sectional area of vent.

Breathing carbon monoxide can cause brain damage or death.

Always read and understand instruction manual.

Содержание BTX-80 SERIES 100

Страница 1: ...MODEL BTX 80 SERIES 100 ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED...

Страница 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Страница 3: ...3 GENERAL SAFETY INFORMATION...

Страница 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Страница 5: ...d Cleveland OH44131 NFPAdocumentsarealsoavailablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the...

Страница 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Страница 7: ...Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K O...

Страница 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued...

Страница 9: ...ship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water tempe...

Страница 10: ...cs All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynami...

Страница 11: ...talled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water s...

Страница 12: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Страница 13: ...e the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is insta...

Страница 14: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 19 26 fo...

Страница 15: ...e requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water...

Страница 16: ...the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized T...

Страница 17: ...P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Syste...

Страница 18: ...system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Страница 19: ...uctions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may...

Страница 20: ...0 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm...

Страница 21: ...rectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or fra...

Страница 22: ...hat the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower h...

Страница 23: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Страница 24: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Страница 25: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4...

Страница 26: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Страница 27: ...and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleanin...

Страница 28: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Страница 29: ...R buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all ele...

Страница 30: ...c does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing t...

Страница 31: ...cal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chl...

Страница 32: ...uld be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner oper...

Страница 33: ...have a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALV...

Страница 34: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Страница 35: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Страница 36: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Страница 37: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Страница 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Страница 39: ...unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVI...

Страница 40: ...40 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2010 A O Smith Corporation All rights reserved...

Отзывы: