background image

20

terMInatIon clearances sIdewall power vent

V

X

VENT TERMINAL

AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

v

v

A

G

V

FIXED

CLOSED

FIXED

CLOSED

OPERABLE

OPERABLE

V

C

B

B

B

B

F

B

V

V

A

J

V

H

M

X

X

V

V

K

B

E

D

L

POWER VENT

(using room air for combustion)

EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION

fIGure 15.

 

Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion.

canadIan InstallatIons 

1

us InstallatIons 

2

canadIan InstallatIons 

1

us InstallatIons 

2

a

Clearance above grade, 

veranda, porch, deck or 

balcony

12 inches (30 cm)

12 inches (30 cm)

h

Clearance to each side 

of center line extended 

above meter/regulator  

assembly

3 feet (91 cm) within a height 15 feet 

(4.5 m) above the meter/ 

regulator assembly

3 feet (91 cm) within a 

height 15 feet (4.5 m) 

above the meter/regulator 

assembly*

B

Clearance to window 

or door that may be 

opened

6 inches (15 cm) for appliances up to 

10,000 Btu/hr (3 kW), 12 inches (30 

cm) for appliances between 10,000 

Btu/hr (3 kW) and 100,000 Btu/hr (30 

kW), 36 inches (91 cm) for appliances 

above 100,000 Btu/hr (30 kW)

4 feet (1.2 m) below 

or to side of opening; 

1 foot (30 cm) above 

opening

I

Clearance to service 

regulator vent outlet 

          

3 feet (91 cm)

3 feet (91 cm)*

c

Clearance to 

permanently closed 

window

12 inches (30 cm)*

12 inches (30 cm)*

j

Clearance to a non 

mechanical air supply 

inlet into building or 

combustion air inlet to 

any other appliance

6 inches (15 cm) for appliances up 

to 10,000 Btu/hr (3 kW), 12 inches 

(30 cm) for appliances between 

10,000 Btu/hr (3 kW) and 100,000 

Btu/hr (30kW), 36 inches (91cm) 

for appliances above 100,000 Btu/

hr (30 kW)

4 feet (1.2 m) below or to 

side of opening; 1 foot  

(30 cm) above opening.

d

Vertical clearance to 

ventilated soffit located 

above the terminal 

within a horizontal 

distance of 2 feet (61 

cm) from the center line 

of the terminal

12 inches (30 cm)*

12 inches (30 cm)*

K

Clearance to a 

mechanical air supply 

inlet

6 feet (1.83 m)

3 feet (91 cm) above if 

within 

10 feet (3 m) horizontally

e

Clearance to 

unventilated soffit

12 inches (30 cm)*

12 inches (30 cm)*

l

Clearance above paved 

sidewalk or paved 

driveway located on 

public property

7 feet (2.13 m)†

7 feet  (2.13 m) †

f

Clearance to outside 

corner

2 feet (60 cm)*

2 feet (60 cm)*

M

Clearance under 

veranda, porch, deck, or 

balcony

12 inches (30 cm) ‡

12 inches (30 cm) ‡

G

Clearance to inside 

corner

18 inches (45 cm)*

18 inches (45 cm)*

1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.

2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.

† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.

vent pIpe terMInatIon

The first step is to determine where the vent pipe will terminate. See 

Figures 15, 20 and 21. The vent may terminate through a sidewall as 

shown in Figure 20 or through the roof as shown in Figure 21.

The  vent  system  must  terminate  so  that  proper  clearances  are 

maintained  as  cited  in  local  codes  or  the  current  edition  of  the 

National Fuel Gas Code, (ANSI Z223.1, 12.9.1 through 12.9.4) or the 

Natural Gas and Propane Installation Code (CAN/CSA-B149.1).

Instructions on proper installation through a sidewall are provided 

in Figure 15.
Plan the vent system layout so that proper clearances are maintained 

from plumbing and wiring.
Vent pipes serving power vented appliances are classified by building 

codes as “vent connectors”. Required clearances from combustible 

materials  must  be  provided  in  accordance  with  information  in 

this  manual  under  LOCATING THE  NEW  WATER  HEATER  and 

INSTALLING THE  WATER  HEATER,  and  with  the  National  Fuel 

Gas Code and local codes.

Содержание BTX-80 SERIES 100

Страница 1: ...MODEL BTX 80 SERIES 100 ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED...

Страница 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Страница 3: ...3 GENERAL SAFETY INFORMATION...

Страница 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Страница 5: ...d Cleveland OH44131 NFPAdocumentsarealsoavailablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the...

Страница 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Страница 7: ...Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K O...

Страница 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued...

Страница 9: ...ship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water tempe...

Страница 10: ...cs All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynami...

Страница 11: ...talled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water s...

Страница 12: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Страница 13: ...e the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is insta...

Страница 14: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 19 26 fo...

Страница 15: ...e requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water...

Страница 16: ...the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized T...

Страница 17: ...P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Syste...

Страница 18: ...system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Страница 19: ...uctions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may...

Страница 20: ...0 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm...

Страница 21: ...rectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or fra...

Страница 22: ...hat the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower h...

Страница 23: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Страница 24: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Страница 25: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4...

Страница 26: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Страница 27: ...and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleanin...

Страница 28: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Страница 29: ...R buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all ele...

Страница 30: ...c does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing t...

Страница 31: ...cal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chl...

Страница 32: ...uld be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner oper...

Страница 33: ...have a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALV...

Страница 34: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Страница 35: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Страница 36: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Страница 37: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Страница 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Страница 39: ...unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVI...

Страница 40: ...40 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2010 A O Smith Corporation All rights reserved...

Отзывы: