GAS PIPING

Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation
codes for your area.

Size the main gas line in accordance with Table 2.   The figures
shown are for straight lengths of pipe at 0.5 in. W.C. pressure
drop, which is considered normal for low pressure systems.
Note:  Fittings such as elbows, tees and line regulators will add
to the pipe pressure drop.  Also refer to the latest version of the
National Fuel Gas Code.

 WARNING

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER
THAN 14.0" W.C.(3.48 kPa) - NATURAL GAS, 14.0" W.C.(3.48kPa)
EXPOSURE TO HIGHER SUPPLY PRESSURE MAY CAUSE
DAMAGE TO THE GAS VALVE WHICH COULD RESULT IN FIRE
OR EXPLOSION.  IF OVERPRESSURE HAS OCCURRED SUCH
AS THROUGH IMPROPER TESTING OF GAS LINES OR
EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS
VALVE MUST BE CHECKED FOR SAFE OPERATION.  MAKE SURE
THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND
THE SAFETY VENT VALVES ARE PROTECTED AGAINST
BLOCKAGE.  THESE ARE PARTS OF THE GAS SUPPLY SYSTEM,
NOT THE HEATER.  VENT BLOCKAGE MAY OCCUR DURING ICE
STORMS.

TABLE 2 - GAS SUPPLY LINE SIZES (IN INCHES)*

MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR

(Based upon a Pressure Drop of 0.5 inch Water Column and

0.6 specific Gravity Gas and max. gas pressure of 0.5 psig)

LENGTH

NOMINAL IRON PIPE SIZES (INCHES)

IN FEET  1/2"   3/4"   1"  1 1/4"  1 1/2"    2"   2 1/2"  3"

4"

10

175

360 680 1400 2100 3960 6300 11000 23000

20

120

250 465

950 1460 2750 4360 7700 15800

30

97

200 375

770

1180 2200 3520 6250 12800

40

82

170 320

660

990 1900 3000 5300 10900

50

73

151 285

580

900 1680 2650 4750

9700

60

66

138 260

530

810 1520 2400 4300

8800

70

61

125 240

490

750 1400 2250 3900

8100

80

57

118 220

460

690 1300 2050 3700

7500

90

53

110 205

430

650 1220 1950 3450

7200

100

50

103 195

400

620 1150 1850 3250

6700

125

44

93 175

360

550 1020 1650 2950

6000

150

40

84 160

325

500

950 1500 2650

5500

175

37

77 145

300

460

850 1370 2450

5000

200

35

72 135

280

430

800 1280 2280

4600

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING
FROM CONTAMINANTS IN THE GAS WAYS.  SUCH FOULING MAY
CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE
INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE
ATTACHING THE GAS LINE, BE SURE THAT ALL GAS PIPE IS
CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY
LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR
DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG.
9).  THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT
SUBJECT TO FREEZING CONDITIONS.  INSTALL IN
ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS
SUPPLIERS.  REFER TO THE LATEST VERSION OF THE NATIONAL
FUEL GAS CODE.

To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipe to gas valve inlet.

Apply joint compounds (pipe dope) sparingly and only to the
male threads of pipe joints.  Do not apply compounds to the first
two threads.  Use compounds resistant to the action of liquefied
petroleum gases.

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS
LEAKAGE.

 

 Use soap and water solution or other material

acceptable for the purpose in locating the leaks. 

 DO NOT USE

MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION
FOR THIS PURPOSE.

DISCONNECT THE HEATER AND ITS MANUAL GAS SHUTOFF
VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY
SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG.  GAS
SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM
THE HEATER FOR TEST PRESSURES OF 1/2 PSIG OR LESS. THE
APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST BE
ISOLATED FROM THE SUPPLY PRESSURE TEST BY CLOSING
THE MANUAL GAS SHUTOFF VALVE.

GAS PIPING AND DIRT LEG INSTALLATION

FIGURE 9

PURGING

Gas line purging is required with new piping or systems in which
air has entered.

 CAUTION

PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED
IN THIS TYPE GAS SERVICE.  TO AVOID RISK OF FIRE OR
EXPLOSION, PURGE DISCHARGE MUST NOT ENTER CONFINED
AREAS OR SPACES WHERE IGNITION CAN OCCUR.  THE AREA
MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION
MUST BE INACTIVATED OR REMOVED.

GAS METER SIZE — NATURAL GASES ONLY

Be sure the gas meter has sufficient capacity to supply the full
rated gas input of the water heater as well as the requirements
of all other gas fired equipment supplied by the meter.  If gas
meter is too small, ask the gas company to install a larger meter
having adequate capacity.

GAS PRESSURE REGULATOR

The gas pressure regulator is built into the gas valve and is
equipped to operate on the gas specified on model and rating
plate.  The regulator is factory adjusted to deliver gas to burner at
correct water column pressure allowing for a nominal pressure
drop through the controls.

The minimum gas supply pressure for input adjustment must
not be less than 4.5" w.c. for natural gas.

Содержание BTR 151 THRU 201/A

Страница 1: ...in U S A 1004 PART NO 196308 001 ADIVISION OFA O SMITH CORPORATION McBEE SOUTH CAROLINA USA www aosmithwaterheaters com CAUTION TEXT IN BLACK BOLD TYPE OR UNDERLINED CONTAINS INFORMATION RELATIVE TO Y...

Страница 2: ...the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and the National Electrical Code NFPA 70 documents are available fro...

Страница 3: ...ater is due to a corrosive atmosphere Refer to the limited warranty for complete terms and conditions IMPROPER COMBUSTION WARNING ATTICAND OREXHAUSTFANSOPERATINGONTHEPREMISES WITHAWATER HEATER CAN RES...

Страница 4: ...the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply Failure to make this reduction would result in an overfiring of the heater causing s...

Страница 5: ...R BLOWER ASSEMBLY All units are equipped with a exhaust inducer The inducer assists in drawing in fresh air to the unit for combustion and then assists in dispensing the combustion by products into th...

Страница 6: ...D BE LOCATEDINANAREAWHERELEAKAGEFROMTHEHEATEROR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENTAREAORTOLOWERFLOORSOFTHESTRUCTURE WHEN SUCH LOCATIONS CANNOT BEAVOIDED ASUITABLE DRAINPANSHOULDBEIN...

Страница 7: ...protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with these heaters This water heater must be vente...

Страница 8: ...ell Excessive pressure may develop in such closed systems causing premature tank failure or intermittent relief valve operation This is not a warranty failure An expansion tank or a similar device may...

Страница 9: ...THAT ALL GAS PIPE IS CLEANONTHEINSIDE TOTRAPANYDIRTORFOREIGNMATERIALINTHEGASSUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIMENT TRAP OR DRIP LEG MUST BE INCORPORATED IN THE PIPING SEE FIG 9 THE DIRT LEG...

Страница 10: ...with the latest version of the National Electrical Code ANSI NFPA No 70 must FIGURE10 SINGLEUNITWIRINGDIAGRAM conform to all local code authority having jurisdiction AN ELECTRICAL GROUND IS REQUIRED...

Страница 11: ...temperature and pressure relief valve of adequate capacity is installed on the heater The locations shown in the installation diagrams on the following pages are typical The discharge opening of the t...

Страница 12: ...D NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FO...

Страница 13: ...E TOGGLESWITCHMUSTBECLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOTOPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALLLINETEMPERATURECONTROLINANUNINSULATED TEEBEYONDTHEDISHWASHINGMACH...

Страница 14: ...ons shown in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of...

Страница 15: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 16: ...RS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEA...

Страница 17: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Страница 18: ...in burner before going into lockout After the controller tries three times it will wait one hour before trying to light the unit again This cycle will continue until the main burners are ignited or th...

Страница 19: ...tes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go on to the next step 7 Turn gas control knob counterclockwise to ON...

Страница 20: ...INJURYOCCURS VARIES WITH THE PERSON S AGE AND TIME OF EXPOSURE THE SLOWER RESPONSETIMEOFCHILDREN AGEDORDISABLEDPERSONS INCREASES THE HAZARDS TO THEM NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP...

Страница 21: ...o decrease gas pressure and input rate 4 Clock the meter as in step 2 above 5 Repeat steps 3 and 4 until the specified input rate is achieved 6 Turn the gas control knob to PILOT Remove the pressure g...

Страница 22: ...for cleaning inspection or removal of inner parts you obtain two new nipple collars part no 74060 The nipple collars on the heater will usually be damaged when removed New pipe collars will insure th...

Страница 23: ...sed DELIMINGUSINGFLO JUGMETHOD UN LIME in the 5 gallon size is recommended for deliming of the BT 80 100 models UN LIME with the necessary hoses and fittings to delime your heater is also available as...

Страница 24: ...luding the complete model and serial number as it appears on the product Refer to the parts list for more information REPLACEMENT PARTS 7 Lower container you may have to place the container on its emp...

Страница 25: ...engages Prover Switch Ignition Control Board provides power to Silicon Nitride Ignitor Silicon Nitride Ignitor warms up for 20 seconds Ignition Control Board opens Gas Valve Ignition Control Board sh...

Страница 26: ...Replace dual bulb controller if differential is too wide greater than 4 F Heater recovery is slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Dra...

Страница 27: ...valves etc is installed in the cold water supply the heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times T...

Страница 28: ...28 A O SMITH WATER PRODUCTS COMPANY 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www aosmithwaterheaters com E MAIL parts hotwater com...

Отзывы: