RELIEF VALVE

At least once a year, the temperature and pressure relief valve
should be checked to ensure that it is in operating condition.  Lift
the lever at the top of the valve several times until the valve seats
properly and operates freely.

If the appliance installation includes other relief valves, such as
in “remote” storage tanks etc., check their relief valve operation
with the same frequency.

 WARNING

THE WATER PASSING OUT OF THE VALVE DURING THIS
CHECKING OPERATION MAY BE EXTREMELY HOT.  AVOID
CONTACT AND DISCHARGE SAFELY TO PREVENT WATER
DAMAGE.

If the temperature and pressure relief valve on the heater
discharges periodically or continuously, a problem exists.  This
may be due to unusually high water temperatures or pressures
in the system, or to a faulty relief valve.  Contact your dealer or a
qualified service technician to find the cause of the problem and
to correct it.  This may also be due to thermal expansion in a
closed water supply system.  Contact the water supplier or local
plumbing inspector on how to correct this situation.  

DO NOT

PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE.

 WARNING

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO
SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO
THE APPLIANCE.

HOT WATER ODOR

On occasion, hot water may develop a strong odor.  If this occurs
drain the heater completely, flush thoroughly, and refill.  If the
problem persists, chlorination of the heater and replacement of
the factory installed magnesium anodes with aluminum anodes
may correct the condition.

Occasionally water softener companies recommend removal of
heater anodes for odor reasons.

 CAUTION

Unauthorized removal of the anode(s) will void the warranty.
For further information contact your dealer.

ANODE ROD INSPECTION

The heater tank is equipped with anode rods to provide corrosion
control.  At least once a year the anode rods should be checked
to determine if replacement is necessary.  Initially the anode
rods are approximately 7/8" in diameter with a 1/8" diameter
steel core wire running down the center of the anode material.
THE ANODES SHOULD BE REPLACED when the 1/8"  diameter
core wire is visible as this means that the  anode material has
been expended in the control of corrosion.

For models with top inlet and outlet, it is recommended that,
before removing the inner cover for cleaning, inspection or
removal of inner parts, you obtain two new nipple collars, part
no. 74060.  The nipple collars on the heater will usually be
damaged when removed.  New pipe collars will insure that the
seal is such as to prevent leakage of flue products when properly
installed.

NOTE:

 

 

Anode rod inspection may need to be made more

frequently in areas subject to acid rain that obtains their water
supply from surface water as the low pH will accelerate anode
activity.

CAUTION:

 

 

Close cold water inlet valve serving heater and open

nearby hot water faucet to relieve the pressure in the heater
before attempting to remove anode(s) for inspection.

FLUSHING

1. Turn off the heater electrical disconnect switch.

2. Open the drain valve and allow water to flow until it runs clean.

3. Close the drain valve when finished flushing.

4. Turn on the heater electrical disconnect switch.

DRAINING

The heater must be drained if it is to be shut down and exposed
to freezing temperatures.  Maintenance and service procedures
may also require draining the heater.

1. Turn off the heater electrical disconnect switch.

2. Close the cold water inlet valve to heater.

3. Open a nearby hot water faucet to vent the system.

4. Open the heater drain valve.

5. If the heater is being drained for an extended shutdown, it is

suggested the drain valve be left open during this period.

•  Follow FILLING instructions when restoring hot water
   service.

RECOMMENDED PROCEDURE FOR

PERIODIC REMOVAL OF LIME DEPOSITS

FROM TANK TYPE COMMERCIAL WATER

HEATERS

The amount of calcium carbonate (lime) released from water is
in direct proportion to water temperature and usage, see chart.
The higher the water temperature or water usage, the more lime
deposits are dropped out of the water.  This is the lime scale
which forms in pipes, heaters and on cooking utensils.

Lime accumulation not only reduces the life of the equipment
but also reduces efficiency of the heater and increases fuel
consumption.

The usage of water softening equipment greatly reduces the
hardness of the water.  However, this equipment does not always
remove all of the hardness (lime).  For this reason it is
recommended that a regular schedule for deliming be
maintained.

The time between cleaning will vary from weeks to months
depending upon water conditions and usage.

Refer to A. O. Smith booklet, Form No. 4800, entitled “Why? When
and How” for detailed description on tank inspection and
cleanout. UN•LIME

®

 and the booklet may be obtained through

your A. O. Smith dealer or distributor.

Содержание BTR 151 THRU 201/A

Страница 1: ...in U S A 1004 PART NO 196308 001 ADIVISION OFA O SMITH CORPORATION McBEE SOUTH CAROLINA USA www aosmithwaterheaters com CAUTION TEXT IN BLACK BOLD TYPE OR UNDERLINED CONTAINS INFORMATION RELATIVE TO Y...

Страница 2: ...the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and the National Electrical Code NFPA 70 documents are available fro...

Страница 3: ...ater is due to a corrosive atmosphere Refer to the limited warranty for complete terms and conditions IMPROPER COMBUSTION WARNING ATTICAND OREXHAUSTFANSOPERATINGONTHEPREMISES WITHAWATER HEATER CAN RES...

Страница 4: ...the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply Failure to make this reduction would result in an overfiring of the heater causing s...

Страница 5: ...R BLOWER ASSEMBLY All units are equipped with a exhaust inducer The inducer assists in drawing in fresh air to the unit for combustion and then assists in dispensing the combustion by products into th...

Страница 6: ...D BE LOCATEDINANAREAWHERELEAKAGEFROMTHEHEATEROR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENTAREAORTOLOWERFLOORSOFTHESTRUCTURE WHEN SUCH LOCATIONS CANNOT BEAVOIDED ASUITABLE DRAINPANSHOULDBEIN...

Страница 7: ...protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with these heaters This water heater must be vente...

Страница 8: ...ell Excessive pressure may develop in such closed systems causing premature tank failure or intermittent relief valve operation This is not a warranty failure An expansion tank or a similar device may...

Страница 9: ...THAT ALL GAS PIPE IS CLEANONTHEINSIDE TOTRAPANYDIRTORFOREIGNMATERIALINTHEGASSUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIMENT TRAP OR DRIP LEG MUST BE INCORPORATED IN THE PIPING SEE FIG 9 THE DIRT LEG...

Страница 10: ...with the latest version of the National Electrical Code ANSI NFPA No 70 must FIGURE10 SINGLEUNITWIRINGDIAGRAM conform to all local code authority having jurisdiction AN ELECTRICAL GROUND IS REQUIRED...

Страница 11: ...temperature and pressure relief valve of adequate capacity is installed on the heater The locations shown in the installation diagrams on the following pages are typical The discharge opening of the t...

Страница 12: ...D NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FO...

Страница 13: ...E TOGGLESWITCHMUSTBECLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOTOPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALLLINETEMPERATURECONTROLINANUNINSULATED TEEBEYONDTHEDISHWASHINGMACH...

Страница 14: ...ons shown in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of...

Страница 15: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 16: ...RS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEA...

Страница 17: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Страница 18: ...in burner before going into lockout After the controller tries three times it will wait one hour before trying to light the unit again This cycle will continue until the main burners are ignited or th...

Страница 19: ...tes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go on to the next step 7 Turn gas control knob counterclockwise to ON...

Страница 20: ...INJURYOCCURS VARIES WITH THE PERSON S AGE AND TIME OF EXPOSURE THE SLOWER RESPONSETIMEOFCHILDREN AGEDORDISABLEDPERSONS INCREASES THE HAZARDS TO THEM NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP...

Страница 21: ...o decrease gas pressure and input rate 4 Clock the meter as in step 2 above 5 Repeat steps 3 and 4 until the specified input rate is achieved 6 Turn the gas control knob to PILOT Remove the pressure g...

Страница 22: ...for cleaning inspection or removal of inner parts you obtain two new nipple collars part no 74060 The nipple collars on the heater will usually be damaged when removed New pipe collars will insure th...

Страница 23: ...sed DELIMINGUSINGFLO JUGMETHOD UN LIME in the 5 gallon size is recommended for deliming of the BT 80 100 models UN LIME with the necessary hoses and fittings to delime your heater is also available as...

Страница 24: ...luding the complete model and serial number as it appears on the product Refer to the parts list for more information REPLACEMENT PARTS 7 Lower container you may have to place the container on its emp...

Страница 25: ...engages Prover Switch Ignition Control Board provides power to Silicon Nitride Ignitor Silicon Nitride Ignitor warms up for 20 seconds Ignition Control Board opens Gas Valve Ignition Control Board sh...

Страница 26: ...Replace dual bulb controller if differential is too wide greater than 4 F Heater recovery is slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Dra...

Страница 27: ...valves etc is installed in the cold water supply the heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times T...

Страница 28: ...28 A O SMITH WATER PRODUCTS COMPANY 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www aosmithwaterheaters com E MAIL parts hotwater com...

Отзывы: