OPERATIONAL CHECKLIST

This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERATION” should be used as an on-the-job
troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction.  Because
improper piping and wiring can result in unsatisfactory system performance, it is suggested that the installation be examined
before using the checklist.  Be sure to refer to the correct piping and wiring diagram for the type of system that is installed.

The system should be filled with water, purged of air, valves properly set and utilities connected and ready to operate.

                                                   

REMEDY

COMPLAINT

                CAUSE

                     USER

                     SERVICEMAN

*Water not hot enough.

Thermostat set too low.

Set thermostat dial to a higher

temperature.

Thermostat out of calibration.

Call serviceman

Recalibrate thermostat.  If thermostat cannot

be recalibrated, replace.

*Insufficient hot water

Thermostat set too low.

Set thermostat dial to a higher

*See WATER TEMPERATURE

temperature.

CONTROL WARNING (on

Page 20).

Thermostat out of calibration.

Call serviceman.

Recalibrate thermostat.  If thermostat cannot

be recalibrated, replace.

Main manual gas shutoff

Open main manual gas shutoff

valve partially closed.

valve to fullest extent.

Heater too small for demand.

Space usage to give heater time

to restore water temperature.

Thermostat differential is

Call serviceman.

Replace dual bulb controller if differential is

too wide.

greater than 4°F.

Heater recovery is slower.

Call serviceman.

Check gas input. If incorrect, adjust gas

pressure or replace main burner orifice.

Drafthood not installed or

Call serviceman.

Install drafthood or baffles as furnished

one or more flue baffles.

with unit.

Water temperature too hot.

Thermostat set too high.

Set thermostat to a lower setting.

Heater makes sounds: sizzling.

Condensation on outside

of tank, normal.

Rumbling.

Sediment accumulation on

Drain  a  quantity  of water through

Delime heater.

bottom of tank.

drain valve. If rumbling persists,

call a serviceman.

Ticking or metallic sounds.

Expansion  and  contraction-

normal.

Pounding.

Air chambers in piping have

Drain piping system and refill.

become waterlogged.

Heater must be off while this is

being done.

Combustion noises.

Too much primary air.

Adjust shutters.

Overfired heater; Incorrect

Call serviceman.

Check and correct as necessary.

burners or orifice for type

of gas used.

Water leaks.

Drain valve not closed

If drain valve cannot be closed

 tightly.

tightly, replace.

If  leakage  source  cannot

Shut  off  gas  supply  to  heater

Repair or in case of suspected tank leakage,

be corrected or identified,

and close cold water inlet valve

be certain to confirm before replacing heater.

call serviceman.

to heater.

Gas odors.

Heater is overfired.

Shut off gas supply to heater

Check for sooted flue passage.

and call a serviceman.

Check for obstructed vent line.

Check backdraft or lack of draft.

Possible gas leaks.

Shut off gas supply to heater and
call gas company at once.

Содержание BTR 151 THRU 201/A

Страница 1: ...in U S A 1004 PART NO 196308 001 ADIVISION OFA O SMITH CORPORATION McBEE SOUTH CAROLINA USA www aosmithwaterheaters com CAUTION TEXT IN BLACK BOLD TYPE OR UNDERLINED CONTAINS INFORMATION RELATIVE TO Y...

Страница 2: ...the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and the National Electrical Code NFPA 70 documents are available fro...

Страница 3: ...ater is due to a corrosive atmosphere Refer to the limited warranty for complete terms and conditions IMPROPER COMBUSTION WARNING ATTICAND OREXHAUSTFANSOPERATINGONTHEPREMISES WITHAWATER HEATER CAN RES...

Страница 4: ...the heater input rate should be reduced at high altitudes for satisfactory operation with the reduced oxygen supply Failure to make this reduction would result in an overfiring of the heater causing s...

Страница 5: ...R BLOWER ASSEMBLY All units are equipped with a exhaust inducer The inducer assists in drawing in fresh air to the unit for combustion and then assists in dispensing the combustion by products into th...

Страница 6: ...D BE LOCATEDINANAREAWHERELEAKAGEFROMTHEHEATEROR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENTAREAORTOLOWERFLOORSOFTHESTRUCTURE WHEN SUCH LOCATIONS CANNOT BEAVOIDED ASUITABLE DRAINPANSHOULDBEIN...

Страница 7: ...protected from freezing downdrafts Remove all soot or other obstructions from the chimney that will retard a free draft Type B venting is recommended with these heaters This water heater must be vente...

Страница 8: ...ell Excessive pressure may develop in such closed systems causing premature tank failure or intermittent relief valve operation This is not a warranty failure An expansion tank or a similar device may...

Страница 9: ...THAT ALL GAS PIPE IS CLEANONTHEINSIDE TOTRAPANYDIRTORFOREIGNMATERIALINTHEGASSUPPLY LINE A DIRT LEG SOMETIMES CALLED SEDIMENT TRAP OR DRIP LEG MUST BE INCORPORATED IN THE PIPING SEE FIG 9 THE DIRT LEG...

Страница 10: ...with the latest version of the National Electrical Code ANSI NFPA No 70 must FIGURE10 SINGLEUNITWIRINGDIAGRAM conform to all local code authority having jurisdiction AN ELECTRICAL GROUND IS REQUIRED...

Страница 11: ...temperature and pressure relief valve of adequate capacity is installed on the heater The locations shown in the installation diagrams on the following pages are typical The discharge opening of the t...

Страница 12: ...D NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FO...

Страница 13: ...E TOGGLESWITCHMUSTBECLOSED ON DURING THERINSEOPERATIONANDOPEN OFF WHENDISHWASHER IS NOTOPERATING OR WHEN ON LONG STANDBY NOTE 2 INSTALLLINETEMPERATURECONTROLINANUNINSULATED TEEBEYONDTHEDISHWASHINGMACH...

Страница 14: ...ons shown in the installation diagrams on the following pages are typical TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION The discharge opening of...

Страница 15: ...TE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK PIPE RELIEF VALVE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES CIRCULATING RETURN LINE...

Страница 16: ...RS WITH MIXING VALVE TWO PRE HEATERS WITH BOOSTER HEATER DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 20 IF HIGHER PREHEA...

Страница 17: ...STER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE RELIEF VALVE TO OPEN DRAIN WHEN USING AN A O SMITH T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 OPENING FOR TANK TEMPERAT...

Страница 18: ...in burner before going into lockout After the controller tries three times it will wait one hour before trying to light the unit again This cycle will continue until the main burners are ignited or th...

Страница 19: ...tes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go on to the next step 7 Turn gas control knob counterclockwise to ON...

Страница 20: ...INJURYOCCURS VARIES WITH THE PERSON S AGE AND TIME OF EXPOSURE THE SLOWER RESPONSETIMEOFCHILDREN AGEDORDISABLEDPERSONS INCREASES THE HAZARDS TO THEM NEVER ALLOW SMALL CHILDREN TO USE A HOT WATER TAP...

Страница 21: ...o decrease gas pressure and input rate 4 Clock the meter as in step 2 above 5 Repeat steps 3 and 4 until the specified input rate is achieved 6 Turn the gas control knob to PILOT Remove the pressure g...

Страница 22: ...for cleaning inspection or removal of inner parts you obtain two new nipple collars part no 74060 The nipple collars on the heater will usually be damaged when removed New pipe collars will insure th...

Страница 23: ...sed DELIMINGUSINGFLO JUGMETHOD UN LIME in the 5 gallon size is recommended for deliming of the BT 80 100 models UN LIME with the necessary hoses and fittings to delime your heater is also available as...

Страница 24: ...luding the complete model and serial number as it appears on the product Refer to the parts list for more information REPLACEMENT PARTS 7 Lower container you may have to place the container on its emp...

Страница 25: ...engages Prover Switch Ignition Control Board provides power to Silicon Nitride Ignitor Silicon Nitride Ignitor warms up for 20 seconds Ignition Control Board opens Gas Valve Ignition Control Board sh...

Страница 26: ...Replace dual bulb controller if differential is too wide greater than 4 F Heater recovery is slower Call serviceman Check gas input If incorrect adjust gas pressure or replace main burner orifice Dra...

Страница 27: ...valves etc is installed in the cold water supply the heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times T...

Страница 28: ...28 A O SMITH WATER PRODUCTS COMPANY 5621 W 115TH STREET ALSIP ILLINOIS 60803 PHONE 1 800 433 2545 FAX 1 800 433 2515 www aosmithwaterheaters com E MAIL parts hotwater com...

Отзывы: