5

The heater is design certified by the Canadian Standards for installation
on combustible flooring in a closet having minimum clearances from
combustible material of: 2" clearance from sides and rear, 6" from the
front and 24" from the top.  (Standard clearance.)  If clearances stated
on the heater differ from standard clearances, install water heater
according to clearances stated on heater.

A minimum clearance of 4" must be allowed for access to replaceable
parts such as the thermostats, drain valve and relief valve.  A top
clearance of 24" should be allowed for blower assembly service.

Adequate clearance for servicing this appliance should be considered
before installation, such as changing the anodes, etc.  Minimum
clearances for proper operation are given above.

 WARNING

In cold climates provide protection against freeze-up.

THE HEATER SHOULD BE LOCATED IN AN AREA WHERE LEAKAGE OF
THE TANK OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE
AREA ADJACENT TO THE HEATER OR TO LOWER FLOORS OF THE
STRUCTURE.

  When such locations cannot be avoided, a suitable drain

pan should be installed under the heater, see fig. 1.  The pan must not
restrict combustion air flow.  Such pans should have a minimum length
and width of at least 2 inches greater than the diameter of the heater
and should be piped to an adequate drain.  Drain pans suitable for these
heaters are available from your dealer or A. O. Smith Water Products
Company, 5621 W. 115th Street, Alsip, Illinois 60803.

 WARNING

DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED
FLOOR.  A FIRE HAZARD MAY RESULT.

  Instead the water heater must

be placed on a metal or wood panel extending beyond the full width and
depth by at least 3 inches (76.2mm) in any direction.  If the heater is
installed in a carpeted alcove or closet, the entire floor shall be covered
by the panel.

AIR REQUIREMENTS

In calculating the free area of a vent opening, the blocking effect of
screens, louvers and grills should be considered.  Screens shall not be
of a mesh smaller than 1/4 inch square.  If the free area is not known,
the latest edition of National Fuel Gas Code ANSI Z223.1 recommends
using figures of 20-25 percent free area for wood louvers or 60-75
percent for metal grills or louvers.

UNCONFINED SPACE

In buildings of conventional frame, brick or stone construction, unconfined
spaces may provide adequate air for combustion, ventilation, and dilution
air for power venter.

If the unconfined space is within a building of tight construction (building
using the following construction: weather stripping, heavy insulation,
caulking, vapor barrier, etc.), air for combustion, ventilation, and venter
dilution must be obtained from outdoors.  The installation instructions for
confined spaces must be followed.

CONFINED SPACE

When drawing combustion and dilution air from inside a conventionally
constructed building to a confined space, such a space shall be provided
with two permanent openings.  ONE  WITHIN 12 INCHES OF THE
ENCLOSURE TOP AND ONE WITHIN 12 INCHES OF THE ENCLOSURE
BOTTOM.  Each opening shall have a free area of one square inch per
1000 Btuh of the total input of all appliances in the enclosure, but not
less than 100 square inches.

If the confined space is within a building of tight construction, air for
combustion, ventilation and power venter dilution must be obtained from
outdoors.  When directly communicating with the outdoors or
communicating through vertical ducts, two permanent openings, located
in the above manner, shall be provided.  Each opening shall have a free
area of not less than one square inch per 4000 Btuh of the total input of
all appliances in the enclosure.  If horizontal ducts are used, each opening
shall have a free area of not less than one square inch per 2000 Btuh of
the total input of all appliances in the enclosure.

 

WATER CONNECTIONS

Refer to figure 12 for typical installation.  A suitable pipe thread sealant
must be used to prevent leakage.

WATER (POTABLE) HEATING AND SPACE

HEATING

1. All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

2. Toxic chemicals, such as those used for boiler treatment, shall NEVER

be introduced into this system.

3. This unit may NEVER be connected to any existing heating system or

component(s) previously used with a non-potable water heating
appliance.

4. When the system requires water for space heating at temperatures

higher than required for domestic water purposes, a tempering valve
must be installed.  Please refer to Fig. 2 for suggested piping
arrangement.

Содержание BTF-75

Страница 1: ...Y BEFORE INSTALLING AND USING THIS APPLIANCE A DIVISION OF A O SMITH CORPORATION McBee South Carolina U S A Stratford Ontario Canada www hotwater com KEEP THIS MANUAL IN THE POCKET ON THE HEATER FOR F...

Страница 2: ...tions and the local code authority having jurisdiction In the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 The NFPA Th...

Страница 3: ...ral gas models A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas LP gas must be used with great caution It is highly...

Страница 4: ...in before operating Please refer to manufacturer s instructions DISHWASHING MACHINE REQUIREMENT These appliances meet the National Sanitation Foundation Standard for sanitary installations when used w...

Страница 5: ...60 75 percent for metal grills or louvers UNCONFINED SPACE In buildings of conventional frame brick or stone construction unconfined spaces may provide adequate air for combustion ventilation and dil...

Страница 6: ...TINGMUSTBEFOLLOWED TOAVOIDCHOKEDCOMBUSTIONORRECIRCULATIONOFFLUEGASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION NEVEROPERATETHEHEATERUNLESSITISVENTED TOTHEOUTDOORSANDHASADEQUATEAI...

Страница 7: ...ceed the thirty 30 equivalent feet of 3 inch pipe or eighty five 85 equivalent feet of 4 inch pipe 3 The blower discharge adapter is made to accept only straight sections of 3 pipe To start a minimum...

Страница 8: ...ow be positioned on the outside wall using the drilled hole as a centering point for the template 3 A MASONRYSIDEWALLS Chisel an opening approximately one half inch larger than the marked circle B WOO...

Страница 9: ...tions are not reversed when making these connections See Figure 7 G Replace side panel and secure with two screws 5 The blower discharge adapter is made to accept only straight sections of 3 pipe To s...

Страница 10: ...run All piping and fittings must be joined by the proper procedures as described under VENTPIPEPREPARATION IMPORTANT The vent system must terminate so that proper clearances are maintained as cited i...

Страница 11: ...f the joint Tapered fitting sockets are designed so that an interference fit should occur when the pipe is inserted about 1 3 to 2 3 of the way into the socket Occasionally when pipe fitting dimension...

Страница 12: ...e sparingly and only to the male threads of pipe joints Do not apply compound to the first two threads Use compounds resistant to the action of liquefied petroleum gases Do not use teflon tape on ther...

Страница 13: ...ly counterclockwise until it stops 4 This appliance is equipped with a device which automatically lights the burner DONOTTRYTOLIGHTTHEBURNERBYHAND 5 Wait five 5 minutes to clear out any gas If you the...

Страница 14: ...atures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20...

Страница 15: ...n etc For safety and satisfactory operation it is recommended that the heater be checked once a year by a competent service person T P VALVE At least once a year the temperature and pressure relief va...

Страница 16: ...e service you received First please contact your dealer or the A O Smith authorized service agent in your area and explain to them why you are not satisfied This will usually correct the problem If af...

Страница 17: ...ch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more tha...

Страница 18: ...connectors 3 System wiring harness in good condition and securely connected at both ends Not Applicable 1 Replace control 1 Airflow proving switch stuck closed 2 Airflow proving switch mis wired or ju...

Страница 19: ...E AT HSI ELEMENT OUTPUT SEE INSET B 120V NOMINAL CHECK DAMAGED OR BROKEN HSI ELEMENT WARNING Line Voltage Hazard Can cause property damage severe injury or death Only a trained experienced service tec...

Страница 20: ...all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipping delivery handling and a...

Отзывы: