16

Should the main burner or burner air openings require cleaning, remove
the burner and clean with a soft brush.  Clean main burner orifice with a
suitable soft material.

CHECK FOR GOOD FLOW OF COMBUSTION AND VENTILATING AIR TO
THE UNIT.  MAINTAIN A CLEAR OPEN AREA AROUND THE HEATER AT
ALL TIMES.  DO NOT STORE COMBUSTIBLES OR FLAMMABLE LIQUIDS
NEAR OR AROUND AN APPLIANCE.

      

  FIGURE 12 - MAIN BURNER AND IGNITER ASSEMBLY

CONDENSATION

Water vapor can condense on the cooler surfaces of the tank forming
droplets, these drip into the fire or run out on the floor.  This is common
at the time of startup after installation, during periods of time when
incoming water is very cold, or the heater may be undersized for the
requirements.

Droplets from the bottom of the flue may be due to corrosive combustion
products or improper vent.  Check with your dealer for more information.

CATHODIC PROTECTION-ANODE

The anode rod within the tank is designed to be slowly consumed
cathodically, minimizing corrosion in the glass lined tank.  A hydrogen
sulfide (rotten egg) odor may result if water contains high sulfate and/or
minerals.  Chlorinating the water supply should minimize the problem.
(See EXTENDED NON-USE PERIODS).

NOTE: Anode must remain installed (except for inspection) to avoid
shortening tank life.  See LIMITED WARRANTY.  Replace as necessary.

SERVICE AND REPAIR

The A.O. Smith water heater requires no special care other than the
normal maintenance as noted above.  If you are having a problem with
your water heater, before calling for service please refer to the following
TROUBLESHOOTING sections.  If service becomes necessary, contact
your dealer, installer or an authorized service agent.  Do not attempt to
repair the water heater yourself.  Any work performed by unauthorized
personnel may void the warranty.

If you are having a problem with your A.O. Smith water heater and are
not pleased with the service you received:

First, please contact your dealer or the A.O. Smith authorized service
agent in your area and explain to them why you are not satisfied.
This will usually correct the problem.

If after working with your dealer or service agent the problem has
not been resolved to your satisfaction, please let us know by either
writing to us at:

A.O. Smith Water Products Company
Service Department
600 East John Carpenter Freeway
Rochelle Park, Suite 200
Irving, TX  75038

or, going to our website at:  www.hotwater.com
Please click on:  "Mail",
then click on:  "Service"
and leave us a message.

Please be sure to provide the following information when writing or
 e-mailing:

Model Number

Serial Number

Date of Original Purchase

Date Problem Originated

Explanation of Problem

Also, please be sure to include a daytime telephone number.

TROUBLE SHOOTING

Water heater may exhibit problems that are unrelated to a malfunction of
the water heater itself.  The following information and tables may serve
to answer your question about a problem that you are having without
having to call a service agent.

For your safety, water heater service should be performed only by a
qualified service technician.  Read the GENERAL SAFETY INFORMATION
section first.

WATER HEATING CYCLE

(GAS AND ELECTRIC POWER ARE ON, “OFF/ON” SWITCH IS ON)

1) SMARTVALVE

®

 (1) CALLS FOR HEAT (SEE FIGURES 7 &12)

A)  THERMOSTAT SENSES NEED FOR HEATING WATER

B)  CONTACTS CLOSE IN THERMOSTAT, POWER (115 VAC)
      FLOWS TO BLOWER MOTOR

2) BLOWER MOTOR ROTATES BLOWER WHEEL

A)  BLOWER WHEEL SPEED INCREASES

B)  WHEEL SPEED INCREASES, AIR PRESSURE SWITCH
      CONTACTS CLOSE

3) 120 VAC FLOWS TO HOT SURFACE IGNITER

NOTE: THE CONTROL MODULE ON THIS UNIT WILL TRY A MAXIMUM OF
THREE TIMES TO LIGHT THE UNIT.  CYCLE CAN BE RESTARTED AT ANY
TIME BY TURNING OFF SWITCH AND THEN TURNING BACK ON.  IF UNIT
HAS GONE THROUGH THREE CYCLES AND DID NOT LIGHT, THEN
REPAIRMAN SHOULD BE CALLED TO CHECK OPERATION OF HEATER.

4) MAIN BURNER IGNITES

A)  GAS FLOWS TO MAIN BURNER PORTS AND IS IGNITED

5) GAS VALVE SENSES BURNER FLAME

6) BURNER HEATS WATER

A)  BURNER HEATS WATER TO THERMOSTAT SETTING

B)  CONTACTS IN THERMOSTAT OPEN,

C)  CYCLE IS COMPLETED

IGNITER

MAIN BURNER

Содержание BTF-75

Страница 1: ...Y BEFORE INSTALLING AND USING THIS APPLIANCE A DIVISION OF A O SMITH CORPORATION McBee South Carolina U S A Stratford Ontario Canada www hotwater com KEEP THIS MANUAL IN THE POCKET ON THE HEATER FOR F...

Страница 2: ...tions and the local code authority having jurisdiction In the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 The NFPA Th...

Страница 3: ...ral gas models A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas LP gas must be used with great caution It is highly...

Страница 4: ...in before operating Please refer to manufacturer s instructions DISHWASHING MACHINE REQUIREMENT These appliances meet the National Sanitation Foundation Standard for sanitary installations when used w...

Страница 5: ...60 75 percent for metal grills or louvers UNCONFINED SPACE In buildings of conventional frame brick or stone construction unconfined spaces may provide adequate air for combustion ventilation and dil...

Страница 6: ...TINGMUSTBEFOLLOWED TOAVOIDCHOKEDCOMBUSTIONORRECIRCULATIONOFFLUEGASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION NEVEROPERATETHEHEATERUNLESSITISVENTED TOTHEOUTDOORSANDHASADEQUATEAI...

Страница 7: ...ceed the thirty 30 equivalent feet of 3 inch pipe or eighty five 85 equivalent feet of 4 inch pipe 3 The blower discharge adapter is made to accept only straight sections of 3 pipe To start a minimum...

Страница 8: ...ow be positioned on the outside wall using the drilled hole as a centering point for the template 3 A MASONRYSIDEWALLS Chisel an opening approximately one half inch larger than the marked circle B WOO...

Страница 9: ...tions are not reversed when making these connections See Figure 7 G Replace side panel and secure with two screws 5 The blower discharge adapter is made to accept only straight sections of 3 pipe To s...

Страница 10: ...run All piping and fittings must be joined by the proper procedures as described under VENTPIPEPREPARATION IMPORTANT The vent system must terminate so that proper clearances are maintained as cited i...

Страница 11: ...f the joint Tapered fitting sockets are designed so that an interference fit should occur when the pipe is inserted about 1 3 to 2 3 of the way into the socket Occasionally when pipe fitting dimension...

Страница 12: ...e sparingly and only to the male threads of pipe joints Do not apply compound to the first two threads Use compounds resistant to the action of liquefied petroleum gases Do not use teflon tape on ther...

Страница 13: ...ly counterclockwise until it stops 4 This appliance is equipped with a device which automatically lights the burner DONOTTRYTOLIGHTTHEBURNERBYHAND 5 Wait five 5 minutes to clear out any gas If you the...

Страница 14: ...atures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20...

Страница 15: ...n etc For safety and satisfactory operation it is recommended that the heater be checked once a year by a competent service person T P VALVE At least once a year the temperature and pressure relief va...

Страница 16: ...e service you received First please contact your dealer or the A O Smith authorized service agent in your area and explain to them why you are not satisfied This will usually correct the problem If af...

Страница 17: ...ch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more tha...

Страница 18: ...connectors 3 System wiring harness in good condition and securely connected at both ends Not Applicable 1 Replace control 1 Airflow proving switch stuck closed 2 Airflow proving switch mis wired or ju...

Страница 19: ...E AT HSI ELEMENT OUTPUT SEE INSET B 120V NOMINAL CHECK DAMAGED OR BROKEN HSI ELEMENT WARNING Line Voltage Hazard Can cause property damage severe injury or death Only a trained experienced service tec...

Страница 20: ...all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipping delivery handling and a...

Отзывы: