NOT ENOUGH OR

NO HOT WATER

VENT PIPE TOO HOT

(ABOVE 170° F)

YELLOW FLAME

CONDENSATION

WATER LEAKS

LEAKING T&P VALVE

HOT  WATER  ODORS  OR  COLOR

(Refer to CATHODIC PROTECTION)

PROBLEM

POSSIBLE MALFUNCTION

        SERVICE TO BE PERFORMED

1) Blower will not run

A ) “ON/OFF” control switch turned off
B) Blower unplugged
C) No power at outlet
D) “ON/OFF” switch defective
E)

Control harness defective

F)

Blower motor defective

2) Blower running, burner not on

A ) Fan not running fast enough to close

air switch contacts

B) Air pressure switch defective
C) Gas valve defective
D) Control harness defective
E)

Igniter defective

F)

Unit has completed three trials to light
and failed

G) Discharge air limit tripped

3) Thermostat problems

A ) Thermostat set too low
B) Thermostat or ECO defective
C) High limit control circuit open

4) Others

A ) Heater undersized
B) Low gas pressure
C) Incoming water is unusually cold
D) Leaking hot water pipes or fixtures
A ) Blower does not run when heater fired

B) Not enough dilution air to mix with flue

 gases in “Tee”

C) Air in room too hot for mixing with flue gases

D) Wrong burner orifice
A ) Dirt in burner ports
B) Combustion air path restricted

C) Not enough room air for proper combustion

A ) Water on the floor under heater
B) Water dripping from fan

Improperly sealed, hot or cold supply connections,
relief valve, drain valve or thermostat threads
Leakage from other appliances or water lines
Condensation of flue products
Thermal expansion in closed water system
Improperly seated valve
High sulfate or mineral content in water supply or
iron or sulfate reducing bacteria in water supply

TROUBLESHOOTING

For your safety, water heater service should be performed only by a qualified service technician.

Read the GENERAL SAFETY INFORMATION section first.

  WARNING: DO NOT BY-PASS ANY CONTROLS TO MAKE HEATER OPERATE. OPERATE ONLY AS WIRED FROM FACTORY.

Turn switch to the “ON” position.
Plug blower back into 115 vac. outlet.
Repair service to outlet.
Replace switch.
Replace control harness.
Replace blower and motor.
Replace switch.
Check for low voltage, less than 102 vac., have service
checked and repaired.
If voltage is above 102 vac., make sure there is not more than
30 Equivalent feet of 3 inch pipe or 85 equivalent feet of 4 inch
pipe installed or vent terminal blockage.
If at least 102 vac., less than 30 equivalent feet of 3 inch pipe
or 85 equivalent feet of 4 inch pipe and not terminal blockage,
replace blower.
Replace switch.
Replace gas valve.
Replace harness.
Replace igniter.
Reset cycle by turning switch off and then back on. If unit
does not light in three trials, call an authorized A.O. Smith
service representative.
Verify dilution air openings are free of obstructions.
Make sure there is no more than 30 equivalent feet of 3 inch pipe or
85 equivalent feet of 4 inch pipe.
Check for low voltage, less than 102 vac., have service
checked and repaired.
Make sure vent terminal is not blocked.

Turn temperature control higher.
Replace thermostat.
Replace.

Reduce hot water use.
Contact an authorized A.O. Smith service representative.
Allow more time for heater to re-heat.
Have plumber check and repair leaks.
Take unit out of service immediately, call an authorized A.O.
Smith service representative.
Proper air circulation must be provided for combustion and
dilution of flue temp. Refer to “INSTALLATION” section.
Room air to be used for dilution with combustion products in
flue should be less than 90°F.
Install correct orifice.
Turn off heater and gas, clean burner head.
Clear area around heater and check under heater, remove
any debris under heater and in openings in bottom cover.
Refer to installation manual - Confined and Unconfined Space
statements on page 4 and 5 for required openings.
See “CONDENSATION.”
Provide drip “TEE” to catch condensation, refer to pages 8 and 10.
Turn off heater & water, repair unit.

Inspect other appliances near water heater.
Refer to “CONDENSATION.”
Install thermal expansion tank (DO NOT plug T&P valve).
Check relief valve for proper operation (DO NOT plug T&P valve).
Drain and flush heater thoroughly, chlorinate, refill and flush
again then chlorinate water supply.

Содержание BTF-75

Страница 1: ...Y BEFORE INSTALLING AND USING THIS APPLIANCE A DIVISION OF A O SMITH CORPORATION McBee South Carolina U S A Stratford Ontario Canada www hotwater com KEEP THIS MANUAL IN THE POCKET ON THE HEATER FOR F...

Страница 2: ...tions and the local code authority having jurisdiction In the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 The NFPA Th...

Страница 3: ...ral gas models A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas LP gas must be used with great caution It is highly...

Страница 4: ...in before operating Please refer to manufacturer s instructions DISHWASHING MACHINE REQUIREMENT These appliances meet the National Sanitation Foundation Standard for sanitary installations when used w...

Страница 5: ...60 75 percent for metal grills or louvers UNCONFINED SPACE In buildings of conventional frame brick or stone construction unconfined spaces may provide adequate air for combustion ventilation and dil...

Страница 6: ...TINGMUSTBEFOLLOWED TOAVOIDCHOKEDCOMBUSTIONORRECIRCULATIONOFFLUEGASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION NEVEROPERATETHEHEATERUNLESSITISVENTED TOTHEOUTDOORSANDHASADEQUATEAI...

Страница 7: ...ceed the thirty 30 equivalent feet of 3 inch pipe or eighty five 85 equivalent feet of 4 inch pipe 3 The blower discharge adapter is made to accept only straight sections of 3 pipe To start a minimum...

Страница 8: ...ow be positioned on the outside wall using the drilled hole as a centering point for the template 3 A MASONRYSIDEWALLS Chisel an opening approximately one half inch larger than the marked circle B WOO...

Страница 9: ...tions are not reversed when making these connections See Figure 7 G Replace side panel and secure with two screws 5 The blower discharge adapter is made to accept only straight sections of 3 pipe To s...

Страница 10: ...run All piping and fittings must be joined by the proper procedures as described under VENTPIPEPREPARATION IMPORTANT The vent system must terminate so that proper clearances are maintained as cited i...

Страница 11: ...f the joint Tapered fitting sockets are designed so that an interference fit should occur when the pipe is inserted about 1 3 to 2 3 of the way into the socket Occasionally when pipe fitting dimension...

Страница 12: ...e sparingly and only to the male threads of pipe joints Do not apply compound to the first two threads Use compounds resistant to the action of liquefied petroleum gases Do not use teflon tape on ther...

Страница 13: ...ly counterclockwise until it stops 4 This appliance is equipped with a device which automatically lights the burner DONOTTRYTOLIGHTTHEBURNERBYHAND 5 Wait five 5 minutes to clear out any gas If you the...

Страница 14: ...atures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20...

Страница 15: ...n etc For safety and satisfactory operation it is recommended that the heater be checked once a year by a competent service person T P VALVE At least once a year the temperature and pressure relief va...

Страница 16: ...e service you received First please contact your dealer or the A O Smith authorized service agent in your area and explain to them why you are not satisfied This will usually correct the problem If af...

Страница 17: ...ch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more tha...

Страница 18: ...connectors 3 System wiring harness in good condition and securely connected at both ends Not Applicable 1 Replace control 1 Airflow proving switch stuck closed 2 Airflow proving switch mis wired or ju...

Страница 19: ...E AT HSI ELEMENT OUTPUT SEE INSET B 120V NOMINAL CHECK DAMAGED OR BROKEN HSI ELEMENT WARNING Line Voltage Hazard Can cause property damage severe injury or death Only a trained experienced service tec...

Страница 20: ...all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipping delivery handling and a...

Отзывы: