background image

18

OFF

BRITE - DM

1 FLASH

2 FLASHES

3 FLASHES

4 FLASHES

5 FLASHES

6 FLASHES

LED STATUS

INDICATES

        CHECK/REPAIR

No power to system control.

Normal Operation

This indication shows whenever the system is
powered, unless some abnormal event has occurred.

Setpoint error, internal failure detected.

Airflow proving switch remains open longer than
30 seconds after a call for heat begins.

Combustion air blower is not energized
until airflow proving switch opens.

Airflow proving switch remains open longer than
30 seconds after combustion air blower energized.

System goes into 5 minute delay period, with
combustion air blower off.  At the end of the
5 minute delay, another ignition cycle will begin.

Thermal Cutoff open.

Combustion air blower is energized.

Internal hardware failure.

Flame signal sensed out of proper sequence.

Combustion air blower is energized.

System Lockout.

After 1 hour lockout reset delay, control will reset
and initiate a new ignition sequence if the call for
heat is still present.

1. Appliance On/Off switch in the Off position.
2. Line voltage input power at L1 and L2 connectors.
3. System wiring harness in good condition and securely

connected at both ends.

Not Applicable.

1. Replace control.

1. Airflow proving switch stuck closed.
2. Airflow proving switch mis-wired or jumpered.

WARNING

Line Voltage Hazard.
Can cause property damage, severe injury or
death.

Turn off appliance before coming in contact with
pressure switch and/or electrical connections.

1. Airflow proving switch operation, tubing and wiring.
2. Obstructions or restrictions in appliance air intake

or exhaust flue system that prevent proper combustion
air flow.

WARNING

Line Voltage Hazard.
Can cause property damage, severe injury or
death.

Turn off appliance before coming in contact with
pressure switch and/or electrical connections.

1. Replace Control.

1. Flame at main burner.

2. Replace control.

1. Gas supply off or at too low pressure to operate.
2. Damaged or broken HSI element.
3. Appliance not properly earth grounded.
4. Flame sense rod contaminated or in incorrect location.
5. HSI element located incorrect position.
6. HSI element or flame sense rod wiring in good

condition and properly connected.

7. Less than 100 Vac between flame rod and burner

pan with 120 Vac input to control.

8. Cycle external power or remove request for heat for

2 seconds and reapply.

TROUBLESHOOTING WITH THE LED

Содержание BTF-75

Страница 1: ...Y BEFORE INSTALLING AND USING THIS APPLIANCE A DIVISION OF A O SMITH CORPORATION McBee South Carolina U S A Stratford Ontario Canada www hotwater com KEEP THIS MANUAL IN THE POCKET ON THE HEATER FOR F...

Страница 2: ...tions and the local code authority having jurisdiction In the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 The NFPA Th...

Страница 3: ...ral gas models A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas LP gas must be used with great caution It is highly...

Страница 4: ...in before operating Please refer to manufacturer s instructions DISHWASHING MACHINE REQUIREMENT These appliances meet the National Sanitation Foundation Standard for sanitary installations when used w...

Страница 5: ...60 75 percent for metal grills or louvers UNCONFINED SPACE In buildings of conventional frame brick or stone construction unconfined spaces may provide adequate air for combustion ventilation and dil...

Страница 6: ...TINGMUSTBEFOLLOWED TOAVOIDCHOKEDCOMBUSTIONORRECIRCULATIONOFFLUEGASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION NEVEROPERATETHEHEATERUNLESSITISVENTED TOTHEOUTDOORSANDHASADEQUATEAI...

Страница 7: ...ceed the thirty 30 equivalent feet of 3 inch pipe or eighty five 85 equivalent feet of 4 inch pipe 3 The blower discharge adapter is made to accept only straight sections of 3 pipe To start a minimum...

Страница 8: ...ow be positioned on the outside wall using the drilled hole as a centering point for the template 3 A MASONRYSIDEWALLS Chisel an opening approximately one half inch larger than the marked circle B WOO...

Страница 9: ...tions are not reversed when making these connections See Figure 7 G Replace side panel and secure with two screws 5 The blower discharge adapter is made to accept only straight sections of 3 pipe To s...

Страница 10: ...run All piping and fittings must be joined by the proper procedures as described under VENTPIPEPREPARATION IMPORTANT The vent system must terminate so that proper clearances are maintained as cited i...

Страница 11: ...f the joint Tapered fitting sockets are designed so that an interference fit should occur when the pipe is inserted about 1 3 to 2 3 of the way into the socket Occasionally when pipe fitting dimension...

Страница 12: ...e sparingly and only to the male threads of pipe joints Do not apply compound to the first two threads Use compounds resistant to the action of liquefied petroleum gases Do not use teflon tape on ther...

Страница 13: ...ly counterclockwise until it stops 4 This appliance is equipped with a device which automatically lights the burner DONOTTRYTOLIGHTTHEBURNERBYHAND 5 Wait five 5 minutes to clear out any gas If you the...

Страница 14: ...atures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 20...

Страница 15: ...n etc For safety and satisfactory operation it is recommended that the heater be checked once a year by a competent service person T P VALVE At least once a year the temperature and pressure relief va...

Страница 16: ...e service you received First please contact your dealer or the A O Smith authorized service agent in your area and explain to them why you are not satisfied This will usually correct the problem If af...

Страница 17: ...ch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and repaired If voltage is above 102 vac make sure there is not more tha...

Страница 18: ...connectors 3 System wiring harness in good condition and securely connected at both ends Not Applicable 1 Replace control 1 Airflow proving switch stuck closed 2 Airflow proving switch mis wired or ju...

Страница 19: ...E AT HSI ELEMENT OUTPUT SEE INSET B 120V NOMINAL CHECK DAMAGED OR BROKEN HSI ELEMENT WARNING Line Voltage Hazard Can cause property damage severe injury or death Only a trained experienced service tec...

Страница 20: ...all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipping delivery handling and a...

Отзывы: