Instruction manual ADMR
72
F06 (lock out error)
Short circuit between
flame probe and earth
Damaged cable in
contact with metal
surface.
Check the wiring of the flame probe. If necessary, replace the
wiring.
If the error persists, contact your installation engineer.
To replace the necessary parts, you must contact your installation
engineer
Ceramic part of the
flame probe is
broken/cracked.
1. Check that the ceramic part of the flame probe is still intact in
the vicinity of the burner's air distribution plate.
2. If not, the flame probe must be replaced.
F07 (lock out error)
A flame has been
detected after the gas
valve was closed.
Defective gas valves
1. Check whether there is still burner pressure present after the
gas valves have closed.
2. Check whether a flame is still present after the gas valves have
closed.
3. If this is the case, the gas control must be replaced.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
F08 (lock out error)
Error message from
safety relay
Flame detection before
the gas valve opened.
1. Reset electronic controller.
2. If the error reappears, replace the electronic controller.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
F09 (lock out error)
Water temperature
safety.
The temperature at the
top of the tank exceeds
93 °C.
1. Check that the circulation pump (if present) is working
2. Check the position of the temperature sensor T
1
.
3. Reset appliance controller
Note
Error “F09” stays active if the water temperature was higher
than 78 °C during the reset. If this is the case, first open the nearest
draw-off point to drain some hot water and allow cold water to run
into the system.
If the error cannot be resolved or is persistent, contact your
installation engineer
F10 (lock out error)
Restriction on the
number of ignition
attempts based on
switching of the flue
damper relay.
Flue damper relay
switching during
demand.
1. Check that the red arrow on the flue damper motor goes fully to
the right and stays in this position during heat demand.
2. Check for physical blockages, and rectify if possible.
3. Check that the voltage on the black lead of the motor controller
continues during heat demand.
4. Check for faulty electrical connections and rectify if possible.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
Symptom
Cause
Solution
Remark
Содержание ADMR - 40
Страница 4: ...4 Instruction manual ADMR gis ...
Страница 10: ...Introduction 10 Instruction manual ADMR 1 gis ...
Страница 54: ...Shutting down 54 Instruction manual ADMR 10 gis ...
Страница 62: ...Main menu 62 Instruction manual ADMR 11 gis ...
Страница 76: ...is Instruction manual ADMR 76 ...
Страница 78: ...Maintenance frequency 78 Instruction manual ADMR 14 is ...
Страница 84: ...Performing maintenance 84 Instruction manual ADMR 15 s ...
Страница 92: ...Appendices 92 Instruction manual ADMR 17 is ...
Страница 94: ...Instruction manual ADMR 94 ...