13.2 Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General errors
Symptom
Cause
Solution
Remark
Gas smell
Gas leak
Close the main gas valve immediately.
Do not operate any switches.
No naked flames.
Ventilate the boiler room.
Contact your installation engineer or local gas company
immediately.
Display is off
Appliance is turned off
Start the appliance up (9 "Starting and running")
No supply voltage
present
1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 V
AC
(-15%, +10%).
See the ADMR electrical diagram (17 "Appendices")
If the error persists, consult your installation engineer.
Defective fuse(s)
Replace fuse(s)
To replace the fuses, you must contact your installation engineer.
Water leakage
Leakage from a water
connection (threaded)
Tighten the threaded connection
If the leak persists, consult your installation engineer
Leakage from another
nearby water appliance
or pipe segment
Trace the leak
Leakage from the
appliance's tank
Consult the supplier and/or manufacturer
Condensation
Before drawing (too much) tap water, wait until the water in the
boiler has reached the set temperature.
Содержание ADMR - 40
Страница 4: ...4 Instruction manual ADMR gis ...
Страница 10: ...Introduction 10 Instruction manual ADMR 1 gis ...
Страница 54: ...Shutting down 54 Instruction manual ADMR 10 gis ...
Страница 62: ...Main menu 62 Instruction manual ADMR 11 gis ...
Страница 76: ...is Instruction manual ADMR 76 ...
Страница 78: ...Maintenance frequency 78 Instruction manual ADMR 14 is ...
Страница 84: ...Performing maintenance 84 Instruction manual ADMR 15 s ...
Страница 92: ...Appendices 92 Instruction manual ADMR 17 is ...
Страница 94: ...Instruction manual ADMR 94 ...